Applications Section 1-4

36

Downloaded from www.Manualslib.com manuals search engine

Page 42 read from a scan by OCR; it may hold reading errors

SECTION 2 Position Proportional Control

2-1 What is Position Proportional Control ... 38 2-1-1 Closed Control ... 38 2-1-2 Floating Control ... 38 2-1-3 Start-Up Procedure ... 39

2-2 Operation and Tuning .......... 00. e eee tenes A 2-2-1 Operation at Process Value Error ... 41 2-2-2 Valve Hysteresis and Dead Band ... 42 2-2-3 Configuring the ES100 Front Panel ... 43 2-2-4 Motor Calibration and Travel Time ... 45 2-2-5 Travel Time with Floating Control ... 46 2-2-6 Autotuning ... 47 2-2-7 Fuzzy Logic Fine Tuning ... 48

2-3 Applications ... 50 2-3-1 Bread Baking OVen ... 50 2-3-2 Drying Furnace ... 51

37

Downloaded from www.Manualslib.com manuals search engine

Page 43 read from a scan by OCR; it may hold reading errors

What is Position Proportional Control Section 2-1

2-1 What is Position Proportional Control

Position Proportional Control is a feature of the ES100 which is used to control steam, cooling water, or some fluid/gas substance by controlling valve positioning. It is used in conjunction with a PID algorithm that produces a manipulated variable which is used by the controller to position the valve. There are two types of position proportional control: closed and floating.

2-1-1 Closed Control

A Position Proportional Control using a potentiometer incorporated into a control valve is called a CLOSED CONTROL LOOP. In this system, the valve opening is converted into a resistance value that is fed back into the controller. Then the valve is rotated forward or reverse until the opening (in degrees) matches the value output with the manipulated variable.

In the following example, the temperature in a furnace is controlled by adjusting the fuel flow to the furnace.

Thermocouple

é fa = AO1 Me 402 ES100-RRP Control a signal Furnace Slidewire feedback

Sk

Valve

Figure 1

Alt

In (Figure 1) we are reading the temperature from a thermocouple in the furnace. We are also reading the exact position of the valve using a potentiometer (slidewire feedback). Using the two relays in the ES100, the controller will send OPEN or CLOSE signals to adjust the valve. The potentiometer feed back lets the ES100 know exactly how wide the valve is open and prevents damage to the valve from over travel.

2-1-2 Floating Control

In a floating control loop, the valve is controlled without using a potentiometer and there is no mechanical feedback from the valve to provide the controller with its exact position (Figure 2).

Thermocouple

* T mu AO1 ES100-RRP Control signal A Furnace sk

Valve

Figure 2

38

Downloaded from www.Manualslib.com manuals search engine

Page 44 read from a scan by OCR; it may hold reading errors

What is Position Proportional Control Section 2-1

The ES100 operates by sending a signal for the valve to OPEN. Based upon the elapsed time that the valve was energized, the ES100 will estimate the actual position of the valve. The Floating Control Loop functions by convert-ing the elapsed time the valve was open or closed into a value that the ES100 can use to determine the position of the valve (Figure 3).

| Valve Y Fully closed y, - + |_ - $$ - _ - - - _ = Fuel flow Valve | Output 50% open Total time needed ‘ ; = a > for valve to be Active Fuel flow 100% open is 20 s.

ES100 for 10s

108 ~ 50 or 50% open 20s

Figure 3

There are several advantages to using Floating Control Loops over that of Closed Control Loops:

1. The control performance is not affected by potentiometer wear and contact failure.

2. Floating Control Loops are more resistive to noise which improves reli-ability and the safety of the system.

3. Floating Control Loops eliminate the need for potentiometer wiring. Saves control valve costs by eliminating the potentiometer.

The disadvantages of Floating Control Loops when compared to a Closed Control Loop are:

1. There is no proportional action in the control loop. 2. There is no Manipulated Variable limiter.

Note: With floating control, the MV upper and lower limits are disabled. When they are required, you must provide the limiting operation directly to the valve.

2-1-3 Start-Up Procedure

Note: For the following procedures the ES100 should be powered up and connected to the correct port of the computer running ES/TOOLS via the RS-232 cable. For Position Proportional Control, use ES100X or ES100P with the suffix “RRP”. (ES100_-RRP____).

1. Position Proportional Control cannot be performed if any other ES100 model number is used.

2. Since the control output module E53-R is installed in the unit, there is no need to purchase another output module unless replacement is required.

