A CTI (Control Technology) product bulletin, dated 05OCT2010, for the 2512-A 75 watt AC power supply for CTI 2500 Series and SIMATIC 505 PLCs. Two units in a 2500-R11-A or 505-6511 base give a redundant supply. It lists the specifications and the steps to install and remove the module.
- Device type
- Triple-wide 120/240VAC power supply for CTI 2500 Series and SIMATIC 505 PLCs p. 1
- Output
- Up to 75 watts at +5VDC for the PLC CPU and I/O modules p. 1
- Input voltage
- 90-264VAC, 47-63Hz, single phase; one 3-pin input terminal strip p. 1
- Derating
- 75 W max. from 0 to 50°C; derate 1.75W/°C above 50°C p. 1
- Redundancy
- Dual configuration in a 2500-R11-A or 505-6511 base p. 1, 2
- Bases
- Single supply in standard 2500-R4, 2500-R8, 2500-R16-A bases p. 2
- Input current
- 1.50 A max. at 110VAC; 0.75 A max. at 220VAC (full load) p. 1
- Inrush current
- 37 A max. at 240VAC input p. 1
- Fuse
- 1.5 Amp 250V, 3 AG, accessible on the front panel p. 1
- Hold up time
- 100mSec at 75W load p. 1
- Isolation
- 2800VDC AC to backplane; 1500VDC AC to chassis; 500VDC chassis to backplane p. 1
- Temperature
- Operating 0 to 60°C (normal locations); storage -40 to 85°C p. 1
- Humidity
- 5% to 95%, non-condensing p. 1
- Shipping weight
- 5.0 lbs (2.3 kg) p. 1
What this manual walks you through
Good to know
- All power to the base is disabled before installing or removing the supply. p. 2
- Input outside 90 to 264 VAC can damage the supply. p. 2
- Output is derated by 1.75 W per °C above 50°C. p. 1
Questions this manual answers
Which PLCs does the 2512-A power supply fit?
CTI 2500 Series and SIMATIC 505 PLCs, in standard 2500-R4, 2500-R8 and 2500-R16-A bases or the 2500-R11-A and 505-6511 redundant bases. p. 1, 2
How do I set up redundant power with the 2512-A?
Install two 2512-A supplies in the leftmost two slots of a 2500-R11-A or 505-6511 base. p. 2
What fuse does the 2512-A use?
A 1.5 Amp 250V 3 AG fuse, reachable from the front panel. p. 1
What input voltage does the 2512-A accept?
90 to 264VAC, 47 to 63Hz, single phase. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
2512-A 75 Watt AC Power Supply with Redundancy Support
Product Bulletin
2500 SeriesTM PLC System
Specifications
Description The 2512-A is a 120/240VAC Power Supply designed for CTI 2500 SeriesTM and SIMATIC® 505® PLCs. The triple-wide module provides up to 75 watts at +5VDC for use by the PLC CPU and I/O modules. When operated in a dual configuration in a 2500-R11-A base, it provides support for power supply redundancy.
Field Connections: One 3-pin 120VAC input terminal strip Input Voltage Operating Range: 90-264VAC, 47-63Hz, single phase Total Wattage Rating: 75 Watts maximum output @ 0oC to 50oC (derating 1.75W/oC above 50oC) Steady State Input Current at full load: 1.50 Amps max. @ 110VAC 0.75 Amps max. @ 220VAC Peak Inrush Current: 37 Amp. max. @ 240VAC input Fusing: 1.5 Amp 250V, 3 AG front panel accessible Hold Up Time: 100mSec @ 75W load Isolation: 2800VDC: 110/220 VAC-to-Backplane 500VDC: Chassis-to-Backplane 1500VDC: 110/220 VAC-to-Chassis Module Size: Triple-wide Operating Temperature: 0o to 60oC (normal locations) 0o to 50oC (Class 1 Div 2 locations) Storage Temperature: -40o to 85oC (-40o to 185oF) Relative Humidity: 5% to 95% (non-condensing) Agency Approvals (pending): UL, UL-Canada, Class 1 Div 2, CE Shipping Weight: 5.0 lbs (2.3 kg)
Features
- CTI 2500 SeriesTM / SIMATIC® 505 base format
- 90-264VAC, 47-63 Hz single phase input
power Up to 75 watts @ +5VDC to PLC CPU and I/O modules Works in CTI 2500-R11-A and Siemens® 505-6511 redundant bases
Control Technology Inc. 5734 Middlebrook Pike, Knoxville, TN 37921 Phone: 865/584-0440 Fax: 865/584-5720
www.controltechnology.com
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Power Supply Location in Base The 2512-A Power Supply can be installed in single sonfigurations in standard bases (2500-R4, 2500-R8, 2500-R16-A). For redundancy, 2512-A must be installed in a dual configuration in a 2500-R11-A or 505-6511 base. The two power supplies are installed in the leftmost two slots as shown below.
WARNING:
- CAUTION
- Disable all power to the base before installing or removing the power supply. Failure to do so could cause damage to the equipment or injury to personnel.
Do not attempt to operate the 2512-A Power Supply out of the Input Voltage Operating Ranges of 90 to 264 VAC. Damage to the Power Supply could occur if out of range input is applied.
Installing and Removing the Power Supply Use the following steps for installing and removing the 2512-A Power Supply from the system base. 1.Position the power supply so that the bezel is facing you. 2.Grasp the top and bottom of the power supply. 3.Carefully slide the power supply into the left most slot in the base until it engages into the backplane connectors. 4. Tighten top and bottom bezel screws into the base chassis. To remove power supply, reverse procedures 1 through 4 used for installation.
©2010 Control Technology Inc. 05OCT2010
All Rights Reserved
CTI P/N: 062-00376-010