Page 27

SECTION 2 Hardware Considerations This section provides information on hardware aspects of the C200HX/HG/HE that are relevant to programming and software operation. These include CPU Unit components, the basic PC configuration, CPU Unit capabilities, and Memory Cassettes. This information is covered in detail in the C200HX/HG/HE Installation Guide. 2-1

2-2 2-3 2-4

2-5 2-6

CPU Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-1 CPU Unit Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 Programming Device Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU Unit Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-1 Hardware and Software Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-2 Writing/Reading UM Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-3 Writing/Reading IOM Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating without a Backup Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU Unit DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14 15 15 17 17 18 19 19 20 21 23

13

Page 28

Section

CPU Unit Components

2-1

2-1

CPU Unit Components The following diagram shows the main CPU Unit components. Indicators Memory Cassette DIP switch

Communications Board (The C200HW-COM06-E is mounted to this CPU Unit.)

Peripheral port

RS-232C port

The CPU Unit has a compartment to connect the Memory Cassette to the CPU Unit. The Memory Cassette works as a RAM together with the built-in RAM of the CPU Unit.

Peripheral Port

A Programming Device can be connected to the peripheral port.

RS-232C Port

The CPU Unit has a built-in RS-232C port.

Communications Board

The CPU Unit has a compartment to connect the Communications Board to the CPU Unit.

DIP Switch

The PC operates according to the DIP switch settings of the CPU Unit. The DIP switch of the CPU Unit for the C200HX/HG/HE has six pins. For the function of each of the pins, refer to the following table. (All six pins are OFF when the PC is shipped.)

6 5

4

3 2 1

Memory Cassette

ON OFF⇔ON

14

Page 29

Section

CPU Unit Components

2-1

Pin

Setting

1

ON

Data cannot be written to the UM area.

OFF

Data can be written to the UM area.

ON

Memory Cassette data is read automatically at startup.

OFF

Memory Cassette data is not read automatically at startup.

ON

Programming Console displays messages in English.

OFF

Programming Console displays messages in Japanese.

ON

The expansion instructions can be set.

OFF

The expansion instructions cannot be set (default setting).

ON

Sets the following conditions for the communications port (including when a CQM1-CIF02 is connected to the Peripheral Port):

2 3 4 5

Function

1 start bit, 7 data bits, even parity, 2 stop bit, 9,600 bps baud rate 6

OFF

Cancels the above settings.

ON

Programming Console is in expansion terminal mode (AR 0712 is turned ON).

OFF

Programming Console is in normal mode (AR 0712 is turned OFF).

2-1-1 CPU Unit Indicators CPU Unit indicators provide visual information on the general operation of the PC. Although not substitutes for proper error programming using the flags and other error indicators provided in the data areas of memory, these indicators provide ready confirmation of proper operation. Indicator

Meaning

RUN (green)

Lit when the PC is operating normally.

ERR (red)

Flashes if the PC detects any non-fatal error in operation. The PC will continue operating. Lit if the PC detects any fatal error in operation. The PC will stop operating. After the PC stops operating, the RUN indicator will be OFF and all output signals of the Output Units will be interrupted (turned OFF).

INH (orange)

Lit when the Load OFF flag (AR bit) is ON, in which case all output signals of the Output Units will be interrupted (turned OFF).

COMM (orange)

Flashes when the CPU Unit is communicating with the device connected to the peripheral port or RS-232C port.

2-1-2 Programming Device Connection A Programming Console or IBM PC/AT running the SYSMAC-CPT Support Software can be used to program and monitor the C200HX/HG/HE PCs. Programming Console

A C200H-PR027-E or CQM1-PRO01-E Programming Console can be connected as shown in the diagram. The C200H-PR027-E is connected via the C200H-CN222 or C200H-CN422 Programming Console Connecting Cable, which must be purchased separately. A Connecting Cable is provided with the CQM1-PRO01-E.

