For the Omron CPM1A-8ED
Page 9
CPM1A
CPM1A J ANALOG I/O MODULE Item
Specification
Model
CPM1A–MAD01
I/O type
Voltage
Analog inputs
Current
2
Input signal range
0 to 10 V or 1 to 5 V
4 to 20 mA
Maximum rated input
±15 V
±30 mA
External input impedance
1 MΩ min.
250 Ω rated
Resolution
1/256
Overall precision
1.0% of full scale
Converted A/D data
8-bit binary
Number of outputs
1
Output signal range
0 to 10 V or –10 to 10 V
4 to 20 mA
External output max. current
5 mA, External output allowed load resistance, 350 Ω
Resolution
1/256 (1/512 when the output signal range is –10 to 10 V.)
Overall precision
1.0% of full scale
Data setting
8-bit binary with sign bit
Analog output (See Note 1.)
Number of inputs
Conversion time (See Note 2.)
10 ms/Unit max.
Isolation method
Photocoupler isolation between I/O terminals and PC (There is no isolation between the analog I/O signals.)
Note: 1. The voltage output and current output can be used at the same time, but the total output current cannot exceed 21 mA. 2. The conversion time is the total time for 2 analog inputs and 1 analog output.
J TEMPERATURE SENSOR MODULES By connecting a Temperature Sensor Module (CPM1A-TS001/TS002/TS101/TS101A/TS102) to the CPM1A, inputs can be received from thermocouples or temperatureresistance thermometers. Inputs converted to binary data (4-digit hexadecimal) and stored in the IR area.
Specifications Item
Specification
Model
CPM1A-TS001/TS002
CPM1A-TS101/TS102
CPM1A-TS101-DA
Number of inputs
TS001: 2; TS002: 4
TS101: 2; TS102: 4
2
Input types (See Note 1)
Thermocouple types K or J, selectable Platinum resistance thermometer types Pt100 and JPt1100, selectable
Input resolution
0.1°C in 2’s complement format
0.1°C in 2’s complement format
Input accuracy
±0.5% or ±2% of the stored value whichever is larger ±1 digit max. (See Note 2)
±0.5% or ±1% of the stored value whichever is larger ±1 digit max. (See Note 2)
1.0% max. full scale
Number of outputs
None
None
1
Output types, - Voltage or current output
Output resolution, - 1/256 (0 to 10 V) 1/512 (–10 to +10 V) 1/256 (4 to 20 mA)
Output accuracy, - 1.0% max. full scale
Conversion cycle
250 ms for all points
60 ms max. for all points
Converted temperature data
Binary data (4-digit hexadecimal)
Binary data (8-digit hexadecimal)
Isolation method
Photocoupler isolation between I/O terminals and the PLC
Note: 1. The same input type must be used for all inputs. 2. Accuracy for K thermocouples at temperatures less than –100°C: ±4°C ± 1 digit max.
9
Page 10
CPM1A
CPM1A
Input Temperature Ranges for CPM1A-TS001/TS002 The rotary switch can be used to make of the following range and input type settings for CPM1A-TS001/002 models. Thermocouple input
Range (°C)
Range (°F)
Type K
–200 to 1300
–300 to 2300
0.0 to 500.0
0.0 to 900.0
–100 to 850
–100 to 1500
0.0 to 400.0
0.0 to 750.0
Type J
Input Temperature Ranges for CPM1A-TS101/TS101DA/TS102 The rotary switch can be used to make of the following range and input type settings for CPM1A-TS101/102 models. Platinum RTD input
Range (°C)
Range (°F)
Pt100
–200.0 to 650.0
–300 to 1200.0
JPt100
–200.0 to 650.0
–300 to 1200.0
J COMMUNICATIONS ADAPTER RS-232C Adapter and RS-422 Adapter Model
CPM1-CIF01
CPM1-CIF11
Functions
Level conversion between the CMOS level (CPU side) and the RS-232C (peripheral device side)
Level conversion between the CMOS level (CPU side) and the RS-422 (peripheral device side)
Insulation
The RS-232C (peripheral device side) is insulated by a DC/DC converter and photocoupler.
The RS-422 (peripheral device side) is insulated by a DC/DC converter and photocoupler.
Power supply
Power is supplied by the CPU.
Power consumption
0.3 A max.
Transmission speed
38.4 kbits/s max.
