Page 502

SECTION 10 Host Link Commands This section describes the host link commands which can be used for host link communications via the C200HX/HG/HE ports. Refer to 8-2 Host Link Communications for information on the procedures for using host link commands and errors associated with host link commands. 10-1 Host Link Command Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2 Host Link End Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2-1 End Code Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2-2 Command/End Code Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3 Host Link Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-1 IR/SR AREA READ –– RR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-2 LR AREA READ –– RL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-3 HR AREA READ –– RH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-4 PV READ –– RC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-5 TC STATUS READ –– RG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-6 DM AREA READ –– RD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-7 AR AREA READ –– RJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-8 EM AREA READ –– RE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-9 IR/SR AREA WRITE –– WR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-10 LR AREA WRITE –– WL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-11 HR AREA WRITE –– WH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-12 PV WRITE –– WC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-13 TC STATUS WRITE –– WG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-14 DM AREA WRITE –– WD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-15 AR AREA WRITE –– WJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-16 EM AREA WRITE –– WE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-17 SV READ 1 –– R# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-18 SV READ 2 –– R$ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-19 SV READ 3 –– R% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-20 SV CHANGE 1 –– W# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-21 SV CHANGE 2 –– W$ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-22 SV CHANGE 3 –– W% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-23 STATUS READ –– MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-24 STATUS WRITE –– SC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-25 ERROR READ –– MF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-26 FORCED SET –– KS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-27 FORCED RESET –– KR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-28 MULTIPLE FORCED SET/RESET –– FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-29 FORCED SET/RESET CANCEL –– KC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-30 PC MODEL READ –– MM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-31 TEST–– TS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-32 PROGRAM READ –– RP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-33 PROGRAM WRITE –– WP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-34 I/O TABLE GENERATE –– MI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-35 COMPOUND COMMAND –– QQMR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-36 COMPOUND COMMAND DATA READ –– QQIR . . . . . . . . . . . . . . . . . . . . . . 10-3-37 ABORT –– XZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-38 INITIALIZE –– . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-39 TXD RESPONSE –– EX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3-40 Undefined Command –– IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

496 497 497 499 500 500 501 502 503 504 505 506 506 507 508 509 510 511 512 513 514 515 516 518 519 520 522 523 525 526 527 528 530 531 532 533 534 535 536 537 538 539 540 540 541

495

Page 503

Section 10-1

Host Link Command Summary

10-1 Host Link Command Summary Command Chart

The commands listed in the chart below can be used for host link communications with the C200HX/HG/HE. PC mode

Header code RUN

Name

MON

Page

PRG

RR

Valid

Valid

Valid

IR/SR AREA READ

500

RL

Valid

Valid

Valid

LR AREA READ

501

RH

Valid

Valid

Valid

HR AREA READ

502

RC

Valid

Valid

Valid

PV READ

503

RG

Valid

Valid

Valid

TC STATUS READ

504

RD

Valid

Valid

Valid

DM AREA READ

505

RJ

Valid

Valid

Valid

AR AREA READ

506

RE

Valid

Valid

Valid

EM AREA READ

506

WR

Not valid

Valid

Valid

IR/SR AREA WRITE

507

WL

Not valid

Valid

Valid

LR AREA WRITE

508

WH

Not valid

Valid

Valid

HR AREA WRITE

509

WC

Not valid

Valid

Valid

PV WRITE

510

WG

Not valid

Valid

Valid

TC STATUS WRITE

511

WD

Not valid

Valid

Valid

DM AREA WRITE

512

WJ

Not valid

Valid

Valid

AR AREA WRITE

513

WE

Not valid

Valid

Valid

EM AREA WRITE

514

R#

Valid

Valid

Valid

SV READ 1

515

R$

Valid

Valid

Valid

SV READ 2

516

R%

Valid

Valid

Valid

SV READ 3

518

W#

Not valid

Valid

Valid

SV CHANGE 1

519

W$

Not valid

Valid

Valid

SV CHANGE 2

520

W%

Not valid

Valid

Valid

SV CHANGE 3

522

MS

Valid

Valid

Valid

STATUS READ

523

SC

Valid

Valid

Valid

STATUS WRITE

525

MF

Valid

Valid

Valid

ERROR READ

526

KS

Not valid

Valid

Valid

FORCED SET

527

KR

Not valid

Valid

Valid

FORCED RESET

528

FK

Not valid

Valid

Valid

MULTIPLE FORCED SET/RESET

530

KC

Not valid

Valid

Valid

FORCED SET/RESET CANCEL

531

MM

Valid

Valid

Valid

PC MODEL READ

532

TS

Valid

Valid

Valid

TEST

533

RP

Valid

Valid

Valid

PROGRAM READ

534

WP

Not valid

Not valid

Valid

PROGRAM WRITE

535

MI

Not valid

Not valid

Valid

I/O TABLE GENERATE

536

QQ

Valid

Valid

Valid

COMPOUND COMMAND

537

XZ

Valid

Valid

Valid

ABORT (command only)