Data Access Console

A C200H-DAC01 Data Access Console can be connected via the C200HCN222 or C200H-CN422 Programming Console Connecting Cable, which must be purchased separately. The following operations are not available when the C200H-DAC01 is used with the C200HX/HG/HE: Set value read and change Error message display

15

Page 30

Section

CPU Unit Components

2-1

An IBM PC/AT or compatible computer with SYSMAC-CPT Support Software can be connected as shown in the diagram.

IBM PC/AT with SYSMAC-CPT Support Software C200H-LK201-V1

C200HX/HG/HE Mounted directly

Host Link Unit

RS-232C port

Connecting Cables

Peripheral port

C200H-CN222/422 (2 m/4 m)

XW2Z-200S/500S (See note)

CQM1-CIF02

Programming Console Connecting Cable

Connecting Cable

Connecting Cable

Programming Device

Support Software

IBM PC/AT or Compatible

WS01-CPB1-E

SYSMAC-CPT Support Software

Programming Console for C200H

Data Access Console for C200H

Programming Console

C200H-PRO27-E

C200H-DAC01

CQM1-PRO01-E

Note The connector of the XW2Z-200S/500S Connecting Cable is a male 25-pin terminal. An adapter is required for the 9-pin male D-sub terminal on the IBM PC/AT or compatible side.

16

Page 31

Section

CPU Unit Capabilities

2-2

2-3

PC Configuration The basic PC configuration consists of two types of Rack: a CPU Rack and Expansion I/O Racks. The Expansion I/O Racks are not a required part of the basic system. They are used to increase the number of I/O points. An illustration of these Racks is provided in 3-3 IR Area. A third type of Rack, called a Slave Rack, can be used when the PC is provided with a Remote I/O System.

CPU Racks

A C200HX/HG/HE CPU Rack consists of three components: (1) The CPU Backplane, to which the CPU Unit and other Units are mounted. (2) The CPU Unit, which executes the program and controls the PC. (3) Other Units, such as I/O Units, Special I/O Units, and Link Units, which provide the physical I/O terminals corresponding to I/O points. A C200HX/HG/HE CPU Rack can be used alone or it can be connected to other Racks to provide additional I/O points. The CPU Rack provides three, five, eight, or ten slots to which these other Units can be mounted depending on the backplane used.

Expansion I/O Racks

An Expansion I/O Rack can be thought of as an extension of the PC because it provides additional slots to which other Units can be mounted. It is built onto an Expansion I/O Backplane to which a Power Supply and up to ten other Units are mounted. An Expansion I/O Rack is always connected to the CPU Unit via the connectors on the Backplanes, allowing communication between the two Racks. Up to three Expansion I/O Racks (two with the C200HE PCs) can be connected in series to the CPU Rack.

Unit Mounting Position

Only I/O Units and Special I/O Units can be mounted to Slave Racks. All I/O Units, Special I/O Units, Group-2 High-density I/O Units, Remote I/O Master Units, PC and Host Link Units, can be mounted to any slot on all other Racks. Interrupt Input Units must be mounted to Backplanes with the “-V2” suffix on the model number. Refer to the C200HX/HG/HE Installation Guide for details about which slots can be used for which Units and other details about PC configuration. The way in which I/O points on Units are allocated in memory is described in 3-3 IR Area.

2-3

CPU Unit Capabilities The following table shows the capabilities of the C200HX/HG/HE CPU Units. The and are equipped with RS-232C ports. Item

C200HE-

C200HG-

C200HX-

DM capacity

CPU11-ZE CPU32-ZE/ CPU33-ZE/ CPU53-ZE/ CPU34-ZE/ CPU54-ZE/ CPU65-ZE/ 42-ZE 43-ZE 63-ZE 44-ZE 64-ZE 85-ZE 3.2K 7.2K words 15.2K words 31.2K words 63.2K words words 4K words 6K words 6K words 6K words

EM capacity

None

6K words × 1 bank

6K words × 3 banks CPU65-ZE: 6K words × 8 banks CPU85-ZE: 6K words × 16 banks

Basic instruction execution time Max. number of Expansion I/O Racks Max. number of Group-2 High-density I/O Units Max. number of Special I/O Units

0.3 µs min.

0.15 µs min.

0.1 µs min.

