The text of a manual · part 2 of 15
Programmable controller Twido Catalog, pages 4 to 6
Pages 4 to 6 of 76: Twido programmable controller; Twido programmable controller
The original document is the PDF (3.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Schneider ABE 7E16EPN20, Schneider ABE 7E16SPN20, Schneider TWDALM3LT, Telemecanique ABE 7E16SPN22 and Telemecanique ABE 7E16SRM20
Page 4
Selection guide
0
Twido programmable controller
0
Compact and modular base controllers
Applications
Compact base controllers
Discrete I/O Basic Number of inputs Number of outputs Type of connection
10 6 sink/source c 24 V inputs (1) 4 relay outputs
I/O expansion
16 9 sink/source c 24 V inputs (1) 7 relay outputs
24 14 sink/source c 24 V inputs (1) 10 relay outputs
40 24 sink/source c 24 V inputs (1) 14 relay outputs 2 source transistor outputs
4 discrete, analog and AS-Interface I/O modules (2)
7 discrete, analog and AS-Interface I/O modules (2)
Non-removable screw terminal block
Number of expansion modules Discrete I/O modules Analog I/O modules AS-Interface (3)
8, 16 or 32 c 24 V inputs; 8, 16 or 32 c 24 V or relay outputs; 2 x 12 bit inputs; 1 x 12 bit output or 2 inputs/1 x 12 bit output, Management of slave modules: Discrete (max. 62 modules),
Maximum number of I/O per configuration (base controller with I/O expansion modules)
10
16
88 with screw terminal I/O expansion modules (4) 152 with HE 10 connector I/O expansion modules
Integrated 5 kHz counting counting and 20 kHz positioning counting
3 x 16 bit counting channels (5)
4 x 16 bit counting channels (5)
1 x 16 bit counting channel (32 bits for versions u 2.5): - dedicated c 24 V discrete inputs for incremental encoder or proximity sensors - up/down counting, up counter, down counter and frequency meter
2 x 16 bit channels (32 bits for versions u 2.5):
7 kHz positioning Functions
PID Event processing
Communication
Integrated CANopen bus Ethernet
152 with screw terminal I/O expansion modules 264 with HE 10 connector I/O expansion modules
2 channels: PWM function
For controller versions ≥ 2.0 For controller versions ≥ 2.0
1 RS 485 serial port (mini-DIN connector)
1 RS 485 serial port (mini-DIN connector), 1 optional serial port: RS 232C (mini-DIN connector) or RS 485 (mini-DIN connector or screw terminals) + RJ45 Ethernet port for TWD LCAE 40DRF With CANopen bus master module TWD NCO1M With TwidoPort Ethernet network interface module 499 TWD 01100 for all controller versions ≥ 3.0
Supply voltage a 100...240 V for TWD LCAA ppp and TWD LCAp 40DRF (c 24 V discrete sensors powered by the base controller), c 19.2…30 V for TWD LCDA ppp
Programming
Application memory
700 instructions
2000 instructions
3000 instructions
Internal bits Internal words (6) Standard function blocks (6) Double words Floating, Trigonometrically Real-time clock Languages Software
128 bits 3000 64 timers, 128 counters
128 bits
256 bits
Twido base controller models
128 timers, 128 counters Yes Yes
Optional TWD XCP RTC real time clock cartridge, using 16 real-time clock blocks Built-in Reversible languages: Ladder language and Instruction List language (with Grafcet instructions) TwidoSoft running under Windows 98 SE, Windows 2000 and Windows XP and TwidoAdjust running under Pocket PC2003
TWD LCpA 10DRF
TWD LCpA 16DRF
TWD LCpA 24DRF
Page 10 (1) Sink input: positive logic. Source input: negative logic. (2) Within the consumption limit controlled by TwidoSoft software. (3) The AS-Interface M3 profile supports analog profile 7.3 (7 slaves), but does not support analog profile S-7.4.
4
3000 instructions, 6000 with memory extension cartridge TWD XCP MFK64
TWD LCAp 40DRF
Page 5
0
0
Modular base controllers
20 12 sink/source c 24 V inputs (1)
40 24 sink/source c 24 V inputs (1)
8 sink or source transistor outputs (depending on model) By HE10 type connector For TWD LMDA 20DTK, allows use of the Telefast pre-wired system
6 relay outputs and 2 transistor source outputs
4 discrete, analog and AS-Interface I/O modules (2)
7 discrete, analog and AS-Interface I/O modules (2)
By removable screw terminal block
16 sink or source transistor outputs (depending on model) By HE10 type connector For TWD LMDA 40DTK, allows use of the Telefast pre-wired system
4 c 24 V inputs/4 relay outputs or 16 c 24 V inputs/8 relay outputs, connection by screw or spring terminals and by HE 10 type connector connection by screw terminals, 8 x 10 bit inputs, 4 x 12 bit inputs, 2 x 10 bit outputs analog (max. 7 modules). For all controller versions ≥ 2.0 84 with screw terminal I/O expansion modules 148 with HE 10 connector I/O expansion modules
132 with screw terminal I/O expansion modules 244 with HE 10 connector I/O expansion modules
152 with screw terminal I/O expansion modules 264 with HE 10 connector I/O expansion modules
2 x 16 bit counting channels (5) - dedicated c 24 V discrete inputs for incremental encoders or proximity sensors - up/down counting, up counter, down counter, frequency meter (pulse width modulation output) and PLS function (pulse generator output)
For all controller versions ≥ 2.0 For all controller versions ≥ 2.0 for controller versions ≥ 3.0 c 24 V supply
3000 instructions
3000 instructions, 6000 with memory extension cartridge TWD XCP MFK64
Yes Optional TWD XCP RTC real time clock cartridge, using 16 real-time clock blocks
TWD LMDA 20DpK (7)
TWD LMDA 20DRT
TWD LMDA 40DpK (7)
16 (4) With maximum of 42 relay outputs (on base controller and I/O expansions). (5) Dedicated c 24 V discrete inputs of the base controller and up/down counting with preset. (6) The maximum values of the internal words and function blocks cannot be cumulated. (7) Replace the p in the reference with T: source transistor outputs, U: sink transistor outputs.