Vibration resistance
10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 1 G in the X, Y and Z directions for 80 minutes each (i.e. for 8 minutes each, 10 times).
Shock resistance Ambient temperature
1.5 G in the X, Y and Z directions 3 times each. Operating
0°C to 55°C (32°F to 131°F)
0°C to 55°C (32°F to 131°F)
Storage
–20°C to 75°C (–4°F to 167°F)
–20°C to 75°C (–4°F to 167°F)
Ambient humidity
Operating
10% to 90% RH (with no condensation)
Ambient environment
Operating
With no corrosive gas
Weight
10
200 g max.
Page 11
CPM1A
CPM1A J COMPOBUS/S I/O LINK MODULE
The CPM1A controller can function as a Slave to a CompoBus/S Master Module (or SRM1 CompoBus/S Master Control Module) when a CPM1A-SRT21 CompoBus/S I/O Link Module is connected. The CompoBus/S I/O Link Module establishes an I/O link of 8 inputs and 8 outputs between the Master Module and the CPM1A. Up to 3 Expansion I/O Modules or Expansion Modules can be connected to a CPM1A CPU Unit. CompoBus/S Master Module (or SRM1 CompoBus/S Master Control Module)
CPM1A-SRT21 CompoBus/S I/O Link Module
CPM1A CPU Unit
CS1j, C200Hj, CQM1 (H), or SRM1 PC Up to 16 Slaves can be connected. (Up to 8 Slaves with the CQM1-SRM21-V1.)
Flat cable SCA1-4F10 or twisted pair Belden #9409 cable
Specifications Model
CPM1A-SRT21
Master/Slave
CompoBus/S Slave
Number of I/O bits
8 input bits, 8 output bits
Number of words occupied in CPM2A I/O memory
1 input word, 1 output word (Allocated in the same way as other Expansion I/O Modules or Expansion Modules)
Node number setting
Set using the DIP switch.
Note: See the CompoBus/S section of Omron’s Remote I/O and Wiring Solutions Catalog (GC RIO1) for more details on CompoBus/S communications.
Dimensions Unit: mm (inch)
J CPU, EXPANSION I/O AND SPECIAL I/O MODULES
90 (3.54)
W
50 (1.97) DC power supply 85 (3.35) AC power supply
Model
W
CPM1A-10CDj-A/D
66 (2.60)
CPM1A-20CDj-A/D
86 (3.39)
CPM1A-30CDj-A/D
130 (5.12)
CPM1A-40CDj-A/D
150 (5.91)
CPM1A-20CAR-A
130 (51.2)
CPM1A-32CAR-A
150 (5.91)
CPM1A-20EDj
86 (3.39)
CPM1A-8Ej
66 (2.60)
CPM1A-SRT21
66 (2.60)
CPM1A-MAD01
66 (2.60)
CPM1A-TSjjj
86 (3.39)
11
Page 12
CPM1A
CPM1A
Unit: mm (inch)
J COMMUNICATION ADAPTER MODULES CPM1-CIF01
CPM1-CIF11 30 (1.18)
30 (1.18) 56 (2.20) 50
21
21
90 (3.54)
90 (3.54)
81
81
J DIMENSIONS WITH PERIPHERAL DEVICES ATTACHED Approx. 90 (3.54)
12
Approx. 125 (4.92)
61 (2.40) 50
Page 13
CPM1A
CPM1A
Functions J CONFIGURATION The CPM1A CPU units feature a compact, one-piece construction that includes 10, 20, 30 or 40 built-in I/O terminals. Three output models are available: Relay outputs, sinking (NPN) transistor output and sourcing (PNP) transistor output.
CPM1A-10CDj-j (10 I/O terminals)
CPM1A-20CDj-j (20 I/O terminals)
CPM1A-30CDj-j (30 I/O terminals)
CPM1A-40CDj-j (40 I/O terminals)
Expansion Up to three Expansion I/O Modules can be connected to a 30-point or 40-point CPU Unit to add an extra 8 or 20 I/O points for each, for a maximum of up to 100 I/O points.
Dedicated I/O Modules Up to 3 Analog I/O Modules or Temperature Sensor Input Modules can be used with 30-point and 40-point CPU Units. Each analog I/O module provides 2 analog inputs and 1 analog output, so a maximum of 6 analog inputs and 3 analog outputs can be achieved by connecting 3 Analog I/O Modules. Each Temperature Sensor Module provides two temperature sensor inputs from either thermocouples or platinum resistance thermometers. Up to 6 inputs can be connected.
