Spec sheet · Panasonic
Panasonic DVUS606L and DVUS715L Spec Sheet
Spec sheet3 pagesPDF 184 KB
The text of all 3 pages is below; the pictures of the pages are in the PDF.
Filed with · 2 models
Also filed with these models on the old site
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Catalog pages C-36 to C-41 for Panasonic quick-connect speed controllers in the UX series and US series. The part number list includes DVUS606L and DVUS715L among other DVUS and DVUX numbers, but the table does not tie each number to a voltage or output. The pages give specifications, controls, wiring, mounting and setup.
- Device type
- Quick-connect speed controllers, UX series and US series p. 1
- Motor output
- 6 W, 15 W, 25 W, 40 W, 60 W, 90 W p. 1
- Rated voltage
- Single-phase 100 VAC or single-phase 200 VAC, 50 Hz / 60 Hz p. 1
- Speed control range
- 90 to 1400 min–1 at 50 Hz; 90 to 1700 min–1 at 60 Hz p. 1, 2
- Speed variation
- 5% (standard value) p. 1
- UX series modes
- UX series: RUN/STOP, SET, REAL, RATIO, soft-start, soft-down and set lock p. 2
- Soft-start/soft-down
- UX series: 0.1 to 30 sec, set in 0.1 sec steps p. 1, 2
- Speed display
- UX series: stored Panasonic gear head ratios convert readings to gear head or conveyor speed p. 2
- Motor cable extension
- Up to 5 m with an extension cable p. 1
- Power cable
- 2 m; white and black power leads, green frame ground p. 1
- Circuit protection
- Circuit breaker (NFB) 5A, plus a ground-fault circuit interrupter in the supply p. 2
- Thermal protector
- 90 W version has a thermal burn-out protector p. 1
- Motor capacitor
- 40 W or smaller: capacitor is inside the controller box p. 1
- Direction switch
- US series: single-pole double-throw ON-OFF-ON; 5 A at 200 VAC or more for 100 V power p. 3
What this sheet walks you through
- Wiring the controller, motor, capacitor and power supply p. 2
- Setting the motor speed in SET mode p. 2
- Showing gear head or conveyor speed with RATIO mode p. 2
- Calibrating speed with the ADJ trimmer p. 2
- Setting soft-start and soft-down times p. 3
- Choosing what happens at power-on p. 3
- Mounting with or without square holes p. 3
- Starting and stopping a US series controller p. 3
- Changing direction of rotation on the US series p. 3
- Installing the controller away from the motor p. 3
Good to know
- The RUN/STOP switch does not switch the power; turn off the main power switch for long idle periods. p. 3
- Do not leave the switch lever between RUN and STOP. p. 3
- Do not operate the direction switch while the motor is running. p. 3
- Mounting without square holes needs a wall 2 mm thick or less. p. 3
- With a large load inertia, speed changes take longer than the set soft-start/down time. p. 3
Questions this sheet answers
How far can the speed controller be mounted from the motor?
Beyond 1 m, use the extension cord; the allowable distance is 5 m. p. 3
What speed range do these Panasonic speed controllers cover?
90 to 1400 min–1 at 50 Hz and 90 to 1700 min–1 at 60 Hz. p. 1, 2
How do I set motor direction on a US series controller?
Connect COM to CW for clockwise or COM to CCW for counterclockwise; for both directions, wire a switch as shown, and never operate it while the motor runs. p. 3
The file
Size and text
Every page · 3
Read it here
The words of each page, so a phone can search and copy them. The pages themselves are in the PDF.
