Page 426
Section
Instruction Execution Times Instruction
Conditions
6-3
ON execution time (µs) OFF execution time (µs) C200HX C200HG C200HE C200HX C200HG C200HE 0.313 0.469 0.938 21.1 36.0
<>L(306)
When comparing a constant to a word When comparing to
41.8
56.4
<>S(307)
When comparing a constant to a word When comparing to
18.8 40.0
33.4 54.8
0.313
0.469
0.938
<>SL(308)
When comparing a constant to a word When comparing to
21.6 42.1
36.4 56.8
0.313
0.469
0.938
<(310)
When comparing a constant to a word When comparing to
18.3 39.6
33.0 54.4
0.313
0.469
0.938
<L(311)
When comparing a constant to a word When comparing to
21.2 41.8
36.0 56.4
0.313
0.469
0.938
<S(312)
When comparing a constant to a word When comparing to
18.6 40.0
33.4 54.8
0.313
0.469
0.938
<SL(313)
When comparing a constant to a word When comparing to
21.6 42.1
36.4 56.8
0.313
0.469
0.938
<=(315)
When comparing a constant to a word When comparing to
18.3 39.8
33.0 54.4
0.313
0.469
0.938
<=L(316)
When comparing a constant to a word When comparing to
21.4 41.9
36.2 56.6
0.313
0.469
0.938
<=S(317)
When comparing a constant to a word When comparing to
18.6 40.1
33.4 54.8
0.313
0.469
0.938
<=SL(318)
When comparing a constant to a word When comparing to
21.8 42.3
36.4 57.0
0.313
0.469
0.938
>(320)
When comparing a constant to a word When comparing to
18.4 39.6
33.2 54.4
0.313
0.469
0.938
>L(321)
When comparing a constant to a word When comparing to
21.3 41.8
36.0 56.4
0.313
0.469
0.938
>S(322)
When comparing a constant to a word When comparing to
18.8 40.0
33.4 54.8
0.313
0.469
0.938
>SL(323)
When comparing a constant to a word When comparing to
21.6 42.1
36.4 56.8
0.313
0.469
0.938
>=(325)
When comparing a constant to a word When comparing to
18.4 39.8
33.2 54.4
0.313
0.469
0.938
>=L(326)
When comparing a constant to a word When comparing to
21.4 41.9
36.2 56.6
0.313
0.469
0.938
>=S(327)
When comparing a constant to a word When comparing to
18.8 40.1
33.4 54.8
0.313
0.469
0.938
>=SL(328)
When comparing a constant to a word When comparing to
21.8 42.3
36.4 57.0
0.313
0.469
0.938
TST(350)
Setting 1 bit of a word to a constant Setting 1 bit to
20.6 42.9
35.4 57.6
0.313
0.469
0.938
TSTN(351)
Setting 1 bit of a word to a constant Setting 1 bit to
20.8 43.0
35.4 57.8
0.313
0.469
0.938
+(400)
Constant + word → word + →
17.0 49.1
31.9 64.0
0.313
0.469
0.938
+L(401)
Constant + word → word + →
19.6 50.5
34.6 65.6
0.313
0.469
0.938
+C(402)
Constant + word → word + →
19.2 51.3
34.0 66.4
0.313
0.469
0.938
415
Page 427
Section
Instruction Execution Times Instruction +CL(403) +B(404)
Conditions Constant + word → word + → Constant + word → word + →
6-3
ON execution time (µs) OFF execution time (µs) C200HX C200HG C200HE C200HX C200HG C200HE 0.313 0.469 0.938 26.1 41.2 58.5 15.6 48.5
73.6 30.4 63.6
Constant + word → word + → Constant + word → word + →
21.6 52.3 16.7 49.5
Constant + word → word + → Constant – word → word – →
0.313
0.469
0.938
36.6 67.4 31.6 64.6
0.313
0.469
0.938
0.313
0.469
0.938
22.8 53.5 16.9 49.1
37.8 68.6 31.8 64.0
0.313
0.469
0.938
0.313
0.469
0.938
Constant – word → word – → Constant – word → word – →
19.5 50.3 19.1 51.1
34.4 65.4 33.8 66.2
0.313
0.469
0.938
0.313
0.469
0.938
Constant – word → word – → Constant – word → word – →
25.7 58.1 15.6 48.5
40.8 73.2 30.4 63.6
0.313
0.469
0.938
0.313
0.469
0.938
Constant – word → word – → Constant – word → word – →
21.6 52.3 16.5 49.5
36.6 67.4 31.6 64.6
0.313
0.469
0.938
0.313
0.469
0.938
Constant – word → word – → Constant × word → word × →
22.8 53.5 19.7 51.9
37.8 68.6 34.8 67.0
0.313
0.469
0.938
0.313
0.469
0.938
Constant × word → word × → Constant × word → word × →
42.7 76.7 17.3 48.9
58.0 92.0 32.2 64.0
0.313
0.469
0.938
0.313
0.469
0.938
Constant × word → word × → Constant × word → word × →
32.1 63.3 30.9 63.9
47.4 78.8 46.0 78.8
0.313
0.469
0.938
0.313
0.469
0.938
Constant × word → word × →
0.469
0.938
Constant ÷ word→ word
110.0 140.8 13.9
0.313
/(430)
108.9 140.9 13.4
0.313
0.469
0.938
÷ →
46.1
46.3
Constant ÷ word→ word
21.9
22.0
0.313
0.469
0.938
÷ →
55.9
56.0
Constant ÷ word→ word
12.5
12.5
0.313
0.469
0.938
÷ →
