Page 344

Section 5-25

Step Instructions

The following diagram demonstrates the flow of processing and the switches that are used for execution control. SW1 Process A

Loading SW2

Process B

Part Installation SW3

Process C

Inspection/discharge SW4

332

Page 345

Section 5-25

Step Instructions

The program for this process, shown below, utilizes the most basic type of step programming: each step is completed by a unique SNXT(009) that starts the next step. Each step starts when the switch that indicates the previous step has been completed turns ON.

00001 (SW1) SNXT(009) 12800

Process A started.

STEP(008) 12800

Process A

00002 (SW2) SNXT(009) 12801

Process A reset. Process B started.

STEP(008) 12801

Process B

00003 (SW3) SNXT(009) 12802

Process B reset. Process C started.

STEP(008) 12802

Process C

00004 (SW4) SNXT(009) 12803

Process C reset.

STEP(008)

Address

Instruction

00000 00001 00002

LD SNXT(009) STEP(008)

Operands 00001 12800 12800

Process A 00100 00101 00102

LD SNXT(009) STEP(008)

00002 12801 12801

Address

Instruction

Operands

Process B 00100 00101 00102

LD SNXT(009) STEP(008)

00003 12802 12802

Process C 00200 00201 00202

LD SNXT(009) STEP(008)

00004 12803 ---

333

Page 346

Section 5-25

Step Instructions Example 2: Branching Execution

The following process requires that a product is processed in one of two ways, depending on its weight, before it is printed. The printing process is the same regardless of which of the first processes is used. Various sensors are positioned to signal when processes are to start and end. Printer

SW A2

SW A1

SW D

Process A Process B

SW B1

SW B2

Weight scale

Process C

The following diagram demonstrates the flow of processing and the switches that are used for execution control. Here, either process A or process B is used depending on the status of SW A1 and SW B1.

SW B1

SW A1 Process A SW A2 Process C SW D End

334

Process B SW B2

Page 347

Section 5-25

Step Instructions

The program for this process, shown below, starts with two SNXT(009) instructions that start processes A and B. Because of the way 00001 (SW A1) and 00002 (SB B1) are programmed, only one of these will be executed to start either process A or process B. Both of the steps for these processes end with a SNXT(009) that starts the step for process C.

00001 (SW A1) 00002 (SW B1) SNXT(009) HR 0000 00001 (SW A1) 00002 (SW B1) SNXT(009) HR 0001

STEP(008) HR 0000 Process A started.

Process A

00003 (SW A2) SNXT(009) HR 0002

Process A reset. Process C started.

STEP(008) HR 0001

Process B

00004 (SW B2) SNXT(009) HR 0002

Process B reset. Process C started.

STEP(008) HR 0002

Process C

00005 (SW D) SNXT(009) HR 0003

Process C reset.

STEP(008)

Address

Instruction

00000 00001 00002 00003 00004 00005 00006

LD AND NOT SNXT(009) LD NOT AND SNXT(009) STEP(008)

Operands 00001 00002 HR 0000 00001 00002 HR 0001 HR 0000

Address

Instruction

Operands

Process B 00100 00101 00102

LD SNXT(009) STEP(008)

00004 HR 0002 HR 0002

Process C Process A 00100 00101 00102

LD SNXT(009) STEP(008)

00003 HR 0002 HR 0001

00200 00201 00202

LD SNXT(009) STEP(008)

00005 HR 0003 ---

335

Page 348

Step Instructions

Section 5-25

Example 3: Parallel Execution

The following process requires that two parts of a product pass simultaneously through two processes each before they are joined together in a fifth process. Various sensors are positioned to signal when processes are to start and end. SW1

Process A

SW3

SW5

SW7

Process B Process E Process D

Process C SW2

SW4

SW6

The following diagram demonstrates the flow of processing and the switches that are used for execution control. Here, process A and process C are started together. When process A finishes, process B starts; when process C finishes, process D starts. When both processes B and D have finished, process E starts.

SW 1 and SW2 both ON

Process A

Process C

SW4

SW3 Process B

Process D

SW5 and SW6 both ON Process E SW7

End

The program for this operation, shown below, starts with two SNXT(009) instructions that start processes A and C. These instructions branch from the same instruction line and are always executed together, starting steps for both A and C. When the steps for both A and C have finished, the steps for process B and D begin immediately. When both process B and process D have finished (i.e., when the status for both of them is “ON,” but SW5 and SW6 have turned ON), processes B and D are reset together by the SNXT(009) at the end of the programming for process B. Although there is no SNXT(009) at the end of process D, the control bit for it is turned OFF by executing SNXT(009) LR 0004. This is because the OUT for LR 0003 is in the step reset by SNXT(009) LR 0004, i.e., LR 0003 is turned OFF when SNXT(009) LR 0004 is executed Process B is thus reset directly and process D is reset indirectly before executing the step for process E.

