Page 294

Section 5-21

Binary Calculations

In the case below, 25,321 +(–13,253) = 12,068 (62E9 + CC3B = 2F24). Neither OF nor UF are turned ON.

6

+

Au: LR 20 2 E 9

Ad: DM 0010 C C 3 B

2

Ad: DM 0020 F 2 4

Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.

5-21-2 BINARY SUBTRACT – SBB(051) Operand Data Areas Mi: Minuend word (binary)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # SBB(051)

@SBB(051)

Mi

Mi

Su

Su

R

R

Su: Subtrahend word (binary)

Description

IR, SR, AR, DM, EM, HR, TC, LR, # R: Result word IR, SR, AR, DM, EM, HR, LR

When the execution condition is OFF, SBB(051) is not executed. When the execution condition is ON, SBB(051) subtracts the contents of Su and CY from Mi and places the result in R. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R.

Mi – Su – CY

CY

R

SBB(051) can also be used to subtract signed binary data. The overflow and underflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Refer to page 30 for details on signed binary data. Flags

282

ER:

The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

CY:

ON when the result is negative, i.e., when Mi is less than Su plus CY.

EQ:

ON when the result is 0.

OF:

ON when the result exceeds +32,767 (7FFF).

UF:

ON when the result is below –32,768 (8000).

N:

ON when bit 15 of the result is set to 1.

Page 295

Section 5-21

Binary Calculations Example 1: Normal Data

The following example shows a four-digit subtraction with CY used to place either #0000 or #0001 into R+1 to ensure that any carry is preserved.

TR 1 00001 CLC(041)

SBB(051)

Address

Instruction

00000 00001 00002 00003

LD OUT CLC(041) SBB(051)

001 LR20 HR 21

=R

25504

00004 00005

MOV(021) #0000 HR 22

AND NOT MOV(021)

= R+1

25504 MOV(021) #0001 HR 22

= R+1

00006 00007 00008

LD AND MOV(021)

Operands 00001 TR 1

001 LR 20 HR 21 25504 #0000 HR 22 TR 1 25504 #0001 HR 22

NEG(160) HR21

00009

NEG(160) HR 21 HR 21

HR 21

In the case below, the content of LR 20 (#7A03) and CY are subtracted from IR 001 (#F8C5). The result is stored in HR 21 and the content of HR 22 (#0000) indicates that the result is positive. If the result had been negative, CY would have been set, #0001 would have been placed in HR 22, and the result would have been converted to its 2’s compliment.

0

F

Mi: IR 001 8 C 5

–

7

Su: LR 20 A 0 3

–

0

R+1: HR 22 0 0 0

7

0

0

0

R: HR 21 E C

2

CY = 0 (from CLC(041))

Note The status of the UF and OF flags can be ignored since they are relevant only in the subtraction of signed binary data.

283

Page 296

Section 5-21

Binary Calculations Example 2: Signed Binary Data

In the following example, SBB(051) is used to subtract one 16-bit signed binary value from another. (The 2’s complement is used to express negative values). The effective range for 16-bit signed binary values is –32,768 (8000) to +32,767 (7FFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds +32,767 (7FFF) and the underflow flag (UF: SR 25405) is turned ON if the result falls below –32,768 (8000).

00000 CLC(041)

SBB(051)

Address

Instruction

00000 00001 00002

LD CLC(041) SBB(051)

LR 20

Operands 00000

LR 20 DM 0010 DM 0020

DM 0010 DM 0020

In the case shown below, 30,020 – (–15,238) = 45,258 (7544 – C47A = 60CA).The OF flag would be turned ON to indicate that this result exceeds the upper limit of the 16-bit signed binary data range. (In other words, the result is a positive value that exceeds 32,767 (7FFF), not a negative number expressed as signed binary data.)

7

–

Mi: LR 20 5 4

4

Su: DM 0010 C 4 7 A

B

R: DM 0020 0 C A

In the case shown below, –30,000 – 3,000 = –33,000 (8AD0 – 0BB8 = 7F18).The UF flag would be turned ON to indicate that this result is below the lower limit of 16-bit signed binary data range. (In other words, the result is a negative number below –32,768 (8000), not a positive number expressed as signed binary data.)

