Programmable Controllers C200HX-CPU-ZE, C200HG-CPU-ZE, C200HE-CPU-ZE Operation Manual: SECTION 5 Instruction Set, pages 214 to 223

Pages 214 to 223 of 613, from Programmable Controllers C200HX-CPU-ZE, C200HG-CPU-ZE, C200HE-CPU-ZE Operation Manual

The original document is the PDF (3.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-SP001 and Omron C200HW-PA204

Page 214

Section 5-16

Data Movement Description

When the execution condition is OFF, XFRB(062) is not executed. When the execution condition is ON, XFRB(062) copies the specified source bits to the specified destination bits. The two rightmost digits of C specify the starting bits in S and D and the leftmost two digits indicate the number of bits that will be copied. C MSB

LSB First bit of S (0 to F) First bit of D (0 to F) Number of bits (01 to FF)

Note Up to 255 (FF) bits can be copied at one time. Example

In the following example, XFRB(062) is used to transfer 5 bits from IR 020 to LR 21 when IR 00001 is ON. The starting bit in IR 020 is 0, and the starting bit in LR 21 is 4, so IR 02000 to IR 02004 are copied to LR 2104 to LR 2108. 00001 XFRB(062) #0540 IR 020

Address

Instruction

00000 00001

LD XFRB(062)

Operands

#0540 020 LR 21

LR 21

Bit 00

Bit 15

S (IR 020)

0 1 0 1 0 1 0 0 0 0 0 1 0 1 1 1

Bit 00

Bit 15

D (LR 21) Flags

ER:

00001

0 1 0 0 0 1 0 1 0 1 1 1 0 0 0 1

The specified source bits are not all in the same data area. The specified destination bits are not all in the same data area. The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

5-16-11 EM BLOCK TRANSFER – XFR2(––) Operand Data Areas N: Number of words (BCD)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # XFR2(––)

@XFR2(––)

N

N

S

S

D

D

S: Starting source word

Limitations

202

IR, SR, AR, DM, EM, HR, TC, LR, # D: Starting destination word IR, SR, AR, DM, EM, HR, TC, LR, #

S and S+N must be in the same data area, as must D and D+N. N must be BCD. XFR2(––) is an expansion instruction. A Programming Device must be used to assign a function code to XFR2(––) in order to use this instruction.

Page 215

Section 5-16

Data Movement Description

When the execution condition is OFF, XFR2(––) is not executed. When the execution condition is ON, XFR2(––) copies the contents of S, S+1, ..., S+N to D, D+1, ..., D+N. If a constant is used for S or D, the constant specifies an address in the current EM bank.

Flags

ER:

N is not BCD. S and S+N or D and D+N are not in the same data area. The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

Example

The following example copies the contents of the 300 words from DM 0000 through DM 0299 to EM 2000 through EM 2299 in the current EM bank. 00000 XFR2(––) #0300

Address

Instruction

00200 00201

LD XFR2(––)

Operands 00000 #0300 DM 0000 #2000

DM 0000 #2000

5-16-12 BLOCK TRANSFER TO OTHER EM BANK – BXF2(––) Operand Data Areas C: First control word

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR BXF2(––)

@BXF2(––)

C

C

S

S

D

D

S: Starting source word

Limitations

IR, SR, AR, DM, EM, HR, TC, LR, # D: Starting destination word IR, SR, AR, DM, EM, HR, TC, LR, #

The value in C+1 must be BCD from 1 to 6144. S and S+N must be in the same data area, as must D and D+N. BXF2(––) is an expansion instruction. A Programming Device must be used to assign a function code to BXF2(––) in order to use this instruction.

Description

When the execution condition is OFF, BXF2(––) is not executed. When the execution condition is ON, BXF2(––) copies the contents of S, S+1, ..., S+N to D, D+1, ..., D+N. The bank can be specified (in C) if an EM area address is used for S or D. If a constant is used for S or D, the constant specifies an address in the source or destination EM bank specified in C.

Control Words

C contains the source and destination bank numbers if data is being transferred to or from EM. The bank numbers are ignored unless an EM area address or a constant is used for S or D. C+1 contains the number of words to transfer and must be BCD (1 to 6144). Control word Bits C 0 to 7 8 to 15 C+1 0 to 15

Function Specifies the source bank number (00 to 0F). Specifies the destination bank number (00 to 0F). Specifies the number of words to transfer (1 to 6144).

203

Page 216

Section 5-16

Data Movement Flags

ER:

N is not BCD. S and S+N or D and D+N are not in the same data area. The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded. The bank indicated by C does not exists when an EM area address is being used.

