Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of G4 Digital AC Output Modules Data Sheet

Spec sheet · Opto 22

G4 Digital AC Output Modules Data Sheet

Spec sheet5 pagesPDF 695 KB

Data sheet for the Opto 22 G4 digital AC output modules, including the G4OAC5 and G4OAC24, with part numbers and specifications.

Download the PDF695 KB

Covers · 2 models

The models it covers

Summary

What is in it

Opto 22's data sheet for the G4 digital AC output modules, used to switch AC loads such as relays, solenoids, motor starters, heaters and lamps. It lists the part numbers (G4OAC5, G4OAC5A, G4OAC5A5, G4OAC5MA, G4OAC5AMA, G4OAC15, G4OAC15A, G4OAC24, G4OAC24A) with their output voltage ranges and logic voltages, full electrical and temperature specifications, schematics and dimensions, and a closing page about other Opto 22 products.

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Opto 22 data sheet (Form 0252-060522) for the G4 digital AC output modules G4OAC5, G4OAC5A, G4OAC5A5, G4OAC5MA, G4OAC5AMA, G4OAC15, G4OAC15A, G4OAC24 and G4OAC24A. It gives the part numbers, electrical and temperature specifications, schematics and dimensions, so a reader can pick the module for a given AC load and logic voltage.

Type
G4 digital AC output module, equivalent to a normally open SPST contact (Form A) p. 1
Output voltage
12-140 VAC p. 1
Logic voltage
G4OAC5: 5 VDC logic; G4OAC24: 24 VDC logic p. 1
Current rating
3 A at 45 °C ambient, 2 A at 70 °C ambient p. 1, 2, 3
UL motor load
1.5 A p. 1
Isolation
4,000 Vrms optical isolation, field side to control side p. 1
Surge
Withstands a one-cycle surge of 80 A p. 1
Switching
Zero voltage turn-on and zero current turn-off; at most one half cycle (8.3 ms at 60 Hz) p. 1, 2, 3
Features
Built-in LED status indicator; removable fuse p. 1
Temperature
Operating -30 to +70 °C; storage -30 to +85 °C p. 1, 2, 3
Minimum load
20 mA p. 3
Line frequency
25-65 Hz p. 3
G4OAC5 logic input
G4OAC5: logic range 4-8 VDC, pickup 4 VDC, dropout 1 VDC, 12 mA at nominal p. 2
FM version
G4OAC5: the data sheet lists an FM-rated version, G4OAC5FM p. 2

What this sheet walks you through

  • Choosing a G4 AC output module by load voltage and logic voltage p. 1
  • Electrical and temperature specifications of each module p. 2, 3
  • Module schematics and dimensions p. 4

Good to know

  • Turn-on waits for the zero volt crossing and turn-off for the zero current crossing, up to one half cycle each. p. 2
  • The current rating falls from 3 A at 45 °C ambient to 2 A at 70 °C ambient. p. 2
  • Commutating dV/dT is snubbed for a 0.5 power factor load. p. 3

Questions this sheet answers

What is the difference between the G4OAC5 and the G4OAC24?

Both switch 12-140 VAC loads; the G4OAC5 takes 5 VDC logic and the G4OAC24 takes 24 VDC logic. p. 1

How much current can a G4 AC output module switch?

3 A at 45 °C ambient and 2 A at 70 °C, with a UL motor load rating of 1.5 A. p. 1, 2

Is the G4OAC5 normally open or normally closed?

Normally open (Form A). Only the G4OAC5A5 in this family is normally closed. p. 1

What can a G4 AC output module drive?

The data sheet names AC relays, solenoids, motor starters, heaters, lamps and indicators as typical loads. p. 1

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 51-5

The file

Revision and size

RevisionForm 0252-060522
PublisherOpto 22
Pages5
PDF695 KB
TextText from the PDF itself.

The first pages · 4 of 5

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 5
Page 2
Page 2of 5
Page 3
Page 3of 5
Page 4
Page 4of 5