336

Page 349

Section 5-25

Step Instructions

00001 (SW1 and SW2)) SNXT(009) LR 0000 Process A started.

Process C started. SNXT(009) LR 0002

STEP(008) LR 0000

Process A

00002 (SW3) SNXT(009) LR 0001

Process A reset. Process B started.

STEP(008) LR 0001

Process B

LR 0003 LR 0003

Used to turn OFF process D.

00004 (SW5 and SW6) SNXT(009) LR 0004

Process E started.

STEP(008) LR 0002

Process C

00003 (SW4) SNXT(009) LR 0003

Process C reset. Process D started.

STEP(008) LR 0003

Process D

STEP(008) LR 0004

Process E

00005 (SW7) SNXT(009) LR 0005

Process E reset.

STEP(008)

337

Page 350

Section 5-26

Special Instructions Address

Instruction

00000 00001 00002 00003

LD SNXT(009) SNXT(009) STEP(008)

Operands 00001 LR 0000 LR 0002 LR 0000

Instruction

00204

STEP(008)

LD SNXT(009) STEP(008)

Operands LR 0002

Process C 00300 00301 00302

Process A 00100 00101 00102

Address

00002 LR 0001 LR 0001

LD SNXT(009) STEP(008)

00003 LR 0003 LR 0003

Process D 00400

STEP(008)

LR 0004

Process B Process E 00200 00201 00202 00203

LD OUT AND SNXT(009)

LR 0003 LR 0003 00004 LR 0004

00500 00501 00502

LD SNXT(009) STEP(008)

00005 LR 0005 ---

5-26 Special Instructions The instructions in this section are used for various operations, including programming user error codes and messages, counting ON bits, setting the watchdog timer, and refreshing I/O during program execution.

5-26-1 FAILURE ALARM – FAL(006) and SEVERE FAILURE ALARM – FALS(007) Ladder Symbols FAL(006) N

Definer Data Areas

@FAL(006) N

N: FAL number # (00 to 99)

N: FAL number

FALS(007) N

# (01 to 99)

Limitations

FAL(006) and FALS(007) share the same FAL numbers. Be sure to use a number in either FAL(006) or FALS(007), not both.

Description

FAL(006) and FALS(007) are provided so that the programmer can output error numbers for use in operation, maintenance, and debugging. When executed with an ON execution condition, either of these instructions will output a FAL number to bits 00 to 07 of SR 253. The FAL number that is output can be between 01 and 99 and is input as the definer for FAL(006) or FALS(007). FAL(006) with a definer of 00 is used to reset this area (see below). FAL Area 25307

25300

X101

338

X100

Page 351

Section 5-26

Special Instructions

FAL(006) produces a non-fatal error and FAL(007) produces a fatal error. When FAL(006) is executed with an ON execution condition, the ALARM/ERROR indicator on the front of the CPU Unit will flash, but PC operation will continue. When FALS(007) is executed with an ON execution condition, the ALARM/ERROR indicator will light and PC operation will stop. The system also generates error codes to the FAL area. Resetting Errors

All FAL error codes will be retained in memory, although only one of these is available in the FAL area. To access the other FAL codes, reset the FAL area by executing FAL(006) 00. Each time FAL(006) 00 is executed, another FAL error will be moved to the FAL area, clearing the one that is already there. FAL error codes are recorded and will be recalled in the following order: First code generated, lowest FAL number greater than the first code, lowest FAL number lower than the first code.

Clearing Messages

FAL(006) 00 is also used to clear message programmed with the instruction, MSG(046). If the FAL area cannot be cleared, as is generally the case when FALS(007) is executed, first remove the cause of the error and then clear the FAL area through the Programming Console (see 4-6-5 Clearing Error Messages).

5-26-2 CYCLE TIME – SCAN(018) Operand Data Areas Mi: Multiplier (BCD)

Ladder Symbols

IR, SR, AR, DM, EM, HR, TC, LR, # SCAN(018)

@SCAN(018)

Mi

Mi

000

000

000

000

000: Not used.

Limitations

000: Not used.

Mi must be BCD. Only the rightmost three digits of Mi are used. SCAN(018) is an expansion instruction. A Programming Device can be used to reassign function code 018 to another expansion instruction.

Description

SCAN(018) is used to set a minimum cycle time. Mi is the minimum cycle time that will be set in tenths of milliseconds, e.g., if Mi is 1200, the minimum cycle time will be 120.0 ms. The possible setting range is from 000.0 to 999.0 ms. If the actual cycle time is less than the cycle time set with SCAN(018) the CPU Unit will wait until the designated time has elapsed before starting the next cycle. If the actual cycle time is greater than the set time, the set time will be ignored and the program will be executed to completion.