Page1of 3
Open in the PDFThe text of page 1, from the PDF itself
Unit type
- Outline drawing Power-on state changeover switch
UX series5(0.20)CW YESCCWOperating switch<UX series>10(0.39)US seriesUnit: mm (inch)
- 40 W or smaller (w/ internal capacitor) Exampie: 200 V
Motor connector (110(4.33)) 89(3.5)
52.5(2.07)
100 V 200 V 100 V 200 V 100 V 200 V
Terminal block (w/ cover)
- 60 W or larger Capacitor leadwires (350±30mm)
Exampie: 200 V
6 W : 15 W : 25 W : 40 W : 60 W : 90 W
6 W : 15 W : 25 W : 40 W : 60 W : 90 W
single-phase 100 VAC / single-phase 200 VAC
single-phase 100 VAC / single-phase 200 VAC
50 Hz / 60 Hz
50 Hz / 60 Hz
90 to 1400 min–1 / 90 to 1700 min–1
90 to 1400 min–1 / 90 to 1700 min–1
Speed variation5% (standard value)5% (standard value)Speed settingDigitalAnalog
Rated voltage Power frequency Speed control range
Operating temperature0 to 40˚C–10 to 40˚CStorage temperature–10 to 60˚C–20 to 60˚C
Soft-start/soft-down time
0.1 to 30 sec
Power indicator LED Speed change knob (13(0.51))
LowHighSTOPRUNFront panel 76(2.99)3.5(0.14)Operation switch60(2.36)
Power cable: 2m(78.74) White, Black: Power cable Green: Frame ground
Capacitor Quick connect tab (Faston 187) 2–ø2.5(ø0.098)hole L Label
6.2 (0.244)HW D
Downloaded from DatasheetLib.com - datasheet search engine
Operation switch60(2.36)Nameplate
Terminal block (w/ cover)
ø4.3(ø0.17) hole 1.5(6.06)
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
Wiring diagram
Capacitor (40 W or smaller versions contain this capacitor in the controller box.)
- 90 W version is provided with thermal burn-out protector.
C-363.5(0.14)10(0.39)OutputUS series
Motor connector (110(4.33)) 89(3.5)
52.5(2.07)
- Specification UX series
76(2.99)
Power cable: 2m(78.74) White, Black: Power cable Green: Frame ground
90(3.54)200 VRUN100(3.94)90 W100 V
DVUS606L DVUS606Y DVUS715L DVUS715Y DVUS825L DVUS825Y DVUS940L DVUS940Y DVUS960L DVUS960Y DVUS990L DVUS990Y
ø22 (ø0.87)60 W200 V
DVUX606L DVUX606Y DVUX715L DVUX715Y DVUX825L DVUX825Y DVUX940L DVUX940Y DVUX960L DVUX960Y DVUX990L DVUX990Y
High10(0.39)40 W100 VLowNameplate10(0.39) max25 W200 V(13(0.51))STOPT15 W100 VSpeed change knobUS series80.5(3.17)6WUX seriesPower indicator LEDø22 (ø0.87)80.5(3.17)• Part No. Voltage
Trimmer potentiometer 60(2.36)
White, Black: Power cable Green: Frame ground
- Provided with quick-connect socket
- Can be extended up to 5 m through extension cable (option)
Capacity2.5(0.098)MAX140(5.51)Power cable: 2m(78.74)90(3.54) 100(3.94)<US series>MODEIndexUS series80(3.15)52.5(2.07)RUN STOPOptionsUX series90(3.54)Wiring diagram80.5(3.17)Motor connector100(3.94)NO
- Features
- Provided with quick-connect socket
- Can be extended up to 5 m through extension cable (option)
- The CPU enables the following various functions: 1. Digital setting of revolving speeds 2. Instantaneous conversion of gear head speed and conveyor speed 3. Digital display of actual speed 4. Soft-start, soft-down 5. Backup of setting conditions 6. Set locking
Unit: mm (inch)LCDNormal/reverse switchExampie: 200 VBrake Unit
Quick-connect speed controller Industry's first digital speed controller
- Digital control, digital display
- Quick conversion of gear head speed and conveyor speed
- Soft-start, soft-down
- Set locking function
Speed controller
Speed controller
Unit: upper (mm) / lower (inch)
DesignationCapacitor part No.LWDHT
50.2 26.7 37 36 4 MUSN960GL 100 V M0PC20M20 (1.98) (1.05) (1.46) (1.42) (0.16) 50 30.5 41 41.5 4 MUSN960GY 200 V M0PC5M40 (1.97) (1.20) (1.61) (1.63) (0.16) 50.2 31 41 42 4 MUSN990GL 100 V M0PC25M20 (1.98) (1.22) (1.61) (1.65) (0.16) 50 30.5 41 41.5 4 MUSN990GY 200 V M0PC6.2M37 (1.97) (1.20) (1.61) (1.65) (0.16)
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-37
Page2of 3
Open in the PDFThe text of page 2, from the PDF itself
Unit type
- Names and functions
- Modes of operation (UX series)
UX series
- Stop Select from RUN/STOP
- Run Select from RUN/STOP
- Indication magnification (Select from MODE key)
Factory setting 1.000 Factory setting 90
- Set lock indication (To enter the set lock mode, simultaneously press MODE , and keys.)