Example

The following example copies the contents of the 300 words from DM 0000 through DM 0299 to EM 2000 through EM 2299 in the EM bank 01. (The source bank number is ignored because an EM area address has not been used for it.) 00000 BXF2(––) DM 1000

Address

Instruction

00200 00201

LD BXF2(––)

Operands 00000 DM 1000 DM 0000 #2000

DM 0000 #2000

C: DM 1000 0

1

0

C+1: DM 1001 0

0

Source bank number (00)

3

0

0

Number of words (300)

Destination bank number (01)

5-16-13 EM BANK TRANSFER – BXFR(125) Operand Data Areas C: First control word

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR BXFR(125)

@BXFR(125)

C

C

S

S

D

D

S: Starting source word IR, SR, AR, DM, EM, HR, TC, LR D: Starting destination word IR, SR, AR, DM, EM, HR, TC, LR

Limitations

The value in C+1 must be BCD from 1 to 6144. S and S+N must be in the same data area, as must D and D+N.

Description

When the execution condition is OFF, BXFR(125) is not executed. When the execution condition is ON, BXFR(125) copies the contents of S, S+1, ..., S+N to D, D+1, ..., D+N. The bank can be specified (in C) if an EM area address is used for S or D.

Control Words

C contains the source and destination bank numbers if data is being transferred to or from EM. The bank numbers are ignored unless an EM area address or a constant is used for S or D. C+1 contains the number of words to transfer and must be BCD (1 to 6144). Control word Bits C 0 to 7 8 to 15 C+1 0 to 15

204

Function Specifies the source bank number (00 to 0F). Specifies the destination bank number (00 to 0F). Specifies the number of words to transfer (1 to 6144).

Page 217

Section 5-17

Data Comparison Flags

ER:

N is not BCD. S and S+N or D and D+N are not in the same data area. The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded. The bank indicated by C does not exists when an EM area address is being used.

Example

The following example copies the contents of the 300 words from DM 0000 through DM 0299 to EM 2000 through EM 2299 in the EM bank 01. (The source bank number is ignored because an EM area address has not been used for it.) 00000 BXFR(125) DM 1000

Address

Instruction

00200 00201

LD BXFR(125)

Operands 00000 DM 1000 DM 0000 EM 2000

DM 0000 EM2000

C: DM 1000 0

1

0

C+1: DM 1001 0

0

Source bank number (00)

3

0

0

Number of words (300)

Destination bank number (01)

5-17 Data Comparison 5-17-1 MULTI-WORD COMPARE – MCMP(019) Operand Data Areas TB1: First word of table 1

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR MCMP(019)

@MCMP(019)

TB1

TB1

TB2

TB2

R

R

TB2: First word of table 2 IR, SR, AR, DM, EM, HR, TC, LR R: Result word IR, AR, DM, EM, HR, TC, LR, SR

Limitations

TB1 and TB1+15 must be in the same data area, as must TB2 and TB2+15. MCMP(019) is an expansion instruction. A Programming Device can be used to reassign function code 019 to another expansion instruction.

Description

When the execution condition is OFF, MCMP(019) is not executed. When the execution condition is ON, MCMP(019) compares the content of TB1 to TB2, TB1+1 to TB2+1, TB1+2 to TB2+2, ..., and TB1+15 to TB2+15. If the first pair is equal, the first bit in R is turned OFF, etc., i.e., if the content of TB1 equals the content of TB2, bit 00 is turned OFF, if the content of TB1+1 equals the content of TB2+1, bit 01 is turned OFF, etc. The rest of the bits in R will be turned ON.

Flags

ER:

One of the tables (i.e., TB1 through TB1+15, or TB2 through TB2+15) exceeds the data area.

205

Page 218

Section 5-17

Data Comparison

The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded. Example

The following example shows the comparisons made and the results provided for MCMP(019). Here, the comparison is made during each cycle when 00000 is ON.

00000 MCMP(019) 100 DM 0200

Address

Instruction

00000 00001

LD MCMP(019)

Operands 00000 100 DM 0200 DM 0300

DM 0300

TB1: IR 100 IR 100 IR 101 IR 102 IR 103 IR 104 IR 105 IR 106 IR 107 IR 108 IR 109 IR 110 IR 111 IR 112 IR 113 IR 114 IR 115

TB2: DM 0200

0100 0200 0210 ABCD ABCD ABCD ABCD 0800 0900 1000 ABCD ABCD ABCD 1400 0210 1212

DM 0200 DM 0201 DM 0202 DM 0203 DM 0204 DM 0205 DM 0206 DM 0207 DM 0208 DM 0209 DM 0210 DM 0211 DM 0212 DM 0213 DM 0214 DM 0215