Flags

ER:

The content of a word containing an indirect DM/EM address is not BCD or the DM/EM area boundary has been exceeded. Mi is not BCD.

339

Page 352

Section 5-26

Special Instructions

5-26-3 TRACE MEMORY SAMPLING – TRSM(045) Data tracing can be used to facilitate debugging programs. To set up and use data tracing it is necessary to have a host computer running CX-Programmer; no data tracing is possible from a Programming Console. Data tracing is described in detail in the CX-Programmer Operation Manual. This section shows the ladder symbol for TRSM(045) and gives an example program. Ladder Symbol TRSM(045) Description

TRSM(045) is used in the program to mark locations where specified data is to be stored in Trace Memory. Up to 12 bits and up to 3 words may be designated for tracing (refer to the SYSMAC-CPT Support Software Operation Manual for details). TRSM(045) is not controlled by an execution condition, but rather by two bits in the AR area: AR 2515 and AR 2514. AR 2515 is the Sampling Start bit. This bit is turned ON to start the sampling processes for tracing. The Sampling Start bit must not be turned ON from the program, i.e., it must be turned ON only from the Programming Device. AR 2514 is the Trace Start bit. When it is set, the specified data is recorded in Trace Memory. The Trace Start bit can be set either from the program or from the Programming Device. A positive or negative delay can also be set to alter the actual point from which tracing will begin. Data can be recorded in any of three ways. TRSM(045) can be placed at one or more locations in the program to indicate where the specified data is to be traced. If TRSM(045) is not used, the specified data will be traced when END(001) is executed. The third method involves setting a timer interval from the Programming Device so that the specified data will be tracing at a regular interval independent of the cycle time (refer to the SYSMAC-CPT Support Software Operation Manual). TRSM(045) can be incorporated anywhere in a program, any number of times. The data in the trace memory can then be monitored via a Programming Console, host computer, etc.

AR Control Bits and Flags

The following control bits and flags are used during data tracing. The Tracing Flag will be ON during tracing operations. The Trace Completed Flag will turn ON when enough data has been traced to fill Trace Memory. Flag

Function

AR 2515

Sampling Start Bit

AR 2514

Trace Start Bit

AR 2513

Tracing Flag

AR 2512

Trace Completed Flag

Precautions

If TRSM(045) occurs TRSM(045) will not be executed within a JMP(008) – JME(009) block when the jump condition is OFF.

Example

The following example shows the basic program and operation for data tracing. Force set the Sampling Start Bit (AR 2515) to begin sampling. The Sampling Start Bit must not be turned ON from the program. The data is read and stored into trace memory. When IR 00000 is ON, the Trace Start Bit (AR 2514) is also turned ON, and the CPU Unit looks at the delay and marks the trace memory accordingly. This can mean that some of the samples already made will be recorded as the trace

340

Page 353

Section 5-26

Special Instructions memory (negative delay), or that more samples will be made before they are recorded (positive delay). The sampled data is written to trace memory, jumping to the beginning of the memory area once the end has been reached and continuing up to the start marker. This might mean that previously recorded data (i.e., data from this sample that falls before the start marker) is overwritten (this is especially true if the delay is positive). The negative delay cannot be such that the required data was executed before sampling was started. 00000

AR 2514

TRSM(045)

AR 2513 ON when tracing

Instruction

00000 00001 00002 00003

LD OUT TRSM(045) LD

Operands

Address

0000 AR 2514

Designates point for tracing.

00200

Indicates that tracing is in progress.

00201

Indicates that tracing has been completed.

AR 2512 ON when trace is complete

Address

Starts data tracing.

Instruction

00004 00005 00006

Operands

OUT LD OUT

00200 AR 2512 00201

AR 2513

5-26-4 MESSAGE DISPLAY – MSG(046) Ladder Symbols

Operand Data Areas

MSG(046)

@MSG(046)

FM

FM

FM: First message word IR, SR, AR, DM, EM, HR, LR, TC

Limitations

FM and FM+7 must be in the same data area.

Description

When executed with an ON execution condition, MSG(046) reads eight words of extended ASCII code from FM to FM+7 and displays the message on the Programming Console. The displayed message can be up to 16 characters long, i.e., each ASCII character code requires eight bits (two digits). Refer to Appendix I for the extended ASCII codes. Japanese katakana characters are included in this code. If not all eight words are required for the message, it can be stopped at any point by inputting “0D.” When 0D is encountered in a message, no more words will be read and the words that normally would be used for the message can be used for other purposes.

Message Buffering and Priority

Up to three messages can be buffered in memory. Once stored in the buffer, they are displayed on a first in, first out basis. Since it is possible that more than three MSG(046)s may be executed within a single cycle, there is a priority scheme, based on the area where the messages are stored, for the selection of those messages to be buffered. The priority of the data areas is as follows for message display:

341