44.3
44.3
Constant ÷ word→ word
12.8
12.8
0.313
0.469
0.938
÷ →
33.5
33.5
Constant ÷ word→ word
13.5
13.5
0.313
0.469
0.938
÷ →
46.3
46.4
+BL(405) +BC(406) +BCL(407) –(410) –L(411) –C(412) –CL(413) –B(414) –BL(415) –BC(416) –BCL(417)
/L(431) /U(432) /UL(433) /B(434)
416
Page 428
Section
Instruction Execution Times Instruction /BL(435) ADBL(480) SBBL(481) MBSL(482) DBSL(483) MBS(484)
DBS(485)
BXF2(––)
IEMS(––) XFR2(––)
Conditions
6-3
Constant ÷ word→ word
ON execution time (µs) OFF execution time (µs) C200HX C200HG C200HE C200HX C200HG C200HE 0.313 0.469 0.938 17.9 18.1
÷ →
48.9
49.0
DM + DM → DM
27.35
42.05
+ →
60.1
74.8
DM – DM → DM
26.95
41.65
– →
59.7
74.4
DM × DM → DM
45.3
60
× →
77.1
91.8
DM ÷ DM → DM ÷ → Constant × word → word
86.6 118.6 20.85
101.3 133.3 35.55
DM × DM → DM
21.65
36.35
× →
53.5
68.2
Constant ÷ word → word
21.55
36.25
DM ÷ DM → DM
22.45
37.15
÷ →
54.9
69.6
Word designation (1 word) designation (1,024 words)
72.8 3.68 ms designation (6,144 words)
8.75 ms
Constant designation (Switch to DM.) Word designation (Switch to EM bank.) Word designation (1 word) designation (1,024 words) designation (6,144 words)
19.25 24.95 46.4 656.2 3.66 ms
71.7 (See note 3) (See note 3) 18.15 23.85 45.3 655.1 (See note 3)
Note
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
0.313
0.469
0.938
1. Same as the C200HX’s instruction execution time. 2. Add 14.7 µs to the C200HX’s instruction execution time. 3. Add 1.1 µs to the C200HX’s instruction execution time.
417
Page 429
Section
I/O Response Time
6-4
6-4
I/O Response Time The I/O response time is the time it takes for the PC to output a control signal after it has received an input signal. The time it takes to respond depends on the cycle time and when the CPU Unit receives the input signal relative to the input refresh period. The minimum and maximum I/O response time calculations described below are for where IR 00000 is the input bit that receives the signal and IR 00200 is the output bit corresponding to the desired output point. 00000
00200
6-4-1 Basic Systems Minimum I/O Response Time
The PC responds most quickly when it receives an input signal just prior to the I/O refresh period in the cycle. Once the input bit corresponding to the signal has been turned ON, the program will have to be executed once to turn ON the output bit for the desired output signal and then the I/O refresh operation would have to be repeated to refresh the output bit. The I/O response time in this case is thus found by adding the input ON-delay time, the cycle time, and the output ON-delay time. This situation is illustrated below.
Cycle
Cycle time
Cycle time
Instruction execution
Instruction execution
I/O refresh Input signal Input ON delay
CPU Unit reads input signal
Output ON delay Output signal I/O response time
Minimum I/O response time = Input ON delay + Cycle time + Output ON delay
418
Instruction execution
Page 430
Section
I/O Response Time Maximum I/O Response Time
6-4
The PC takes longest to respond when it receives the input signal just after the I/O refresh phase of the cycle. In this case the CPU Unit does not recognize the input signal until the end of the next cycle. The maximum response time is thus one cycle longer than the minimum I/O response time, except that the I/O refresh time would not need to be added in because the input comes just after it rather than before it.
Cycle
Cycle time
Cycle time
Cycle time
Instruction execution
Instruction execution
Instruction execution
I/O refresh
Input signal
CPU Unit reads input signal
Input ON delay
Output ON delay
Output signal
I/O response time
Maximum I/O response time = Input ON delay + (Cycle time × 2) + Output ON delay Calculation Example
The data in the following table would produce the minimum and maximum cycle times shown calculated below. Item
Time
Input ON-delay
1.5 ms
Output ON-delay
15 ms
Cycle time
20 ms
Minimum I/O response time = 1.5 + 20 + 15 = 36.5 ms Maximum I/O response time = 1.5 + (20 x 2) +15 = 56.5 ms Note In this example the I/O refresh time is negligible has not been included in the minimum I/O response time.