0100 0200 0210 0400 0500 0600 0210 0800 0900 1000 0210 1200 1300 1400 0210 1600

R: DM 0300 DM 030000 DM 030001 DM 030002 DM 030003 DM 030004 DM 030005 DM 030006 DM 030007 DM 030008 DM 030009 DM 030010 DM 030011 DM 030012 DM 030013 DM 030014 DM 030015

0 0 0 1 1 1 1 0 0 0 1 1 1 0 0 1

5-17-2 COMPARE – CMP(020) Ladder Symbols

Operand Data Areas Cp1: First compare word

CMP(020) IR, SR, AR, DM, EM, HR, TC, LR, # Cp1 Cp2: Second compare word Cp2

IR, SR, AR, DM, EM, HR, TC, LR, #

Limitations

When comparing a value to the PV of a timer or counter, the value must be in BCD.

Description

When the execution condition is OFF, CMP(020) is not executed. When the execution condition is ON, CMP(020) compares Cp1 and Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area.

Precautions

Placing other instructions between CMP(020) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. CMP(020) cannot be used to compare signed binary data. Use CPS(114) instead. Refer to 5-17-8 SIGNED BINARY COMPARE – CPS(114) for details.

206

Page 219

Section 5-17

Data Comparison Flags

ER:

The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

EQ:

ON if Cp1 equals Cp2.

LE:

ON if Cp1 is less than Cp2.

GR:

ON if Cp1 is greater than Cp2. Flag

Example 1: Saving CMP(020) Results

00000

Address

C1 < C2

C1 = C2

C1 > C2

GR

25505

OFF

OFF

ON

EQ

25506

OFF

ON

OFF

LE

25507

ON

OFF

OFF

The following example shows how to save the comparison result immediately. If the content of HR 09 is greater than that of 010, 00200 is turned ON; if the two contents are equal, 00201 is turned ON; if content of HR 09 is less than that of 010, 00202 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 00200, 00201, and 00202 are changed only when CMP(020) is executed.

TR 0 CMP(020) HR 09 010

25505 00200

Greater Than

00201

Equal

00202

Less Than

25506

25507

Address

Instruction

00000 00001 00002

LD OUT CMP(020)

00003 00004

Example 2: Obtaining Indications during Timer Operation

LD AND

Operands 00000 TR 0 010 HR 09 TR 0 25505

Address

Instruction

00005 00006 00007 00008 00009 00010 00011

OUT LD AND OUT LD AND OUT

Operands 00200 TR 0 25506 00201 TR 0 25507 00202

The following example uses TIM, CMP(020), and the LE flag (25507) to produce outputs at particular times in the timer’s countdown. The timer is started by turning ON 00000. When 00000 is OFF, TIM 010 is reset and the second two CMP(020)s are not executed (i.e., executed with OFF execution conditions). Output 00200 is produced after 100 seconds; output 00201, after 200 seconds; output 00202, after 300 seconds; and output 00204, after 500 seconds.

207

Page 220

Section 5-17

Data Comparison

The branching structure of this diagram is important in order to ensure that 00200, 00201, and 00202 are controlled properly as the timer counts down. Because all of the comparisons here use to the timer’s PV as reference, the other operand for each CMP(020) must be in 4-digit BCD. 00000 TIM 010 #5000

500.0 s

CMP(020) TIM 010 #4000 25507 00200

Output at 100 s.

00200 CMP(020) TIM 010 #3000 25507 00201

Output at 200 s.

00201 CMP(020) TIM 010 #2000 25507 00202

Output at 300 s.

00204

Output at 500 s.

TIM 010

Address

Instruction

00000 00001

LD TIM

00002

CMP(020)

00003 00004 00005 00006

AND OUT LD CMP(020)

Operands 00000 010 #5000 TIM 010 #4000 25507 00200 00200 TIM 010 #3000

208

Address

Instruction

00007 00008 00009 00010

AND OUT LD CMP(020)

00011 00012 00013 00014

AND OUT LD OUT

Operands 25507 00201 00201 TIM 010 #2000 25507 00202 TIM 010 00204

Page 221

Section 5-17

Data Comparison

5-17-3 DOUBLE COMPARE – CMPL(060) Ladder Symbols

Operand Data Areas Cp1: First word of first compare word pair

CMPL(060) IR, SR, AR, DM, EM, HR, TC, LR Cp1 Cp2: First word of second compare word pair Cp2

IR, SR, AR, DM, EM, HR, TC, LR

___

Limitations

Cp1 and Cp1+1 must be in the same data area, as must Cp2 and Cp2+1. CMPL(060) is an expansion instruction. A Programming Device can be used to reassign function code 060 to another expansion instruction.