SET REAL MOTOR SPEED
r/min
- RUN/STOP key SIG. OUT
- MODE key
- Unit of revolving speed (Displayed when RATIO is set to 1 or more.)
MODE
key Increases the set value.
- Indicates that the reading is motor revolving speed. (Active only when RATIO is set to 1 or more.)
- ADJ control Use this trimmer potentiometer if discrepancy is found between the preset and the actual rotation speeds.
key Decreases the set value.
- Power-on state changeover switch
- Motor connector
Factory setting NO
<CAUTION> 1. When using a gear head, check the direction of rotation of its output shaft. The direction is not common to all models. 2. The fan of a fan-cooled motor starts to run as the controller is turned on.
- Normal/reverse switch Factory setting CW
White, Black: Power cable Green: Frame ground
- Capacitor for motor
US series
- Speed setting knob Low STOP
Multiplication can be set by the factor of 0.005 to 0.995: select the desired one from and keys. 1.000 0.995 ... 0.015 0.010 0.005 (in unit of 0.005)
<Example>
- Power frequency 50Hz : 90 100 110 ... 1400 min–1
- Power frequency 60Hz : 90 100 110 ... 1400 ...1700 min–1 [With reading magnification other than 1.000] Readings are based on the reading magnification setting in RATIO mode and gear reduction ratio setting. Desired value can be selected among the values shown below, by using and keys.
<Example> Reduction gear ratio = 3 Selection unit is 10/3 min–1. The reading rounds off fraction.
- Power frequency 50 Hz: 29.9 33.3 36.6 ... 466.6 min–1
- Power frequency 60 Hz: 29.9 33.3 36.6 ... 466.6 ... 566.6 min–1 <Example> Magnification = 0.500 Selection unit is 10 x 0.500. The reading rounds off fraction.
- Power frequency 50 Hz: 45.0 50.0 55.0 ... 700.0
- Power frequency 60 Hz: 45.0 50.0 55.0 ... 700.0 ... 850.0 [Note] Exception: reading magnification 1.000 “MOTOR SPEED r/min” is displayed. Only “r/min” is displayed when the value exceeds 1.000. Otherwise, nothing is displayed.
REAL mode
High RUN
- Front panel (removable)
Wiring diagram Power supply Extension cord Power switch
<Recommended circuit breakers> Sanken Airpax Co., Ltd. Controller Type single-phase: IELH-1-11-63-5A-M Rated current 5 A, current breaking characteristic DELAY63 Recommended current breaking characteristic: DELAY61-6 Ground the return circuit to the earth terminal. East Japan: 0492-83-7575
- Contact to (100 Ω or smaller, ø1.6 mm or more). West Japan: 06-6312-8716
Multiple number setting value (to display the settings in terms of the speed of belt conveyor) <“SET” or “REAL” reading = motor revolving speed multiplied by multiplication factor)
SET mode In this mode, the revolving speed can be set to a value within the range shown below, by using and keys. [With reading magnification 1.000] Value can be set in unit of 10 min–1.