539

Valid

Valid

Valid

INITIALIZE (command only)

540

EX

Valid

Valid

Not valid

TXD RESPONSE (response only)

540

IC

---

---

---

Undefined command (response only)

541

496

Page 504

Section 10-2

Host Link End Codes

10-2 Host Link End Codes 10-2-1 End Code Summary These are the response (end) codes that are returned in the response frame. When two or more errors occur, the end code for the first error will be returned. End code

Contents

Probable cause

Corrective measures

00

Normal completion

---

---

01

Not executable in RUN mode

The command that was sent cannot be executed when the PC is in RUN mode.

Check the relation between the command and the PC mode.

02

Not executable in MONITOR mode

The command that was sent cannot be executed when the PC is in MONITOR mode.

03

UM write-protected

The PC’s UM is write-protected.

Turn OFF pin 1 of the CPU Unit’s DIP switch.

04

Address over

The program address setting in an SV Read or SV Change command is above the highest program address but less than 65,536.

Correct the program address setting and transfer the command again.

13

FCS error

The FCS is wrong. Either the FCS calculation is mistaken or there is adverse influence from noise.

Check the FCS calculation method. If there was influence from noise, transfer the command again.

14

Format error

The command format is wrong or a command that can’t be divided has been divided.

Check the format and transfer the command again.

15

Entry number data error

The data is outside of the specified range or too long.

Correct the data and transfer the command again.

16

Command not supported

The operand specified in an SV Check the command and program. Read or SV Change command does not exist in the program.

18

Frame length error

The maximum frame length of 132 bytes was exceeded. (If the frame exceeds 280 bytes, the Reception Overflow Flag will be turned ON and there won’t be a response.)

Check the command and divide it into multiple frames if necessary.

19

Not executable

Items to read not registered for composite command (QQ).

Execute QQ to register items to read before attempting batch read.

20

Couldn’t create I/O table

Unrecognized Remote I/O Unit, too many I/O words, or node number duplication for Remote Optical I/O Units.

Check the Remote I/O System and the number of I/O words.

23

User memory protected

Pin 1 on C200HX/HG/HE DIP switch is ON.

Turn OFF pin 1 of the CPU Unit’s DIP switch.

A3

Aborted due to FCS error in transmit data

An FCS error occurred in the second or later frame.

Check the FCS calculation method. If there was influence from noise, transfer the command again.

A4

Aborted due to format error in transmit data

The command format did not match the number of bytes in the second or later frame.

Check the format and transfer the command again.

A5

Aborted due to entry number data error in transmit data

There was a entry number data error in the second or later frame.

Correct the data and transfer the command again.

A8

Aborted due to frame length error in transmit data

The length of the second or later frame exceeded the 132-byte max.

Keep frames to 132 bytes or fewer.

497

Page 505

Section 10-2

Host Link End Codes Errors without Responses

A response won’t be received with some errors, regardless of the command. These errors are listed in the following table.

Error Parity overrun or framing error during command reception

PC operation The Communications Error Flag will be turned ON, an error code will be registered, and receptions will be reset. (The error will be cleared automatically if communications restart normally.)

A carriage return (CR) isn’t received within 280 bytes.

SR 26407 (RS-232C Port Reception Overflow Flag) will be turned ON. Communications return to normal when a normal command is transmitted.

A command is received that doesn’t have the @ character at the beginning of the first frame. Incorrect node number (Not the local node, hexadecimal, or over 31) A Write command’s intermediate frame or last frame has only one or two bytes of data.

Receptions are reset.