39

Downloaded from www.Manualslib.com manuals search engine

Page 45 read from a scan by OCR; it may hold reading errors

What is Position Proportional Control Section 2-1

In order to get the controller up and running the quickest way, we will only program selected items. There will not be a need to do any advanced programming at this time.

Figure 4 shows an ES100-RRP using a K type thermocouple as Analog Input 1, and both outputs are being used to control the position of the valve (Analog Out 1, 2). The position of the valve is known from a potentiometer feedback.

Thermocouple

Alt, - _

> - - _>| ES100-RRP Control i | Slidewire “one Furnace feedback | | Valve Figure 4

ES100 Wiring Diagram

For closed control, a potentiometer is required. If no potentiometer is connected to the ES100 when it is configured for closed control, an error code will be displayed and control of the process cannot continue. The Manipulated Variable or MV, will go to a default value (Figure 5).

A potentiometer with a resistance value in the 100 - 2.5 KQ range should be used. For floating control, no potentiometer is required.

Not used (8) | © So 2) ; ® ae S| © 063, Power 24 | TS suppl @®----- 3 ; w 62. 3 Closed co c 6). &_. ®' output @ | ne | ‘Open output ~~ | | 1 B 1 ! @) Relay output |, a) ) on ' Relay output ! ® ! a) | ry | b@) €) 1 ) obo ee a) ' ' Thermo- a@/------ po + ' ! couple 0) 9 ' ey L e@)), 7 hy an? oll. 8 Be 1 @ re 24 VAC | Power supply Open Closel C = Potentiometer Close Control wo Winding valve PS en O < p Figure 5

40

Downloaded from www.Manualslib.com manuals search engine

Page 46 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 2-2

2-2 Operation and Tuning

Before you can tune the controller you must first set it up. Proceed in the order of the listed operations.

¢ Operation and Process Value Error

¢ Valve Hysteresis and Dead Band

¢ Configuring the Front Panel

¢ Motor Calibration and Travel Time

¢ Travel Time with Floating Control

2-2-1 Operation at Process Value Error

The operation at process value error, is used to determine what the controllers action will be. For example, if the potentiometer wire breaks and the control loop becomes open, what action do you wish the controller to take? (Options include fully opening the valve, fully closing the valve, or holding its present position).

1. From the main menu select Setting Menu <Offline>.

2. From the Setting Menu <Offline>, select [Operation at PV error |.

3. Select |MVat PV error (posi-prop) | for valve positioning controllers (Figure 6)., f Operation at PV error ‘iO

| || || || ||F9:option] | Fi :Help I ESC: Exit ]

| »

[mu at PV error (posi-prop) > No output

Figure 6

4. Select the desired action from the pop-up menu in Figure 7.

5. Select ESC:Cancel ; 6. Select ESC:Cancel ;, Operation at PY error CI Set by +,, , or SPACE BAR.

| > exccexit |

AY at PY error (posi- - prop)

ESC :Cancel

Closed side output ON (valve fully closed)

No output (valve hold)

Open side output ON Cvalve fully open)

Figure 7

41

Downloaded from www.Manualslib.com manuals search engine

Page 47 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 2-2

2-2-2 Valve Hysteresis and Dead Band

A dead band is a place in the process where no control action is desired

(Figure 8). A A 100% Dead Band vi, Open Close Relay Relay AO1 oy! A02 > Mv 0% 50% 100% Figure 8

Hysteresis results in the activating point being different from the release point. Typically, this value is expressed as a percentage of the output or alarm setting value. It identifies the distance between the activation point and the release point resulting from the PV approaching or moving away from the activation point.

To set the dead band and hysteresis for the valve proceed as follows:

1. From the Setting Menu <Offline>, select (Figure 9).

E | Setting Menu <Off line> \ | F1:File || || || ||Fo:option] | || ESC : Exit ] | Controller type [C ESi16@@X-RRP @4FE Ver. 1.x* ] ] | Configuration Parameters ]

Parameter

Sp conditions | bper at PV error] | Control params |

| Output ] | Front panel | | Power ON oper | Event Comnunicat ions } | } | Posi-prop Posi-prop 2 Is Bank Assignment

[| BankcsP> |

| Digital oper | Analog oper ] ri le name [VALVES .ES4 ||Comment |valve positioning Roadmap Figure 9 2. Select |Posiprop dead band | Figure 10. Insert a dead band between the OPEN and CLOSE action of the valve. The default value is 2%., Position-proportional |

| |Fo:option]| F1a:Hep || esc:Exit |

Set by number key.

