Spec sheet · Opto 22
G4 Digital AC Input Modules
Spec sheet5 pagesPDF 184 KB
Data sheet for the Opto 22 G4 digital AC input modules, including the G4IAC24 (90-140 VAC/VDC input, 24 VDC logic).
Covers · 1 model
The models it covers
Summary
What is in it
Opto 22 data sheet for the G4 digital AC input modules, which detect on/off AC (or DC) voltage levels with optical isolation between field inputs and logic. It lists features, typical applications such as sensing limit, proximity and float switches, part numbers for each input and logic voltage (including the G4IAC24), full specifications for every model, schematics and dimensions.
Its parts
- Features
- Description
- Part Numbers
- Specifications
- Schematics
- Dimensions
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Opto 22 data sheet (form 0251-110715) for the G4 digital AC input modules G4IAC5, G4IAC5A, G4IAC5L, G4IAC5MA, G4IAC15, G4IAC15A, G4IAC24 and G4IAC24A, which detect on/off AC or DC voltage levels and give an optically isolated logic output. It lists the part numbers by input and logic voltage and gives the specifications of each module, with schematics and dimensions.
- Module type
- G4IAC24: G4 AC input module, 90–140 VAC/VDC input, 24 VDC logic p. 1
- Logic supply
- G4IAC24: 24 VDC nominal, 20–30 VDC range, 15 mA at nominal voltage p. 1, 3
- Isolation
- 4000 V input-to-output for 1 ms (transient), 1500 V for 1 minute p. 1, 3
- Switching time
- 20 ms turn-on, 20 ms turn-off p. 3
- Output
- Transistor, 50 mA sinking, 0.4 V drop at 50 mA, 30 V breakdown, 100 microamps leakage at 30 VDC p. 3
- Input current
- 5 mA at maximum line p. 3
- Off-state input
- G4IAC24: up to 1.4 mA, 40 V keeps the module off p. 3
- Temperature
- -30 to +70 °C operating, -30 to +85 °C storage p. 1, 3
- Peak repetitive voltage
- 500 VAC p. 3
- Features
- Built-in LED status indicator; input filtering and a hysteresis amplifier for noise rejection p. 1
- Approvals
- The data sheet states UL recognized, CSA certified, CE approved; passes NEMA Showering Arc Test (ICS 2-230); meets IEEE-472 p. 1
- Family
- G4IAC5, G4IAC5A, G4IAC5L, G4IAC5MA, G4IAC15, G4IAC15A, G4IAC24, G4IAC24A p. 1
- Document
- Opto 22 form 0251-110715, 2011 p. 1
What this sheet walks you through
- Choosing a G4 AC input module by input voltage and logic voltage p. 1
- Comparing the specifications of the 15 and 24 VDC logic modules p. 3
- Typical sensing uses: voltage presence and contact closure from switches and thermostats p. 1
- Schematics and dimensions p. 4
Good to know
- The data sheet states that dimensions and specifications are subject to change. p. 1
Questions this sheet answers
What logic voltage does the G4IAC24 use?
24 VDC nominal, with an output supply range of 20–30 VDC. p. 1, 3
What input voltage does the G4IAC24 accept?
90–140 VAC/VDC. p. 1
How fast does the G4IAC24 switch?
Turn-on and turn-off times are 20 ms each. p. 3
How much current can the G4IAC24 output sink?
50 mA, with a 0.4 V drop at 50 mA. p. 3
Does the G4IAC24 have a status LED?
Yes. The G4 AC input modules have a built-in LED status indicator. p. 1
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.