–

8

Mi: LR 20 A D

0

Su: DM 0010 B B 8

7

R: DM 0020 F 1 8

0

The absolute value of the true result (80E8=33,000) can be obtained by taking the 2’s complement of 7F18 using NEG(160). Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.

284

Page 297

Section 5-21

Binary Calculations

5-21-3 BINARY MULTIPLY – MLB(052) Operand Data Areas Md: Multiplicand word (binary)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # MLB(052)

@MLB(052)

Md

Md

Mr

Mr

R

R

Mr: Multiplier word (binary) IR, SR, AR, DM, EM, HR, TC, LR, # R: First result word IR, SR, AR, DM, EM, HR LR

Limitations

R and R+1 must be in the same data area.

Description

When the execution condition is OFF, MLB(052) is not executed. When the execution condition is ON, MLB(052) multiplies the content of Md by the contents of Mr, places the rightmost four digits of the result in R, and places the leftmost four digits in R+1. Md

X

Mr

R +1

R

Precautions

MLB(052) cannot be used to multiply signed binary data. Use MBS(484) instead. Refer to 5-21-7 SIGNED BINARY MULTIPLY – MBS(484) for details.

Flags

ER:

The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded. ON when the result is 0. ON when bit 15 of R+1 is set to 1.

EQ: N:

5-21-4 BINARY DIVIDE – DVB(053) Operand Data Areas Dd: Dividend word (binary)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # DVB(053)

@DVB(053)

Dd

Dd

Dr

Dr

R

R

Dr: Divisor word (binary)

Description

IR, SR, AR, DM, EM, HR, TC, LR, # R: First result word IR, SR, AR, DM, EM, HR LR

When the execution condition is OFF, DVB(053) is not executed. When the execution condition is ON, DVB(053) divides the content of Dd by the content of Dr and the result is placed in R and R+1: the quotient in R, the remainder in R+1. Quotient R

Dr

Remainder R+1

Dd

285

Page 298

Section 5-21

Binary Calculations Precautions

DVB(053) cannot be used to divide signed binary data. Use DBS(485) instead. Refer to 5-21-9 SIGNED BINARY DIVIDE – DBS(485) for details.

Flags

ER:

Dr contains 0. The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

EQ:

ON when the result is 0.

N:

ON when bit 15 of R is set to 1.

Example 00000 DVB(053) 001

Address

Instruction

00000 00001

LD DVB(053)

Operands

001 LR 0020 HR 05

LR 20 HR 05

0

R+1: HR 06 0 0 2 Remainder (2)

00000

1

Dd: IR 001 0 F 7

0

Dr: LR 20 0 0

3

0

R: HR 05 5 A

7

Quotient (1447)

5-21-5 DOUBLE BINARY ADD – ADBL(480) Operand Data Areas Au: First augend word (binary)

Ladder Symbols

IR, SR, AR, DM, EM, HR, LR, TC ADBL(480)

@ADBL(480)

Au

Au

Ad

Ad

R

R

Ad: First addend word (binary)

Limitations

IR, SR, AR, DM, EM, HR, LR, TC R: First result word IR, SR, AR, DM, EM, HR, LR

Au and Au+1 must be in the same data area, as must Ad and Ad+1, and R and R+1. ADBL(480) is an expansion instruction. A Programming Device can be used to reassign function code 480 to another expansion instruction.

Description

286

When the execution condition is OFF, ADBL(480) is not executed. When the execution condition is ON, ADBL(480)) adds the eight-digit contents of Au+1 and Au, the eight-digit contents of Ad+1 and Ad, and CY, and places the result in R and R+1. CY will be set if the result is greater than FFFF FFFF.

Page 299

Section 5-21

Binary Calculations Au + 1

Au

Ad + 1

Ad

+ CY

CY

R+1

R

ADBL(480) can also be used to add signed binary data. The overflow and underflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Refer to page 30 for details on signed binary data. Flags

Example 1: Normal Data

ER:

The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

CY:

ON when the result is greater than FFFF FFFF.

EQ:

ON when the result is 0.

OF:

ON when the result exceeds +2,147,483,647 (7FFF FFFF).

UF:

ON when the result is below –2,147,483,648 (8000 0000).

N:

ON when bit 15 of R is set to 1.

The following example shows an eight-digit addition with CY (SR 25504) used to represent the status of the 9th digit.