2 Racks

2 Racks

3 Racks

2 Racks

3 Racks

10 Units

16 Units

10 Units

16 Units

10 Units

16 Units

10 Units

16 Units

Program capacity

None 10 Units

10 Units

0.1 µs min.

17

Page 32

Section

Memory Cassettes Item

C200HEC200HGC200HXCPU11-ZE CPU32-ZE/ CPU33-ZE/ CPU53-ZE/ CPU34-ZE/ CPU54-ZE/ CPU65-ZE/ 42-ZE 43-ZE 63-ZE 44-ZE 64-ZE 85-ZE No Yes Yes Yes

Clock function Communications Board Slot

2-4

2-4

No

Yes

Yes

Yes

Memory Cassettes The C200HX/HG/HE comes equipped with a built-in RAM for the user’s program, so a normal program be created even without installing a Memory Cassette. An optional Memory Cassette can be used to store the program, PC Setup, I/O comments, DM area and other data area contents. Refer to the C200HX/ HG/HE Installation Guide for details on installing Memory Cassettes.

Memory Cassette Functions

The Memory Cassette can be used to store and retrieve UM and IOM data; UM stored in the Memory Cassette can also be compared to the UM in the PC.

1, 2, 3...

1. The contents of UM (user memory) can be stored in the Memory Cassette for later retrieval or verification. If pin 2 of the CPU Unit DIP switch is set to ON, the contents of the Memory Cassette are automatically retrieved when the PC is turned ON. The UM area contains the ladder program, fixed DM (such as the PC Setup), expansion DM, I/O comments, the I/O table, and the UM area allocation information. 2. The contents of the PC’s I/O memory (IOM) can be stored in the Memory Cassette for later retrieval. IOM includes the IR area, SR area, LR area, HR area, AR area, timer and counter PVs, DM 0000 through DM 6143, and EM 0000 through EM 6143. UM and IOM data is completely compatible between the ZE-versions of the C200HX/HG/HE and other C200HX/HG/HE PCs, except the new instructions (symbol math and input comparison instructions) that aren’t supported by the original C200HX/HG/HE CPU Units.

Compatible Memory Cassettes

There are two types of Memory Cassette available: EEPROM and EPROM. The following table summaries the Memory Cassettes which can be used with the C200HX/HG/HE PCs. Refer to Appendix A Standard Models for actual Memory Cassette model numbers and specifications. Memory

Capacity

Comments

EEPROM

4K, 8K, 16K, 32K, or 64K words 16K or 32K words

The EEPROM Memory Cassette can be used to write and read UM and I/O data to the CPU Unit. It does not require any backup power supply and will retain its data even after it is removed from the CPU Unit. An EPROM Memory Cassette can be used only to backup and read UM data.

EPROM

Use a standard PROM writer to write the program to the EPROM Memory Cassette.

Note

1. Data stored in EEPROM won’t be reliable after the contents have been overwritten 50,000 times. 2. The EPROM chip is not included with the Memory Cassette; it must be purchased separately.

18

Page 33

Section

Memory Cassettes

2-4

2-4-1 Hardware and Software Settings The hardware and software settings related to Memory Cassette operations are described below. Switch Settings

Switch 1 on the Memory Cassette is turned OFF when the Memory Cassette is shipped. Check the setting on switch 1 before installation. Memory Cassette EEPROM EPROM

Switch 1 setting ON OFF ON OFF

SR Area Flags and Control Bits

Function The data in the Memory Cassette is write-protected. The data in the Memory Cassette can be overwritten. 27512-equivalent ROM-KD-B EPROM (32K words, 150 ns access time) 27256-equivalent ROM-JD-B EPROM (16K words, 150 ns access time)

SR 269 through SR 273 contain flags and control bits related to Memory Cassette contents and operation. Refer to 3-4 SR (Special Relay) Area for details.

2-4-2 Writing/Reading UM Data Use the following procedures to transfer UM data to or from a Memory Cassette. Note UM contains the ladder program, fixed DM (such as the PC Setup), expansion DM, I/O comments, the I/O table, and the UM area allocation information. Writing UM Data to a Memory Cassette 1, 2, 3...