[Pos i-prop dead band [x]

IN

> 2.8 [Switching output hysteresis > 6.8 [x]

Figure 10

42

Downloaded from www.Manualslib.com manuals search engine

Page 48 read from a scan by OCR; it may hold reading errors

Operation and Tuning

Section 2-2

3. Select [Switching output hysteresis |’ This setting adjusts the hysteresis to protect your valve/process from too quick of a reaction from the controller, which could result in a fluttering effect from the output relay if the hysteresis is too small. The default is 0.8%.

4. Double-click on LESC:Cancel }.

2-2-3 Configuring the ES100 Front Panel

In this section you will learn how to use ES/TOOLS to configure the front panel of the ES100 to display the process parameters of your choice (PID, PV, SP, MV). However, you may elect not to make any changes to the front panel. In this case proceed to Motor Calibration and Travel Time in this section.

There will be differences in the software setup of the controller between slide wire feedback and floating control. If you are using floating control, some op-erational parameters will not be displayed in ES/TOOLS.

1. From Setting Menu <Offline> select Front Panel. A pop-up menu appears. Double-click on the PF Key (Figure 11).

Front panel

| n__PF Key }

Monitor item key ]

Setting item key ]

Other itens |

Figure 11 2. APF key menu appears (Figure 12)., PF key i?

| || || || ||F9:0pt ion] | Fi6:Help || ESC: Exit |

Set by +,, , or SPACE BAR.

PF1 key type | Select monitor iten PF2 key tupe | Select monitor iten

Figure 12

43

Downloaded from www.Manualslib.com manuals search engine

Page 49 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 2-2

3. Double-click on the button which brings up the PF1 key type pop-up menu. Select Select monitor item | (Figure 13). The screen will disappear after

4. selecting. 5. Now select LPF2 key type }, 6. This will bring you to a pop-up menu which you can select

|Run/reset (stop) inversion | The screen will disappear after selecting.

| || || |

Set by +, -, Pacer Pap

||eosoption][ eracuete || esececce |

PFi key type

ESC :Cancel

Figure 13

Select the button twice to return to the Front Panel menu.

Select | Monitor item key | The monitor item selection key menu will appear (Figure 14).

FA i Monitor item selection key iO

| || _ || || | |Fo:option] | F108 :Help || ESC: Exit |

Set by +, -, or SPACE BAR.

Monitor item 1 PU/SP

Monitor item 2 PU/valve opening position

Monitor item 3 | Invalid Invalid Invalid Invalid [Monitor iten 8 |) tmvatia

Figure 14

44

Downloaded from www.Manualslib.com manuals search engine

Page 50 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 2-2

Note: From here you may modify which items are to be displayed on the front panel of the ES100. For example, you may display your P, I, and D values by modi-fying Monitor items 3, 4 and 5 as shown in Figure 15., | || || || | |Fo:option] | F18:Help || ESC: Exit |

Monitor item selection key |

Set by +,, , or SPACE BAR.

Monitor item 1 PU/SP

Monitor item 2 PV/valve opening position

Monitor item 3 P

Monitor item 4 I

Monitor item 5 D

Monitor item 6 Invalid

Monitor item 7 Invalid

Monitor item & Invalid

9. From the monitor item selection key menu, select [Monitor item 3] pop-up menu appears. 10. Select the item you which to monitor from the list.

2-2-4 Motor Calibration and Travel Time

In order for the ES100 to accurately control your process, precise information will have to be obtained on valve reaction speed and the time required to go from fully OPEN to fully CLOSED. Motor calibration cannot be performed with ES/TOOLS. It only can be executed from the front panel of the ES100.

Performing Motor Calibration - (Parameter C051 in the ES100 Setting Level 2). Refer to your ES100 User Manual.

Note: If you are using floating control, you do not need to perform this operation. Skip to section 2-2-5. You do need to perform the travel time setup steps in the section following Motor Calibration.

This operation is required only when operating a closed control loop or slide wire feed back. Motor Calibration is required by the ES100 because it uses the electrical resistance of the valve to determine the valve’s position. By performing motor calibration you allow the ES100 to scale the resistance values into a range, from fully closed to fully open.

1. You must to have the controller completely connected to your process (a power source and the valve it will be controlling, slidewire feedback, etc.).

2. Slide the ES100 controller out of the plastic housing and locate Switch 1 and Switch 2 on the top of the controller near the face plate. Make sure that SW1, SW2-1 and SW2-2 are turned ON. SW2-3 and SW2-4 should be turned OFF. See Figure 16.

Sw swe

7

OFF

OFF) LT J on

SW 1, - SW 2-4 SW 2-3 SW 2-2 SW 2-1

Figure 16

45