00000 CLC(041)

ADBL(480)

Address

Instruction

00000 00001 00002

LD CLC(041) ADBL(480)

000

Operands 00000

000 DM 0020 LR 21

DM 0020 LR 21

14020187 + 00A3F8C5 = 14A5FA4C Au + 1 : 001 1 4 0 2

Au : 000 0 1 8

Ad + 1 : DM 0021

Ad : DM 0020 F 8 C 5

0

0

A

3

7

0

+ R + 1 : LR 22 1 4 A 5

R : LR 21 F A 4

CY (Cleared with CLC(041))

C 0

CY (No carry)

Note The status of the UF and OF flags can be ignored since they are relevant only in the addition of signed binary data. Example 2: Signed Binary Data

In the following example, ADBL(480) is used to add two 32-bit signed binary values and output the 32-bit signed binary result to R and R+1. (The 2’s complement is used to express negative values). The effective range for 32-bit signed binary values is –2,147,483,648 (8000 0000) to +2,147,483,647 (7FFF FFFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds +2,147,483,647 (7FFF FFFF) and the under-

287

Page 300

Section 5-21

Binary Calculations flow flag (UF: SR 25405) is turned ON if the result falls below –2,147,483,648 (8000 0000). 00000 CLC(041)

ADBL(480)

Address

Instruction

00000 00001 00002

LD CLC(041) ADBL(480)

LR 20

Operands 00000

LR 20 DM 0010 DM 0020

DM 0010 DM 0020

In the case below, 1,799,100,099 + (–282,751,929) = 1,516,348,100 (6B3C167D + EF258C47 = 5A61A2C4). Neither OF nor UF are turned ON. Au + 1 : LR 21 6 B 3 C

Au : LR 20 1 6 7

Ad + 1 : DM 0011

Ad : DM 0010 8 C 4 7

E

F

2

5

+

D

0 R + 1 : DM 0021 5 A 6 1

CY (Cleared with CLC(041))

R : DM 0020 A 2 C 4 0

UF (SR 25405)

0

OF (SR 25404)

Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.

5-21-6 DOUBLE BINARY SUBTRACT – SBBL(481) Operand Data Areas Mi: First minuend word (binary)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR SBBL(481)

@SBBL(481)

Mi

Mi

Su

Su

R

R

Su: First subtrahend word (binary)

Limitations

IR, SR, AR, DM, EM, HR, TC, LR R: First result word IR, SR, AR, DM, EM, HR, LR

Mi and Mi+1 must be in the same data area, as must Su and Su+1, and R and R+1. SBBL(481) is an expansion instruction. A Programming Device can be used to reassign function code 481 to another expansion instruction.

Description

288

When the execution condition is OFF, SBBL(481) is not executed. When the execution condition is ON, SBBL(481) subtracts CY and the eight-digit value in Su and Su+1 from the eight-digit value in Mi and Mi+1, and places the result in R and R+1. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R+1 and R. Use the DOUBLE 2’s COMPLEMENT instructions to convert the 2’s complement to the true result.

Page 301

Section 5-21

Binary Calculations Mi + 1

Mi

Su + 1

Su

– CY

CY

R+1

R

SBBL(481) can also be used to subtract signed binary data. The overflow and underflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Refer to page 30 for details on signed binary data. Flags

Example 1: Normal Data

ER:

The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

CY:

ON when the result is negative, i.e., when Mi is less than Su plus CY.

EQ:

ON when the result is 0.

OF:

ON when the result exceeds +2,147,483,647 (7FFF FFFF).

UF:

ON when the result is below –2,147,483,648 (8000 0000).

N:

ON when bit 15 of R+1 is set to 1.

In this example, the eight-digit number in IR 002 and IR 001 is subtracted from the eight-digit number in DM 0021 and DM 0020, and the result is output to LR 22 and LR 21. If the result is negative, CY (SR 25504) is turned ON.

