For the Phoenix Contact 1605-M12

Page 1

Extract from the online catalog

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

Ethernet switch, 5 Ethernet ports on the front in M12 format, automatic detection of 10 or 100 Mbps data transmission rate, coupling of network segments with different transmission speeds, auto crossing function, IP67 protection Product notes WEEE/RoHS-compliant since: 01/20/2010

Commercial data GTIN (EAN) 4

046356

499781 sales group

K000

Pack

1 pcs.

Catalog page information

Page 104 (AX-2011)

http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads.

Product description Ethernet interface The FL SWITCH 1605 M12 has five front Ethernet ports in M12 format. Only CAT5 / CAT6 Ethernet cables with D-coded M12 connectors can be connected to these. The data transmission speed is 10Mbps or 100Mbps. In addition, each port has an auto crossing function at 100Mbps: It is not necessary to make a distinction between 1:1 or crossover Ethernet cables.

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Page 1 / 7 Jun 9, 2011

Page 2

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

Switching properties of FL SWITCH 1605 M12 –Store-and-forward: All data telegrams that are received by the switch are saved and their validity is checked. Invalid or faulty data packets (>1522 bytes or CRC errors) and fragments (<64 bytes) are rejected. Valid data telegrams are forwarded by the switch. The switch always forwards the data using the data transmission speed that is used in the destination network segment. –Multi-address function: The switch independently learns the addresses for termination devices, which are connected via a port, by evaluating the source addresses in the data telegrams. Only packets with unknown addresses, with a source address of this port or with a multicast/broadcast address in the destination address field are forwarded via the corresponding port. The switch can store up to 4096 addresses in its address table with an aging time of 40 seconds. This is important when more than one termination device is connected to one or more ports. In this way, several independent subnetworks can be connected to one switch. Technical data Interfaces Interface 1

Ethernet

No. of ports

5

Connection method

M12 D-coded

Transmission physics

Twisted pair connection

Transmission speed

10/100 MBit/s

Transmission length

100 m (per segment)

Signal LEDs

Data receive, link status

Function Basic functions

Unmanaged switch / autonegotiation, complies with IEEE 802.3, store and forward switching mode

Status and diagnostic indicators

LEDs: US (voltage supply), link and activity per port

Network expansion parameters Cascading depth

Network, linear, and star structure: any

Maximum conductor length ((twisted pair)

100 m

Supply voltage Supply voltage

24 V DC (M12 connector)

Residual ripple

3.6 VPP (within the permitted voltage range)

Supply voltage range

18 V DC ... 32 V DC

Typical current consumption

40 mA (24 V DC)

Max. current consumption

40 mA (+ 10 mA per port)

Current consumption

40 mA ... 80 mA (at 24 V DC)

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Page 2 / 7 Jun 9, 2011

Page 3

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

General data Width

30 mm

Height

200 mm

Depth

41 mm

Mounting type

Wall mounting

Type AX

Stand-alone

Weight

220 g

Degree of protection

IP65/IP66/IP67

Ambient temperature (operation)

-40 °C ... 70 °C

Ambient temperature (storage/transport)

-40 °C ... 70 °C

Permissible humidity (operation)

10 % ... 95 %

Permissible humidity (storage/transport)

10 % ... 95 % (no condensation)

Air pressure (operation)

86 kPa ... 108 kPa (1500 m above sea level)

Air pressure (storage/transport)

66 kPa ... 108 kPa (3500 m above sea level)

Housing material

PBT

Material base plate

High-grade steel (1.4301/1.4016)

Note

NOTE: Meet noise immunity requirementsConnect FE using a mounting screw when mounting on a conductive surface. When mounting on a non-conductive surface, FE is connected using the mounting screw via a cable lug.

Mechanical tests Type of test

Shock test in acc. with IEC 60068-2-27

Test result

Operation: 30 g, 6 ms continuous testing, 5 g 30 ms continuous testing

Type of test

Shock in acc. with IEC 60068-2-27:1997 Vibration resistance in acc. with IEC 60068-2-6

Test result

Operation/Storage/Transport: 5 g, 150 Hz, Criterion 3

Type of test

Free fall in acc. with IEC 60068-2-32

Test result

0.5 m

Type of test

Vibration resistance according to IEC 61373, EN 61373

Test result

Category 1, Class B

Conformity with EMC directives Developed in acc. with standard

Noise emission test according to EN 61000-6-3

Test standard

EN 61000-6-3 (noise emission)

Test result

Class B

Test standard

EN 55011 (emitted interference)

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Page 3 / 7 Jun 9, 2011

Page 4

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

Test result

Class B

Test standard

EN 55022 (emitted interference)

Test result

Class B

Test standard

EN 61000-4-2 (ESD)

Test result

Criterion B

Test standard

EN 61000-4-3 (electromagnetic fields)

Test result

Criterion A, 20 V/m

Test standard

EN 61000-4-5 (surge)

Test result

Criterion A; interfaces 1 kV

Test standard

EN 61000-4-4

Test result

Criterion A, 2.2 kV Criterion A; Field intensity: 10 V/m

Accessories Item

Designation

Description

1536515

SAC-5P-FR SCO/.../...

