Spec sheet · Power Source
Power Source FHG24SXU Spec Sheet
Spec sheet2 pagesPDF 741 KB
Both pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A two-page specification sheet from ETA-USA for the FHG-SX-U series of 600W switching power supplies with power factor correction. It covers the models FHG 3.3SX-U through FHG 48SX-U, including the FHG 24SX-U. It lets a reader check input, output, protection, environmental and size data.
- Device
- 600W switching power supply with power factor correction p. 1
- AC input
- 115VAC~230VAC nominal, 85~264VAC range, 50/60Hz, single phase p. 2
- Input current
- 7.5 / 4A at full load (115V / 230VAC input) p. 2
- Inrush current
- 17A max. at 115VAC, 33A max. at 230VAC p. 2
- Power factor
- 0.99 at 115VAC, 0.97 at 230VAC p. 1
- Output adjustment
- ± 10%, typical p. 2
- Ripple and noise
- (Output V x 1%) + 100mVp-p max. p. 2
- Hold-up time
- 20mS min. at 25°C, rated input and output p. 2
- Protection
- Over-current by constant current limiting; over-voltage by output shutdown p. 2
- Remote functions
- Remote control and remote sensing possible p. 2
- Dimensions
- 130X200X93 (mm) p. 1
- Weight
- 2.6Kg p. 2
- Temperature
- Operating -5 ~ +50° C (see derating curve); storage -20~+85°C p. 2
- Switching frequency
- 130KHz fixed p. 2
What this sheet walks you through
- Choosing a model by output voltage p. 1
- Input, output and general specifications p. 2
- Block diagram and terminal connection drawings p. 2
Good to know
- Operating temperature is subject to the output derating curve. p. 2
- All specifications and data are subject to change without notice. p. 1
Questions this sheet answers
What input voltage does the FHG 24SX-U accept?
The FHG-SX-U series takes 85~264VAC at 50/60Hz, single phase, with 115VAC~230VAC nominal. p. 2
How much power does the FHG-SX-U series supply?
The sheet describes them as 600W switching power supplies with power factor correction. p. 1
How big and heavy is the FHG-SX-U power supply?
The sheet gives 130X200X93 (mm) and a weight of 2.6Kg. p. 1, 2
Can the FHG-SX-U output voltage be adjusted?
Yes, the output is adjustable by ± 10%, typical. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
ETA-USA
600W
High Quality Switching Power Supplies
85-264VAC
Power - Factor Correction
FHG-SX-U1SERIESOutput TableFHG-SX-U (85~264V)MODEL(CSA)Load & Output V.O utput Derating130X200X93 (mm )OUTPUT VOLTAGE CURRENT
FHG 3.3SX-U FHG 05SX-U FHG 06SX-U FHG 12SX-U FHG 15SX-U FHG 24SX-U FHG 30SX-U FHG 36SX-U FHG 48SX-U
3.3V 5V 6V 12V 15V 24V 30V 36V 48V
120A 120A 100A 53A 42A 27A 21.6A 18A 13.5A
EFFICIENCY 70% 75% 81% 81% 81% 83% 84% 83% 84%
FHG-Series is a new generation of powersupplies. Its the latest design following the international standard and market demands. This type of powersupply has all in one : Power factor correction, low line distortion according to EN 60555-2, electro magnetic interference (EMI) complies with EN 55022/B, FCC level B. Safety complies with EN 60950-1 , UL 1950, CSA 234. High efficiency and power fac tor correction is an optimal combination of good costparformance for both, end-users and power production companies.
Special Features 1. Power factor 115VAC=0.99 230VAC=0.97 2. Harmonics : EN 60555-2 IEC1000-3-2 3. EMI: complies to EN 55022/13, FCC/B 4. Safety: UL1950, C-UL(CSA950), EN60950-1, VDE0805, IEC950 approved CE marked to the low voltage directive
Applications All specifications and data subject to change without notice
Process control, Office-Equipment, Computer Peripherals, Telecommunication, Industrial Electronics and Machines, Household Equipment.
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
FHG-SX-U SPECIFICATION I N PUT
G EN ERAL S PECIFICATIO N Power factor correction Over-current protection Over-voltage protection Remote control Remote sensing Switching frequency Withstand voltage Insulation resistance Leakage current Weight
:Active filter circuit with boost converter :Constant current limiting :Output shutdown :Possible :Possible :130KHz Fixed :(Input-Output) :AC3000V(1Minute) :(Input-Chassis) :AC2500V (1Minute) :(Output-Chassis) :AC 500V (1Minute) :(Input-Output-Chassis):50M MIN. :AC 115VAC, 50Hz, 25°C 0.28mA AC 230VAC, 50Hz, 25°C 0.58mA :2.6Kg
E N VIRO N M EN T Operating temperature Storage temperature Humidity Vibration
Shock
:-5 ~+50° C (See output derating curve) :-20~+85°C :85% :(5~10Hz) Amplitude (peak to peak) 10mm(constant) :(10~55Hz) Acceleraton 2G (constant) X, Y, Z :30G
Dimension (mm)
Voltage nominal Voltage range Power factor & harmonic correction range Frequency Current on full road Inrush current Phase
:115VAC~230VAC :85~264VAC :85~255VAC :50/60Hz :7.5 / 4A(Input 115V/AC230VAC) :17A MAX.(Input 115VAC), 33A MAX. (Input 230VAC) :Single
O UTPUT Adjustable voltage Ripple & noise Input regulation Load regulation Temperature coefficient Drift / Time effect Rise up time Hold-up time
:± 10%, typical :(Output V x 1%) + 100mVp-p MAX. :0.5%MAX :1.0%MAX :0.03% / °C :(Output V X 0.5%)+15mV/8H (After 1 H) :500mS typ. @ 115 VAC in / 200mS typ. @230 VAC in :20mS MIN (at 25°C, Rated-InputOutput)
B lock DiagramTerminal ConnectionETA-USA
16315 Vineyard Blvd. Morgan Hill, CA 95037 Phone: 1-800-ETA-POWER, (408) 778-2793 Fax: (408) 779-2753
Visit Us On The Web at: Or Email at:
http://www.eta-usa.com/ sales@eta-usa.com