Use the following procedure to write UM data to an EEPROM Memory Cassette.

Reading UM Data from a Memory Cassette

There are two ways to read UM data from a Memory Cassette: automatic transfer at startup or a one-time transfer using a Programming Device. (There is no function that automatically writes data to the Memory Cassette.) Automatic Transfer at Startup:

1. Before turning ON the C200HX/HG/HE’s power supply, make sure that switch 1 on the Memory Cassette is set to OFF. 2. Turn ON the C200HX/HG/HE and write the ladder program or read an existing program from a data disk. 3. Switch the C200HX/HG/HE to PROGRAM mode. 4. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to turn ON SR 27000 (the Save UM to Cassette Bit). The data will be written from the PC to the Memory Cassette. SR 27000 will be turned OFF automatically after the data transfer has been completed. 5. If you want to write-protect the data on the Memory Cassette, turn OFF the PC and set switch 1 of the Memory Cassette to ON. If this switch is ON, data in the Memory Cassette will be retained even if SR 27000 is turned ON.

1, 2, 3...

1. Turn ON pin 2 of the CPU Unit’s DIP switch. 2. Install the Memory Cassette containing the data into the C200HX/HG/HE. 3. Turn ON the C200HX/HG/HE’s power supply. The contents of the Memory Cassette will be transferred to the CPU Unit automatically. A memory error will occur if the data couldn’t be transferred. One-time Transfer using a Programming Device:

1, 2, 3...

1. Install the Memory Cassette containing the data into the C200HX/HG/HE. 2. Turn ON the C200HX/HG/HE and switch it to PROGRAM mode. 3. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to turn ON SR 27001 (the Load UM from Cassette Bit). The data will be read from the Memory Cassette to the PC. SR 27001 will be turned OFF automatically after the data transfer has been completed.

19

Page 34

Section

Memory Cassettes Comparing UM Data on a Memory Cassette 1, 2, 3...

2-4

Use the following procedure to the UM data on an Memory Cassette to the UM data in the PC. 1. Switch the C200HX/HG/HE to PROGRAM mode. 2. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to turn ON SR 27002 (the Compare UM to Cassette Bit). The data will be compared between the PC and the Memory Cassette. SR 27002 will be turned OFF automatically after the data comparison has been completed. 3. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to check the status of SR 27003 (the Comparison Results Flag).

Note If data verification is executed in a mode other than PROGRAM mode, an operation continuance error (FAL90) will occur and 27002 will turn ON (1). Although 27003 will also turn ON, comparison will not be performed. If data comparison is executed without mounting the Memory Cassette, 27003 will turn ON (1).

2-4-3 Writing/Reading IOM Data Use the following procedures to transfer IOM data to or from a Memory Cassette. (A PROM writer is required to write data to an EPROM Memory Cassette. Refer to the SYSMAC Support Software Operation Manual for details.) IOM includes the IR area, SR area, LR area, HR area, AR area, timer and counter PVs, DM 0000 through DM 6143, and EM 0000 through EM 6143. The capacity of the Memory Cassette must match the memory capacity of the CPU Unit when IOM data is transferred to or from a Memory Cassette. The memory requirements are as follows: Writing IOM: CPU Unit’s capacity ≤ Memory Cassette’s capacity Reading IOM: CPU Unit’s capacity = Amount of IOM data in Memory Cassette Note In C200HS PCs, the data transfer will be performed even if the memory capacities don’t match, an error which can easily go unnoticed. The following table shows the Memory Cassette capacity required to store 1 or more banks of EM. Memory Cassette capacity 4K words

Number of EM banks

8K words

None (A 4K-word Memory Cassette can’t be used to store other IOM data, either.) None

16K words

1 bank (Only EM bank 0 can be stored.)

32K words

3 banks (EM banks 0 through 2 can be stored.)

Bits 08 through 15 of SR 273 indicate the EM bank number of the IOM data stored in the Memory Cassette. Content of SR 27308 to SR 27315 00

01 04

Writing IOM Data to a Memory Cassette 1, 2, 3...