- Power indicator
- RUN/STOP switch
- ADJ With the speed setting knob turned fully clockwise, adjust the trimpot (normally covered with the front panel) for the revolutions shown below: 50 Hz: 1400 min–1 60 Hz: 1700 min–1
Circuit breaker (NFB) : 5A <Caution> Install a ground-fault circuit interrupter in the power supply.
Reduction gear ratio setting value (to display the settings in terms of gear head output shaft speed) <“SET” or “REAL” reading = motor revolving speed divided by gear reduction settings>
The reduction ratios of Panasonic gear head are stored in the unit, choose the suitable one by using and keys: 1.000 3 ... 100 ... 202 ... 1000 ... 2020
Index
- Settings/revolving speed
- Power-on state setting (In the SET mode, set the revolving speed to the max. and then press and hold key for 5 seconds or more. “YES” or “NO” is displayed.)
RUN STOP SS SD SET.L RATIO
- Revolution speed (Select from MODE key)
Factory setting 0 sec
Options
- Revolution speed (Select from MODE key)
- Indicates that the soft-down time is being set or soft-down process is activated. (Press the MODE key while in SS mode.)
RATIO mode By setting the speed in unit of motor revolving speed multiplied by the factor or by displaying the actual speed, gear head output shaft speed or belt conveyor travel speed can be converted. The RATIO mode is used to set the factor. Selection of indication magnification can be made from and keys.
Brake Unit
Exampie: 200 V
- Indicates that the soft-start time is being set or Factory soft-start process is activated.(To enter SS mode, setting press and hold MODE key for at least 1 second.) 0 sec
Speed controller
Speed controller
Capacitor cap
- National specifications: Option
- Specifications compliant with overseas standards: Attachment
- In the case of models with a model number to which “A” is suffixed, the capacitor cap is optional. The models with a model number to which “A” is suffixed (not equipped with a capacitor cap) are not sold or available in Japan.
Motor Ground the return circuit to the earth terminal. (100 Ω or less, ø1.6 mm or more). Tightening torque: 1.0 to 1.5 N·m
Capacitor (supplied with the motor) For connection to the capacitor, see the motor instruction manual.
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-38
Downloaded from DatasheetLib.com - datasheet search engine
In the REAL mode, motor's real revolutions multiplied by the reading magnification is displayed. [Reading magnification 1.000] The speed is displayed in unit of 5 min–1. <Example> 0 5 ... 90 100 110 ... 1400 ... 1700 min–1 [With reading magnification other than 1.000] Readings are based on the reading magnification setting in RATIO mode and gear reduction ratio setting.
<Example> Reduction gear ratio = 3 Selection unit is 5/3 min–1. The reading rounds off fraction. 0 1.6 ... 29.9 33.3 36.6 ... 466.6 ... 566.6 min–1 <Example> Magnification = 0.500 Selection unit is 10 x 0.500. The reading rounds off fraction. 0 2.5 ... 45.0 50.0 55.0 ... 700.0 ... 850.0 [Note] Exception: reading magnification 1.000 “MOTOR SPEED r/min” is displayed. Only “r/min” is displayed when the value exceeds 1.000. Otherwise, nothing is displayed.
RATIO mode The soft-start time is set in this mode from and 0 0.1 0.2 0.3 0.4 ... 29.9 30.0 sec
keys in unit of 0.1 sec, up to 30 sec.
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-39
Page3of 3
Open in the PDFThe text of page 3, from the PDF itself
Unit type
SD setting mode
- Mounting method (UX series, US series) and
keys
r/min
<Mounting through square holes>
UX series, US series
Unit: mm (inch)
Object 2- M4 or 2- ø4.5(ø0.18)
750 min–1 =5 1500 min–1 This means that 5 seconds are required to change from 0 min–1 to 750 min–1. The same applies to “SD”. Note 2) In the practical application, speed change time will be longer than the set soft-start/down time if the load inertia is large.