00000 CLC(041)

SBBL(481)

Address

Instruction

00000 00001 00002

LD CLC(041) SBBL(481)

001

Operands 00000

001 DM 0020 LR 21

DM 0020 LR 21

14020187 + 00A3F8C5 = 14A5FA4C Au + 1 : 002 1 4 0 2

Au : 001 0 1 8

Ad + 1 : DM 0021

Ad : DM 0020 F 8 C 5

0

0

A

3

–

7

0 R + 1 : LR 22 1 3 5 E

R : LR 21 0 8 C

CY (Cleared with CLC(041))

2 0

CY (No carry)

Note The status of the UF and OF flags can be ignored since they are relevant only in the subtraction of signed binary data. Example 2: Signed Binary Data

In the following example, SBBL(481) is used to subtract one 32-bit signed binary value from another and output the 32-bit signed binary result to R and R+1. The effective range for 32-bit signed binary values is –2,147,483,648 (8000 0000) to +2,147,483,647 (7FFF FFFF). The overflow flag (OF: SR 25404) is turned ON if the result exceeds +2,147,483,647 (7FFF FFFF) and the under-

289

Page 302

Section 5-21

Binary Calculations flow flag (UF: SR 25405) is turned ON is the result falls below –2,147,483,648 (8000 0000). 00000 CLC(041)

SBBL(481)

Address

Instruction

00000 00001 00002

LD CLC(041) SBBL(481)

Operands

001

00000

001 DM 0020 LR 21

DM 0020 LR 21

In the case below, 1,799,100,099 – (–282,751,929) = 2,081,851,958 (6B3C 167D – {EF25 8C47 – 1 0000 0000} = 7C16 8A36). Neither OF nor UF are turned ON.

– –

Au + 1 : 001 6 B 3 C

Au : 000 1 6 7

Ad + 1 : DM 0021

Ad : DM 0020 8 C 4 7

E

F

2

5

D

0 R + 1 : LR 22 7 C 1 6

R : LR 21 8 A 3

CY (Cleared with CLC(041))

6 0

UF (SR 25405)

0

OF (SR 25404)

Note The status of the CY flag can be ignored when adding signed binary data since it is relevant only in the addition of normal hexadecimal values.

5-21-7 SIGNED BINARY MULTIPLY – MBS(484) Operand Data Areas Md: Multiplicand word

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # MBS(484)

@MBS(484)

Md

Md

Mr

Mr

R

R

Mr: Multiplier word IR, SR, AR, DM, EM, HR, TC, LR, # R: First result word IR, SR, AR, DM, EM, HR LR

Limitations

R and R+1 must be in the same data area. MBS(484) is an expansion instruction. A Programming Device can be used to reassign function code 484 to another expansion instruction.

Description

MBS(484) multiplies the signed binary content of two words and outputs the 8-digit signed binary result to R+1 and R. The rightmost four digits of the result are placed in R, and the leftmost four digits are placed in R+1. Refer to page 30 for details on signed binary data. Md

X R +1

290

Mr

R

Page 303

Section 5-21

Binary Calculations Flags

Example

ER:

The content of an word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded.

EQ:

ON when the result is 0000 0000, otherwise OFF.

N:

ON when bit 15 of R+1 is set to 1.

In the following example, MBS(484) is used to multiply the signed binary contents of IR 001 with the signed binary contents of DM 0020 and output the result to LR 21 and LR 22.

00000 MBS(484) 001

Address

Instruction

00000 00001

LD MBS(484)

Operands

001 DM 0020 LR 21

DM 0020 LR 21

X F

R+1: LR 22 F A A

00000

1

Md: 001 5 B

1

(5,553)

F

Mr: DM 0020 C 1 3

(–1,005)

D

R: LR 21 8 2

3

(–5,580,765)

5-21-8 DOUBLE SIGNED BINARY MULTIPLY – MBSL(482) Operand Data Areas Md: First multiplicand word

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR MBSL(482)

@MBSL(482)

Md

Md

Mr

Mr

R

R

Mr: First multiplier word

Limitations

IR, SR, AR, DM, EM, HR, TC, LR R: First result word IR, SR, AR, DM, EM, HR LR

Md and Md+1 must be in the same data area, as must Mr and Mr+1, and R through R+3. MBSL(482) is an expansion instruction. A Programming Device can be used to reassign function code 482 to another expansion instruction.

Description

MBSL(482) multiplies the 32-bit (8-digit) signed binary data in Md+1 and Md with the 32-bit signed binary data in Mr+1 and Mr, and outputs the 16-digit signed binary result to R+3 through R. Refer to page 30 for details on signed binary data.

x R+3

R+2

Md + 1

Md

Mr + 1

Mr

R+1

R

291