20

Meaning There is no Memory Cassette installed, no IOM data in the Memory Cassette, or no EM data in the Memory Cassette. The Memory Cassette contains IOM data that includes EM bank 0 only. The Memory Cassette contains IOM data that includes EM banks 0 through 2.

Use the following procedure to write IOM data to an EEPROM Memory Cassette. 1. Before turning ON the C200HX/HG/HE’s power supply, make sure that switch 1 on the Memory Cassette is set to OFF.

Page 35

Section

Operating without a Backup Battery

2-5

2. Turn ON the C200HX/HG/HE and switch it to PROGRAM mode. 3. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to turn ON SR 27300 (the Save IOM to Cassette Bit). The data will be written from the PC to the Memory Cassette. SR 27300 will be turned OFF automatically after the data transfer has been completed. 4. If you want to write-protect the data on the Memory Cassette, turn OFF the PC and set switch 1 of the Memory Cassette to ON. If this switch is ON, data in the Memory Cassette will be retained even if SR 27300 is turned ON. Reading IOM Data from a Memory Cassette

Use the following procedure to read IOM data from a Memory Cassette. The contents of the error history (DM 6000 through DM 6030) can’t be read from the Memory Cassette.

Note There is no function that automatically reads IOM data from the Memory Cassette. 1, 2, 3...

2-5

1. Install the Memory Cassette containing the data into the C200HX/HG/HE. 2. Turn ON the C200HX/HG/HE and switch it to PROGRAM mode. 3. Use a host computer running SYSMAC-CPT Support Software or a Programming Console to turn ON SR 27301 (the Load IOM from Cassette Bit). The data will be read from the Memory Cassette to the PC. SR 27301 will be turned OFF automatically after the data transfer has been completed.

Operating without a Backup Battery An EEPROM or EPROM Memory Cassette can be used together with various memory settings to enable operation without a backup battery. The following conditions must be met. 1, 2, 3...

1. The user program must be written to an EPROM or EEPROM Memory Cassette. 2. The clock cannot be used. (A battery is required to run the internal clock.) 3. The PC Setup must be set to not detect low battery voltage. 4. The system must be designed to run properly even if DM area data is lost. 5. The Output OFF Bit (SR 25215) must be programmed to remain OFF. (The status of this bit will be unstable without a battery.) 25314 (Always OFF Flag) 25215

6. The Forced Status Hold Bit (SR 25211) and Data Retention Control Bit (SR 25212) must be set to be cleared in the PC Setup. (The status of these bits will be unstable without a battery.) 7. The DIP switch on the CPU Unit must be set so that pin 1 is OFF and pin 2 is ON. If these conditions can be met, use the following procedures to operate without a backup battery. EEPROM Memory Cassette 1, 2, 3...

1. Allocate UM area using the SYSMAC Support Software (SSS) if you want to use Expansion DM for Special I/O Units or if you want to store I/O comments in the PC. 2. Write and transfer the user program, including a line using the Always OFF Flag (SR 25314) to ensure that the Output OFF Bit (SR 25215) remains OFF. 25314 (Always OFF Flag) 25215

21

Page 36

Section

Operating without a Backup Battery

2-5

3. Set the following in the PC Setup DM 6601 = 0000 (To reset Forced Status Hold Bit (SR 25211) and I/O Status Hold Bit (SR 25212) at startup) DM 6655 bits 12 to 15 = 1, bits 4 to 7 = 0 (To not detect low battery voltage) DM 6600 and DM 6602 to DM 6654 = As required by the application. 4. Set Fixed DM (including the Communications Board settings in DM 6144 to DM 6599) and Expansion DM as required by the application. 5. Check operation. 6. Mount the Memory Cassette in the CPU Unit. 7. Switch to PROGRAM mode. 8. Turn ON SR 27000 to transfer the program, Fixed DM, and the PC Setup to the Memory Cassette. (This bit will automatically reset itself if turned ON from a Programming Console. It will need to be turned OFF by clearing forced status if it is set from the SSS.) 9. Turn ON the write protect switch on the Memory Cassette. 10. Turn OFF pin 1 and turn ON pin 2 on the DIP switch on the CPU Unit to automatically transfer the program, Fixed DM, and the PC Setup from the Memory Cassette when power is turned ON. EPROM Memory Cassette 1, 2, 3...