2- M4 screwSDController53 +10 (2.09 +0.039)Power-on state settingOptions5S SS
) 0 81+10 (3.19 +0.039 90 ±0.2 (3.54 ±0.008)
10 x
1500 750 0
The soft-start/down time is defined as the time required to change revolving speed between 0 min–1 and 1500 min–1. <Example> When the soft-start time is set to 10 seconds and “SET” revolving speed is 750 min–1, then,
Brake Unit
The soft-down time is set in this mode from in unit of 0.1 sec, up to 30 sec. Note 1) Soft-start/down
Speed controllerSpeed controllerIndex
The state of the unit upon power-up can be preset from the power-on state setting switch.
Previous stateUpon power-on“RUN” “STOP”Stop Stop
<Mounting without using square hole>
US series only
- Single-pole double-throw: ON-OFF-ON
- 100 V power: 5 A at 200 VAC or more
- 200 V power: 3 A at 400 VAC or more
Remove the jumper lead.
Direction when viewed from motor output shaft end Switch
2- M4 screwNutø17(ø0.67)12±0.2Front panel
4 – ø3.5(ø0.14) (Cross section A) 50 ±0.2 (1.97 ±0.008)
(Cross section A)
Controller 2.0 mm max.
Caution Switch specification
COM CW CCW AC AC FG
Body mounting screw (M3 flat-head)
ø7(ø0.28) ø23(ø0.91)
ø3.5 (ø0.14)
- Changing direction of rotation (US series)
90 ±0.2(3.54 ±0.008)
1. Connect the “motor connector”. 2. Make sure that the RUN/STOP switch is in “STOP” position. Connect the power cable to the AC source. 3. Turn on power. “Power” indicator will light. 4. Place the RUN/STOP switch in “RUN” position, and the motor starts. CAUTION: Do not place the switch lever in between RUN and STOP. 5. To stop the motor, move the lever to “STOP” position. Note that the RUN/STOP switch does not turn on/off power supply: when not using the motor for a long period, turn off the main power switch. 6. The electric fan, if used with the motor, rotates as the power to the speed controller is turned on and stops as the controller power source is turned off.
15 ±0.2(0.59 ±0.008)
- Operating method (US series)
Unit: mm (inch)
13.2 ±0.2 (0.52 ±0.008) 2 – ø7.5(ø0.30)
90˚
Upon power-on Startup (after approx. 1 sec) Stop
ø6.5 (ø0.26)
“RUN” “STOP”
Mounting procedure 1. Drill 2 square holes in the object. 2. Secure the controller and front panel with 2 M4 screws.
26 ±0.2(1.02 ±0.008)
Previous state
(2) “NO” Upon power-on, the unit is in stop mode regardless of the state at the previous power off. To restart, operate RUN-STOP key.
(0.47 ±0.008)
(1) “YES” Upon power-on, the unit reproduces the state as it was turned off.
ClockwiseConnect COM to CWCounterclockwiseConnect COM to CCW
- Unidirectional rotatio
- Normal/reverse rotation
Terminal “CW” or “CCW” on the controller rear panel should be left open. [Note] When a gear head is connected, the direction of its output shaft may or may not be the same as that of motor shaft depending on the reduction ratio.
When it is necessary to select the rotating direction, connect the switch as shown in the figure. [Note] Do not operate this switch while the motor is running.
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-40
Downloaded from DatasheetLib.com - datasheet search engine
Wall thickness of the equipment where the controller is to be mounted should be 2 mm or less. Mounting procedure 1. Drill 2 square holes in the wall of the object. 2. Remove the front panel from the controller. 3. Secure the controller body with M3 flat-head screws and nuts. 4. Place the front panel on the wall and secure the panel with M4 screws and nuts.
<To install controller and motor separately> When installing the speed controller at a distance more than 1 m from the motor, use optional “extension cord” that is supplied as standard accessory (allowable distance 5 m). Refer to page D-4 (Option).
- Please read your User's manual carefully so that you will understand the operation and safety precautions before attempting to operate the system.
C-41