6-4-2 Remote I/O Systems With Remote I/O Systems, only the cycle time of the PC needs to be considered in computing the I/O response times as long as the remote I/O transmission time is negligible and smaller than the cycle time. The cycle time, however, is increased by the presence of the Remote I/O System. The processing that determines and the methods for calculating maximum and minimum response times from input to output are provided in this section. Calculations assume that both the input and the output are located on Slave Racks in a Remote I/O System, but the calculations are the same for I/O points on Optical I/O Units, I/O Link Units, I/O Terminals, etc. Input on Slave Rack
Output on Slave Rack X
Although more precise equations are possible if required, equations used for the following calculations do not consider fractions of a scan.
419
Page 431
Section
I/O Response Time
6-4
In looking at the following timing charts, it is important to remember the sequence in which processing occurs during the PC scan, particular that inputs will not produce programmed actions until the program has been executed. When calculating the response times involving inputs and outputs from another CPU Unit connected by an I/O Link Unit, the cycle time of the controlling CPU Unit and the cycle time of the PC to which the I/O Link Unit is mounted must both be considered. ! Caution Remote I/O Transmission Times
Noise may increase I/O delays. The remote I/O transmission time is computed as follows: TRM
= Total Slave transmission time for one Master =
TRT = =
ΣTRT + ΣTTT Transmission time for each Slave 1.4 ms + (0.2 ms × n) Where n = number of I/O words on the Slave Rack
TTT
=
Optical I/O Unit/I/O Terminal transmission time
=
2 ms × m Where m = number of Optical I/O Units/I/O Terminals
Minimum I/O Response Time
The minimum response time occurs when all signals are processed as soon as they are received. Here, three scans are required so that the program is executed, as shown in the following diagram. Time = Input ON delay + cycle time × 3 + output ON delay Cycle time > Remote I/O transmission times Cycle time
CPU Unit
Program execution Transfer to CPU Unit
Master Transfer to Master Slave Slave I/O refresh Input Output
420
Page 432
Section
I/O Response Time
6-4
The maximum response time occurs when the input just misses the program execution portion of the scan, meaning that processing must wait for the next transmission and then the next (i.e., the fourth) scan.
Maximum I/O Response Time
Time = Input ON delay + cycle time × 4 + output ON delay Cycle time > Remote I/O transmission times Note Use the maximum cycle time output to AR 26 in computing the maximum I/O response time. Cycle time CPU Unit
Program execution Transfer to CPU Unit
Master Slave I/O refresh
Transfer to Master
Slave Input Output
Example Calculations
Calculations would be as shown below for an input ON delay of 1.5 ms, an output ON delay of 15 ms, and a cycle time of 20 ms. Minimum I/O Response Time Time = 1.5 ms + (20 ms × 3) + 15 ms = 76.5 ms Maximum I/O Response Time Time = 1.5 ms + (20 ms × 4) + 15 ms = 96.5 ms Note
1. The cycle time may be less than or equal to the remote I/O transmission time when there are Special I/O Units on Slave Racks. If this is the case, there may be cycles when I/O is not refreshed between the Master and the C200HX/HG/HE CPU Unit. 2. Refreshing is performed for Masters only once per cycle, and then only after confirming completion of the remote cycle. 3. The short duration of ON/OFF status produced by differentiated instructions can cause inaccurate signals when dealing with Remote I/O Systems unless appropriate programming steps are taken.
421
Page 433
Section
I/O Response Time
6-4
6-4-3 Host Link Systems The following diagram illustrates the processing that takes place when an input on one PC is transferred through the Host Link System to turn ON an output on another PC. Refer to Host Link System documentation for further details. Output on #31
Input on #0
X
Host computer
Command/response for Unit # 0
Command/response for Unit # 31
Command
Command Response
Buffer for Host Link Unit # 0
Response Host computer processing time
CPU Unit reads input signal Cycle time
PC for Host Link Unit # 0 I/O refresh CPU Unit writes output signal
Host link service
Buffer for Host Link Unit # 31
Cycle time PC for Host Link Unit # 31 Host link service
I/O refresh
Input signal Input ON delay
Output ON delay
Output signal I/O response time
The equations used to calculate the minimum and maximum cycle times are given below. The number of cycles required for each PC depends on the amount of data being read/written. Minimum response time =
Input ON delay + Command transmission time + (Cycle time of PC for Unit #0 × 3) + Response transmission time + Host computer processing time + Command transmission time + (Cycle time of PC for Unit #31 × 3) + Output ON delay
Maximum response time =
Input ON delay + Command transmission time + (Cycle time of PC for Unit #0 × 10) + Response transmission time + Host computer processing time + Command transmission time + (Cycle time of PC for Unit #31 × 10) + Output ON delay
6-4-4 PC Link Systems The processing that determines and the methods for calculating maximum and minimum response times from input to output are provided in this subsection. The following System and I/O program steps will be used in all examples below. This System contains eight PC Link Units.
422