J INTERRUPT INPUTS There are two input interrupts in the CPM1A 10-point I/O CPU and four in the 20-, 30-, and 40-point I/O CPUs. Input interrupts are available in two modes.. In addition to normal interrupt inputs, the CPM1A has a counter mode that counts high-speed input signals and triggers interrupts at fixed count multiples.
Application Example: 10 point I/O CPU
20, 30, and 40 point I/O CPU
Cutting Metal Sheets to Specified Lengths The proximity sensor detects the edge of a metal plate to operate the cutter. Metal sheets can be cut continuously to the specified lengths at a high speed. Metal sheets
Cutter
Cutter operation signal
Conveyor
Proximity sensor Input interrupt
CPM1A
Input Interrupt Mode If an input interrupt occurs, the regular program shuts down irrelevant of the cycle time, and the interrupt processing program is executed immediately.
Regular program
Regular program
Interrupt program
Input interrupt
13
Page 14
CPM1A
CPM1A
Counter Mode When the number of external signals counted at high speed reaches a specified number of counts, the regular program shuts down, and the interrupt processing program is executed at fixed counts. The count can be set between 0 and 65535.
Regular program
Regular program
Interrupt program
Input interrupt
Counter setting
J QUICK-RESPONSE INPUTS Quick-response inputs can detect input signals with a pulse width as short as 0.2 ms regardless of their timing during the scan cycle. Quick-response inputs and interrupt inputs use the same input terminals.
CPU
Input no.
Minimum input pulse width
10 point I/O CPU
00003 to 00004
0.2 ms
20 point, 30 point, 40 point I/O CPU
00003 to 00006
Application Example: Overseeing processes
Program execution
0.2 ms min Input signal (00003)
I/O refreshing
Overseeing Program processes execution
I/O refreshing
Calculating the Number of Chips The metal sensor counts the number of parts that have passed. Steady counting can be achieved even when the input-ON time is short. CPM1A
IR 00003 One cycle F2LP-WK4 F2LP-W
14
Page 15
CPM1A
CPM1A J HIGH-SPEED COUNTER The CPM1A has a high-speed counter function that can be used in the incrementing and up/down mode. Using this function together with the input interrupts enables zone comparison control or target value control irrelevant of the cycle time.
Counting mode
Incrementing mode
Up/Down mode
Input no.
00000
Count input
A-phase input
00001, B-phase input
00002
Reset input
Z-phase input
Input method
Single-phase input
Phase-difference, 4× inputs
Count frequency
5.0 kHz
2.5 kHz
Count range
0 to 65535
–32767 to 32767
Note: When using in the incrementing mode, the input 00001 can be used as an input contact. Count input
00000 00001 00002
Reset input Solenoid
Sensor
Rotary encoder
Inverter, etc.
15
Page 16
CPM1A
CPM1A
J INTERVAL TIMER INTERRUPTS The CPM1A has one interval timer. The interval timer shuts down the regular program regardless of the point in the cycle once the time is up, and immediately executes an interrupt processing program. Interval timers are used in the following two modes. Item
One-shot mode
Scheduled interrupt mode
Operation
An interrupt is executed only once when the time is up.
Interrupts are executed repeatedly at fixed periods.
Setting time
0.5 ms to 319,968 ms (0.1-ms units)
Application Example:
Normal program
Computing the Sheet Speed The number of pulse inputs is computed in the interrupt mode at a fixed time to calculate the speed.
Interval timer MOV(21) ADD(30)
CPM1A
Interrupt processing program Encoder SBN(92) 00
MOV(21)
RET(93) END(01)
J ANALOG SETTING The CPM1A contains two analog setting controls that can be used for a broad range of analog timer and counter settings. Turning the setting control stores values of 0 to 200 (BCD data) in the SR area. Analog setting
Storage area
Setting value (BCD)
Analog setting 0
SR 250
0000 to 0200
Analog setting 1
SR 251
Application Example: Analog setting 0 Analog setting 1 *Phillips screwdriver is required.
Tact Operation Control of Conveyor Lines A conveyor can be stopped temporarily as required for assembly processes. When the timer function and limit switches are used in a combination, conveyors can be stopped for a fixed time or can be run at a constant speed for a fixed distance. Fine adjustment of the stopping time can be easily done by using the analog setting controls.
CPM1A LS
Motor
16