498

The command is discarded and receptions are reset. FCS error

Page 506

Section 10-2

Host Link End Codes

10-2-2 Command/End Code Table The following table shows which end codes can be returned for each command. Header

Possible End Codes

Comments

RR

00

13

14

15

18

A3

A8

---

RL

00

13

14

15

18

A3

A8

---

RH

00

13

14

15

18

A3

A8

---

RC

00

13

14

15

18

A3

A8

---

RG

00

13

14

15

18

A3

A8

---

RD

00

13

14

15

18

A3

A8

---

RJ

00

13

14

15

18

RE

00

13

14

15

18

A3

A8

---

WR

00

01

13

14

15

18

A3

A4

A5

A8

---

WL

00

01

13

14

15

18

A3

A4

A5

A8

---

WH

00

01

13

14

15

18

A3

A4

A5

A8

---

WC

00

01

13

14

15

18

A3

A4

A5

A8

---

WG

00

01

13

14

15

18

A3

A4

A5

A8

---

WD

00

01

13

14

15

18

WJ

00

01

13

14

15

18

WE

00

01

13

14

15

R#

00

13

14

15

16

18

23

---

R$

00

04

13

14

15

16

18

23

---

R%

00

04

13

14

15

16

18

23

---

W#

00

01

13

14

15

16

18

23

---

W$

00

01

04

13

14

15

16

18

23

---

W%

00

01

04

13

14

15

16

18

23

---

MS

00

13

14

SC

00

13

14

15

18

MF

00

13

14

15

18

---

KS

00

01

13

14

15

18

---

KR

00

01

13

14

15

18

---

FK

00

01

13

14

15

18

---

KC

00

13

14

18

---

MM

00

---

TS RP

00

WP

00

01

02

MI

00

01

02

QQ

00

03

14

18

14

18

13

14

18

14 14

13

14

A3

A4

A5

A8

---

A3

A4

A5

A8

---

A3

A4

A5

A8

---

18

13

13

23

18

13

13

---

15

18

--19

--19

18 15

18

---

23

A3

23

A3

A4

A5

A8

---

A8

---

20 19

--A3

A4

A5

A8

---

XZ

---

No response

---

No response

EX

---

No end code

IC

---

No end code

499

Page 507

Section 10-3

Host Link Commands

10-3 Host Link Commands This section explains the various Host Link commands that can be issued from the host computer to the PC. Refer to 8-2 Host Link Communications for information on the procedures for using host link commands and errors associated with host link commands.

10-3-1 IR/SR AREA READ –– RR Reads the contents of the specified number of IR and SR words, starting from the specified word. Command Format @ x 101 x 100

Node no.

R

R

Header code x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning word (0000 to 0511)

No. of words (0001 to 0512)

FCS

↵

Terminator

Response Format @ x 101 x 100

Node no.

R

R

Header code x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word)

FCS

↵

Terminator

Read data (for number of words read)

Limitations

The text portion of the response’s first frame can contain up to 30 words. If more than 30 words are read, the data will be returned in multiple frames. In the second and later frames, the text portion of the response can contain up to 31 words. The INITIALIZE and ABORT commands can be sent instead of the delimiter for multiple responses for this command. If other commands are sent, they will be treated the same as delimiters.

PC Settings RUN OK

PC Mode MONITOR OK

PROGRAM OK

UM Area Write-protected Read-protected OK OK

Execution Conditions Commands Single OK

End Codes

Responses Multiple ---

Multiple OK

An end code of 14 (format error) will be returned if the length of the command is incorrect and an end code of 15 (entry number data error) will be returned if the specified words exceed the data area boundaries or aren’t specified in BCD. End code

500

Single OK

Contents

00

Normal completion

13

FCS error

14

Format error

15

Entry number data error

18

Frame length error

A3

Aborted due to FCS error in transmit data

A8

Aborted due to frame length error in transmit data

Page 508

Section 10-3

Host Link Commands

10-3-2 LR AREA READ –– RL Reads the contents of the specified number of LR words, starting from the specified word. Command Format @ x 101 x 100

Node no.

R

L

Header code x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning word (0000 to 0063)

No. of words (0001 to 0064)

FCS

↵

Terminator

Response Format @ x 101 x 100

Node no.

R

L

Header code x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word)

FCS

↵

Terminator

Read data (for number of words read)

Limitations

The text portion of the response’s first frame can contain up to 30 words. If more than 30 words are read, the data will be returned in multiple frames. In the second and later frames, the text portion of the response can contain up to 31 words. The INITIALIZE and ABORT commands can be sent instead of the delimiter for multiple responses for this command. If other commands are sent, they will be treated the same as delimiters.

PC Settings RUN OK

PC Mode MONITOR OK

PROGRAM OK

UM Area Write-protected Read-protected OK OK

Execution Conditions Commands Single OK

End Codes

Responses Multiple ---

Single OK

Multiple OK

An end code of 14 (format error) will be returned if the length of the command is incorrect and an end code of 15 (entry number data error) will be returned if the specified words exceed the data area boundaries or aren’t specified in BCD. End code

Contents

00

Normal completion

13

FCS error

14

Format error

15

Entry number data error

18

Frame length error

A3

Aborted due to FCS error in transmit data

A8

Aborted due to frame length error in transmit data

501

Page 509

Section 10-3

Host Link Commands

10-3-3 HR AREA READ –– RH Reads the contents of the specified number of HR words, starting from the specified word. Command Format @ x 101 x 100

Node no.