5
Page 6
Presentation
0
Twido programmable controller Compact base controllers
564493-3-3
Presentation The Twido range of compact programmable controllers offers an “all-in-one” solution in a compact overall size 3.1/6.18 x 3.54 x 2.75" (80/157 x 90 x 70 mm). Eight compact base controllers are available, differing in their processing capacity and in their number of c 24 V inputs and number of relay and transistor outputs (10, 16, 24 and 40 I/O). These base controllers use: v an a.c. supply between a 100 and 240 V (providing the c 24 V supply to the sensors) v or a d.c. supply, between c 19.2 and 30 V (an external auxiliary supply must be provided for supply to the sensors)
TWD LCpA 10DRF
564493-3-3
This type of compact base controller offers the following advantages: b A significant number of I/O (up to 40 I/O) in a small overall size, so reducing the size of consoles or panels for applications where space is an important factor. b A variety of expansion options and product options offer the user a degree of flexibility which is generally only available with larger automation platforms. 24 I/O compact base controllers TWD LCpA 24DRF can take up to 4 discrete and/or analog I/O expansion modules, corresponding to a 64 I/O configuration; 40 I/O compact base controllers TWD LCAp 40DRF can take up to 7 modules. All compact base controllers can take optional modules such as a digital display, memory cartridge and real-time clock cartridge, as well as an additional RS 485 or RS 232C communication port (extra port not compatible with base controllers TWD LCpA 10DRF). The compact controller solution also allows great wiring flexibility. For discrete I/O expansion modules (with base controllers TWD LCpA 24DRF and TWD LCAp 40DRF) several possible types of connection are offered, such as removable screw terminal blocks and spring type connections which allow simple, fast and safe wiring. The Telefast pre-wired system allows the connection of modules with HE 10 connectors: v to pre-formed cables with free wires at one end for direct connection to sensors/ pre-actuators v to the Telefast pre-wired system for Twido (connection cable and Telefast sub-base assembly). b The display and plug-in memory options allow easy adjustment, transfer and backup of applications: v the digital display can be used as a local display and adjustment tool v the EEPROM technology in the memory cartridges allows backup and transfer of programs to any Twido compact or modular controller b TwidoSoft software allows easy programming using instruction list language instructions or ladder language graphic objects. It uses the same objects and sets of instructions as those used by PL7-07 software for Nano programmable controllers. TwidoSoft software allows existing Nano PLC applications to be reused with Twido controllers by importing an ASCII file. b Compact controllers have 2 analog adjustment points (only one for 10 and 16 I/O base controllers) accessible on the front panel.
564494-3-3
TWD LCpA 16DRF
121114-49-M
TWD LCpA 24DRF
TWD LCAp 40DRF Outputs relay 4
Analog adjustment 1 point 0…1023
Serial ports
I/O expansion
TWD LCpA 10DRF c 24 V inputs 6
1 x RS 485
TWD LCpA 16DRF
9
7
1 point 0…1023
TWD LCpA 24DRF
14
10
1 x RS 485, option 1 x RS 232C/485 1 x RS 485, option 1 x RS 232C/485
TWD LCAp 40DRF
24
Compact base controller
6
Optional cartridge
No
Display module Yes
No
Yes
1 slot: real-time clock or memory
1 slot: real-time clock or memory
1 point Yes, 4 max Yes 1 slot: real-time 0…1023 (1) clock or memory 1 point 0…511 14 + 2 source 1 point 1 x RS 485, Yes, 7 max Yes 1 memory slot transistor 0…1023 option (2) (3) outputs 1 point 1 x RS 232C/485 0…511 (1) i.e.: a maximum of 88 I/O with screw terminal expansion modules, with a maximum of 32 relay outputs in I/O expansion modules. Maximum of 152 I/O with HE 10 connector expansion modules. (2) i.e. a maximum of 152 I/O with screw terminal expansion modules. Maximum of 264 I/O with HE 10 connector expansion modules. (3) Built-in real-time clock.
0