Sensor/Actuator cable, 5-position, Free conductor end, on Socket, angled M12-SPEEDCON, A-coded, Cable length: Free input (0.2 ... 40.0 m)

1536489

SAC-5P-FS SCO/.../...

Sensor/Actuator cable, 5-position, Free conductor end, on Socket, straight M12-SPEEDCON, A-coded, Cable length: Free input (0.2 ... 40.0 m)

1542415

SAC-5P-MS-FR SCO/.../...

Sensor/Actuator cable, 5-position, Plug, straight M12SPEEDCON, A-coded, on Socket, angled M12-SPEEDCON, Acoded, Cable length: Free input (0.2 ... 40.0 m)

1523625

SAC-5P-MS-FS SCO/.../...

Sensor/Actuator cable, 5-position, Plug, straight M12SPEEDCON, A-coded, on Socket, straight M12-SPEEDCON, Acoded, Cable length: Free input (0.2 ... 40.0 m)

1553624

SACC-M12MRD-4Q SH

Bus system connector, connector, angled, 4-pos., M12 shielded, D-coded, QUICKON connection block, cable diameter max. 8 mm

1543223

SACC-M12MSD-4Q SH

Bus system connector, plug, straight, 4-pos., M12 shielded, Dcoded, QUICKON connection block, cable diameter max. 8 mm

1416402

VS-93E/...

CAT5e, Ethernet cable, shielded, 2-pair, AWG 26 stranded (7wire), RAL 5021 (water blue), length variable

1657494

VS-BH-M12FSD-RJ45/180

Control cabinet feed-through, M12, 4-pos., D-coded on RJ45 socket, socket input 180°, IP65/67

1406056

VS-M12MS-IP20-93E-LI/2,0

Assembled Ethernet cable, CAT5e, shielded, 2-pair, AWG 26 stranded (7-wire), RAL 5021 (water blue), M12 plug on RJ45 plug/ IP20, line, length 2 m

General

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Page 4 / 7 Jun 9, 2011

Page 5

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

1406632

VS-M12MS-M12MS-93E-LI/2,0

Assembled Ethernet cable, CAT5e, shielded, 2-pair, AWG 26 stranded (7-wire), RAL 5021 (water blue), M12 plug on M12 plug, line, length 2 m

1405798

VS-M12MS-OE-93E-LI/2,0

Assembled Ethernet cable, CAT5e, shielded, 2-pair, AWG 26 stranded (7-wire), RAL 5021 (water blue), M12 plug on free conductor end, line, length 2 m

ZBF 8:UNBEDRUCKT

Zack strip, flat, unprinted: 10-section, for individual labeling with M-PEN or ZBF-T, sufficient for 100 terminal blocks, color: white

SAC-5PY-F/M-F VP SH

Y distributor, 5-position, shielded, Socket, straight M12SPEEDCON, A-coded, on Socket, straight M12-SPEEDCON, Acoded and Plug, straight M12-SPEEDCON, A-coded

Marking 0808781

Plug/Adapter 1419933

Protection and sealing elements 1680539

PROT-M12

An M12 screw plug for the unoccupied M12 sockets of the sensor/ actuator cable, boxes and flush-type connectors

Diagrams/Drawings Dimensioned drawing

Side view (dimensions in mm) Top view (dimensions in mm) Product drawing

X1 - X5: Ethernet connection X6: Supply voltage ACT: ACT LEDs LNK: Link LED US: US1 LED

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Page 5 / 7 Jun 9, 2011

Page 6

FL SWITCH 1605 M12 Order No.: 2700200 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2700200

Schematic diagram

Connecting the supply voltage PIN 1 Us PIN 2 n.c. Pin 3 GND Pin 4 n.c. Pin 5 Functional earth ground

PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de

Assignment of the LAN socket Pin 1 Transmit + Pin 2 Receive + Pin 3 Transmit Pin 4 Receive -

Page 6 / 7 Jun 9, 2011