Description

When the execution condition is OFF, CMPL(060) is not executed. When the execution condition is ON, CMPL(060) joins the 4-digit hexadecimal content of Cp1+1 with that of Cp1, and that of Cp2+1 with that of Cp2 to create two 8-digit hexadecimal numbers, Cp+1,Cp1 and Cp2+1,Cp2. The two 8-digit numbers are then compared and the result is output to the GR, EQ, and LE flags in the SR area.

Precautions

Placing other instructions between CMPL(060) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. CMPL(060) cannot be used to compare signed binary data. Use CPSL(115) instead. Refer to 5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(115) for details.

Flags

ER:

The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

GR:

ON if Cp1+1,Cp1 is greater than Cp2+1,Cp2.

EQ:

ON if Cp1+1,Cp1 equals Cp2+1,Cp2.

LE:

ON if Cp1+1,Cp1 is less than Cp2+1,Cp2.

209

Page 222

Section 5-17

Data Comparison

The following example shows how to save the comparison result immediately. If the content of HR 10, HR 09 is greater than that of 011, 010, then 00200 is turned ON; if the two contents are equal, 00201 is turned ON; if content of HR 10, HR 09 is less than that of 011, 010, then 00202 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 00200, 00201, and 00202 are changed only when CMPL(060) is executed.

Example: Saving CMPL(060) Results

00000

TR 0 CMPL(060) HR 09 010 ––– 25505 00200

Greater Than

00201

Equal

00202

Less Than

25506

25507

Address

Instruction

00000 00001 00002

LD OUT CMPL(060)

Operands

Address

00000 TR 0

00004 00005 00006 00007 00008 00009 00010

HR 09 010 00003

AND

25505

Instruction OUT LD AND OUT LD AND OUT

Operands 00200 TR 0 25506 00201 TR 0 25507 00202

5-17-4 BLOCK COMPARE – BCMP(068) Operand Data Areas CD: Compare data

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # BCMP(068)

@BCMP(068)

CD

CD

CB

CB

R

R

CB: First comparison block word

Limitations

IR, DM, EM, HR, TC, LR, SR, AR R: Result word IR, SR, AR, DM, EM, HR, TC, LR

Each lower limit word in the comparison block must be less than or equal to the upper limit. BCMP(068) is an expansion instruction. A Programming Device can be used to reassign function code 068 to another expansion instruction.

210

Page 223

Section 5-17

Data Comparison Description

When the execution condition is OFF, BCMP(068) is not executed. When the execution condition is ON, BCMP(068) compares CD to the ranges defined by a block consisting of of CB, CB+1, CB+2, ..., CB+31. Each range is defined by two words, the first one providing the lower limit and the second word providing the upper limit. If CD is found to be within any of these ranges (inclusive of the upper and lower limits), the corresponding bit in R is set. The comparisons that are made and the corresponding bit in R that is set for each true comparison are shown below. The rest of the bits in R will be turned OFF. CB ≤ CD ≤ CB+1 Bit 00 CB+2 ≤ CD ≤ CB+3 Bit 01 CB+4 ≤ CD ≤ CB+5 Bit 02 CB+6 ≤ CD ≤ CB+7 Bit 03 CB+8 ≤ CD ≤ CB+9 Bit 04 CB+10 ≤ CD ≤ CB+11 Bit 05 CB+12 ≤ CD ≤ CB+13 Bit 06 CB+14 ≤ CD ≤ CB+15 Bit 07 CB+16 ≤ CD ≤ CB+17 Bit 08 CB+18 ≤ CD ≤ CB+19 Bit 09 CB+20 ≤ CD ≤ CB+21 Bit 10 CB+22 ≤ CD ≤ CB+23 Bit 11 CB+24 ≤ CD ≤ CB+25 Bit 12 CB+26 ≤ CD ≤ CB+27 Bit 13 CB+28 ≤ CD ≤ CB+29 Bit 14 CB+30 ≤ CD ≤ CB+31 Bit 15 Normally the first word in the range is less than the second, but if the first word in the range is greater than the second, the corresponding bit in R will be turned OFF when CD is outside of the range defined by the two words, as shown in the following diagram.

ÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉ ÉÉÉÉÉÉ ÉÉÉÉÉÉ ÉÉÉÉÉÉ CB

CB + 1

0000

9999

CB+1

0000

Flags

ER:

CB

9999

The comparison block (i.e., CB through CB+31) exceeds the data area. The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

211