R

H

Header code x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning word (0000 to 0099)

No. of words (0001 to 0100)

FCS

↵

Terminator

Response Format @ x 101 x 100

Node no.

Limitations

R

H

Header code x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word)

FCS

↵

Terminator

Read data (for number of words read)

The text portion of the response’s first frame can contain up to 30 words. If more than 30 words are read, the data will be returned in multiple frames. In the second and later frames, the text portion of the response can contain up to 31 words. The INITIALIZE and ABORT commands can be sent instead of the delimiter for multiple responses for this command. If other commands are sent, they will be treated the same as delimiters.

PC Settings RUN OK

PC Mode MONITOR OK

PROGRAM OK

UM Area Write-protected Read-protected OK OK

Execution Conditions Commands Single OK

End Codes

Responses Multiple ---

Multiple OK

An end code of 14 (format error) will be returned if the length of the command is incorrect and an end code of 15 (entry number data error) will be returned if the specified words exceed the data area boundaries or aren’t specified in BCD. End code

502

Single OK

Contents

00

Normal completion

13

FCS error

14

Format error

15

Entry number data error

18

Frame length error

A3

Aborted due to FCS error in transmit data

A8

Aborted due to frame length error in transmit data

Page 510

Section 10-3

Host Link Commands

10-3-4 PV READ –– RC Reads the contents of the specified number of timer/counter PVs (present values), starting from the specified timer/counter. Command Format @ x 101 x 100

Node no.

R

C x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Header code

Beginning timer/counter (0000 to 0511)

R x 161 x 160 x 103 x 102 x 101 x 100

No. of timers/counters (0001 to 0512)

FCS

↵

Terminator

Response Format @ x 101 x 100

Node no.

Limitations

C

Header code

End code

Read data (1 word) Read data (for number of words read)

FCS

↵

Terminator

The text portion of the response’s first frame can contain up to 30 words. If more than 30 words are read, the data will be returned in multiple frames. In the second and later frames, the text portion of the response can contain up to 31 words. The INITIALIZE and ABORT commands can be sent instead of the delimiter for multiple responses for this command. If other commands are sent, they will be treated the same as delimiters.

PC Settings RUN OK

PC Mode MONITOR OK

PROGRAM OK

UM Area Write-protected Read-protected OK OK

Execution Conditions Commands Single OK

End Codes

Responses Multiple ---

Single OK

Multiple OK

An end code of 14 (format error) will be returned if the length of the command is incorrect and an end code of 15 (entry number data error) will be returned if the specified words exceed the data area boundaries or aren’t specified in BCD. End code

Contents

00

Normal completion

13

FCS error

14

Format error

15

Entry number data error

18

Frame length error

A3

Aborted due to FCS error in transmit data

A8

Aborted due to frame length error in transmit data

503

Page 511

Section 10-3

Host Link Commands

10-3-5 TC STATUS READ –– RG Reads the status of the Completion Flags of the specified number of timers/ counters, starting from the specified timer/counter. A “1” indicates that the Completion Flag is ON. Command Format @ x 101 x 100

Node no.

R

G

Header code x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning timer/counter (0000 to 0511)

No. of timers/counters (0001 to 0512)

FCS

↵

Terminator

Response Format @ x 101 x 100 Node no.

R

G

Header code x 161 x 160 ON/ OFF

End code

FCS

↵

Terminator

Read data (1 timer/counter) Read data (for number of TC read)

Limitations

The text portion of the response’s first frame can contain up to 121 words. If more than 121 words are read, the data will be returned in multiple frames. In the second and later frames, the text portion of the response can contain up to 124 words. The INITIALIZE and ABORT commands can be sent instead of the delimiter for multiple responses for this command. If other commands are sent, they will be treated the same as delimiters.

PC Settings RUN OK

PC Mode MONITOR OK

PROGRAM OK

UM Area Write-protected Read-protected OK OK

Execution Conditions Commands Single OK

End Codes

Responses Multiple ---

Multiple OK

An end code of 14 (format error) will be returned if the length of the command is incorrect and an end code of 15 (entry number data error) will be returned if the specified words exceed the data area boundaries or aren’t specified in BCD. End code

504

Single OK

Contents

00

Normal completion

13

FCS error

14

Format error

15

Entry number data error

18

Frame length error

A3

Aborted due to FCS error in transmit data

A8