1. Allocate UM area using the SYSMAC Support Software (SSS) if you want to use Expansion DM for Special I/O Units or if you want to store I/O comments in the PC. 2. Write and transfer the user program, including a line using the Always OFF Flag (SR 25314) to ensure that the Output OFF Bit (SR 25215) remains OFF. 25314 (Always OFF Flag) 25215

3. Set the following in the PC Setup DM 6601 = 0000 (To reset Forced Status Hold Bit (SR 25211) and I/O Status Hold Bit (SR 25212) at startup) DM 6655 bits 12 to 15 = 1, bits 4 to 7 = 0 (To not detect low battery voltage) DM 6600 and DM 6602 to DM 6654 = As required by the application. 4. Set Fixed DM (including the Communications Board settings in DM 6144 to DM 6599) and Expansion DM as required by the application. 5. Check operation. 6. Transfer the program, Fixed DM, and the PC Setup to the SSS. 7. Write the program, Fixed DM, and the PC Setup to ROM using the SSS and a PROM writer. 8. Mount the ROM onto the Memory Cassette. 9. Mount the Memory Cassette in the CPU Unit. 10. Turn OFF pin 1 and turn ON pin 2 on the DIP switch on the CPU Unit to automatically transfer the program, Fixed DM, and the PC Setup from the Memory Cassette when power is turned ON.

22

Page 37

Section

CPU Unit DIP Switch

2-6

2-6

CPU Unit DIP Switch The 6 pins on the DIP switch control six of the CPU Unit’s operating parameters.

Pin 1

Item Memory protect

Setting

2

Automatic transfer of Memory Cassette contents

3

Message language

OFF ON OFF

4

Expansion instruction setting

ON

5

Communications parameters

OFF ON

ON OFF ON

Function The UM area1 cannot be overwritten from a Programming Device. The UM area1 can be overwritten from a Programming Device. The contents of the Memory Cassette will be automatically transferred to the internal RAM at start-up. The contents will not be automatically transferred. Programming Console messages will be displayed in English. Programming Console messages will be displayed in the language stored in system ROM. (Messages will be displayed in Japanese with the Japanese version of system ROM.) Expansion instructions will be set by user. Normally ON when using a host computer for programming/monitoring. Expansion instructions set to defaults. Standard communications parameters (see note 1) will be set for the following serial communications ports. • Built-in RS-232C port • Peripheral port (only when a CQM1-CIF01/-CIF02 Cable is connected. Does not apply to Programming Console.) Note 1. Standard communications parameters are as follows: Serial communications mode: Host Link or peripheral bus; start bits: 1; data length: 7 bits; parity: even; stop bits: 2; baud rate: 9,600 bps 2. The CX-Programmer running on a personal computer can be connected to the peripheral port via the peripheral bus using the above standard communications parameters.

OFF

6

Expansion TERMINAL mode setting when AR 0712 is ON

Note

ON OFF

The communications parameters for the following serial communications ports will be set in PC Setup as follows: • Built-in RS-232C port: DM 6645 and DM 6646 • Peripheral port: DM 6650 and DM 6651 Note When the CX-Programmer is connected to the peripheral port with the peripheral bus, either set bits 00 to 03 of DM 6650 in the Fixed DM Area to 0 Hex (for standard parameters), or set bits 12 to 15 of DM 6650 to 0 Hex and bits 00 to 03 of DM 6650 to 1 Hex (for Host Link or peripheral bus ) separately. Expansion TERMINAL mode (Programming Console); AR 0712 ON. Normal mode (Programming Console); AR 0712: OFF

1. The UM area contains the ladder program, fixed DM (including the PC Setup), expansion DM, I/O comments, the I/O table, and the UM area allocation information. 2. All six pins are set to OFF when the PC is shipped.

23