Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Control Technologies 2512-A, Siemens 2512-A and Texas Instruments 2512-A Manual

Manual · Control Technologies

Control Technologies 2512-A, Siemens 2512-A and Texas Instruments 2512-A Manual

Manual2 pagesPDF 65 KB

Both pages are below, each with its text.

Download the PDF65 KB

Covers · 3 models

The models it covers

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

A CTI (Control Technology) product bulletin, dated 05OCT2010, for the 2512-A 75 watt AC power supply for CTI 2500 Series and SIMATIC 505 PLCs. Two units in a 2500-R11-A or 505-6511 base give a redundant supply. It lists the specifications and the steps to install and remove the module.

Device type
Triple-wide 120/240VAC power supply for CTI 2500 Series and SIMATIC 505 PLCs p. 1
Output
Up to 75 watts at +5VDC for the PLC CPU and I/O modules p. 1
Input voltage
90-264VAC, 47-63Hz, single phase; one 3-pin input terminal strip p. 1
Derating
75 W max. from 0 to 50°C; derate 1.75W/°C above 50°C p. 1
Redundancy
Dual configuration in a 2500-R11-A or 505-6511 base p. 1, 2
Bases
Single supply in standard 2500-R4, 2500-R8, 2500-R16-A bases p. 2
Input current
1.50 A max. at 110VAC; 0.75 A max. at 220VAC (full load) p. 1
Inrush current
37 A max. at 240VAC input p. 1
Fuse
1.5 Amp 250V, 3 AG, accessible on the front panel p. 1
Hold up time
100mSec at 75W load p. 1
Isolation
2800VDC AC to backplane; 1500VDC AC to chassis; 500VDC chassis to backplane p. 1
Temperature
Operating 0 to 60°C (normal locations); storage -40 to 85°C p. 1
Humidity
5% to 95%, non-condensing p. 1
Shipping weight
5.0 lbs (2.3 kg) p. 1

What this manual walks you through

  • Placing the supply in a single or redundant base p. 2
  • Installing and removing the power supply p. 2

Good to know

  • All power to the base is disabled before installing or removing the supply. p. 2
  • Input outside 90 to 264 VAC can damage the supply. p. 2
  • Output is derated by 1.75 W per °C above 50°C. p. 1

Questions this manual answers

Which PLCs does the 2512-A power supply fit?

CTI 2500 Series and SIMATIC 505 PLCs, in standard 2500-R4, 2500-R8 and 2500-R16-A bases or the 2500-R11-A and 505-6511 redundant bases. p. 1, 2

How do I set up redundant power with the 2512-A?

Install two 2512-A supplies in the leftmost two slots of a 2500-R11-A or 505-6511 base. p. 2

What fuse does the 2512-A use?

A 1.5 Amp 250V 3 AG fuse, reachable from the front panel. p. 1

What input voltage does the 2512-A accept?

90 to 264VAC, 47 to 63Hz, single phase. p. 1

The file

Size and text

Pages2
PDF65 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Control Technologies 2512-A, Siemens 2512-A and Texas Instruments 2512-A Manual

The text of page 1, from the PDF itself

2512-A 75 Watt AC Power Supply with Redundancy Support

Product Bulletin

2500 SeriesTM PLC System

Specifications

Description The 2512-A is a 120/240VAC Power Supply designed for CTI 2500 SeriesTM and SIMATIC® 505® PLCs. The triple-wide module provides up to 75 watts at +5VDC for use by the PLC CPU and I/O modules. When operated in a dual configuration in a 2500-R11-A base, it provides support for power supply redundancy.

Field Connections: One 3-pin 120VAC input terminal strip Input Voltage Operating Range: 90-264VAC, 47-63Hz, single phase Total Wattage Rating: 75 Watts maximum output @ 0oC to 50oC (derating 1.75W/oC above 50oC) Steady State Input Current at full load: 1.50 Amps max. @ 110VAC 0.75 Amps max. @ 220VAC Peak Inrush Current: 37 Amp. max. @ 240VAC input Fusing: 1.5 Amp 250V, 3 AG front panel accessible Hold Up Time: 100mSec @ 75W load Isolation: 2800VDC: 110/220 VAC-to-Backplane 500VDC: Chassis-to-Backplane 1500VDC: 110/220 VAC-to-Chassis Module Size: Triple-wide Operating Temperature: 0o to 60oC (normal locations) 0o to 50oC (Class 1 Div 2 locations) Storage Temperature: -40o to 85oC (-40o to 185oF) Relative Humidity: 5% to 95% (non-condensing) Agency Approvals (pending): UL, UL-Canada, Class 1 Div 2, CE Shipping Weight: 5.0 lbs (2.3 kg)

Features

  • CTI 2500 SeriesTM / SIMATIC® 505 base format
  • 90-264VAC, 47-63 Hz single phase input

power Up to 75 watts @ +5VDC to PLC CPU and I/O modules Works in CTI 2500-R11-A and Siemens® 505-6511 redundant bases

Control Technology Inc. 5734 Middlebrook Pike, Knoxville, TN 37921 Phone: 865/584-0440 Fax: 865/584-5720

www.controltechnology.com

Page 2 of Control Technologies 2512-A, Siemens 2512-A and Texas Instruments 2512-A Manual

The text of page 2, from the PDF itself

Power Supply Location in Base The 2512-A Power Supply can be installed in single sonfigurations in standard bases (2500-R4, 2500-R8, 2500-R16-A). For redundancy, 2512-A must be installed in a dual configuration in a 2500-R11-A or 505-6511 base. The two power supplies are installed in the leftmost two slots as shown below.

WARNING:

CAUTION
Disable all power to the base before installing or removing the power supply. Failure to do so could cause damage to the equipment or injury to personnel.

Do not attempt to operate the 2512-A Power Supply out of the Input Voltage Operating Ranges of 90 to 264 VAC. Damage to the Power Supply could occur if out of range input is applied.

Installing and Removing the Power Supply Use the following steps for installing and removing the 2512-A Power Supply from the system base. 1.Position the power supply so that the bezel is facing you. 2.Grasp the top and bottom of the power supply. 3.Carefully slide the power supply into the left most slot in the base until it engages into the backplane connectors. 4. Tighten top and bottom bezel screws into the base chassis. To remove power supply, reverse procedures 1 through 4 used for installation.

©2010 Control Technology Inc. 05OCT2010

All Rights Reserved

CTI P/N: 062-00376-010