Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Siemens 3RU1116-1GC1 Spec Sheet

Spec sheet · Siemens

Siemens 3RU1116-1GC1 Spec Sheet

Spec sheet2 pagesPDF 63 KB

Both pages are below, each with its text.

Download the PDF63 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

A two-page Siemens product data sheet, dated 01/11/2008, for the 3RU1116-1GC1 thermal overload relay in size S00 with Cage Clamp connections. It lists the current setting range, trip class, auxiliary contacts, fuse and motor ratings, mounting and enclosure rating. A reader can use it to check that the relay suits a motor and an S00 contactor.

Type
Overload relay, size S00, class 10, for installation as a single unit p. 1
Setting range
4.5 to 6.3 A p. 1
Auxiliary contacts
1 NO + 1 NC, no change-over contact p. 1
Motor rating
2.2 kW rated, three-phase motors p. 1
Fuse link
20 A rated p. 1
Connections
Cage Clamp terminals on the main circuit and on the auxiliary and control circuit p. 1
Contactor size
Combines with size S00 p. 1
Mounting
Stand-alone installation p. 2
Enclosure
IP20 p. 2
Type of assignment
2 p. 1
Protection marking
The spec sheet states type of protection DMT 98 ATEX G 001 p. 1

What this sheet walks you through

  • General technical details of the relay p. 1
  • Mechanical design and connection type p. 1
  • Ambient conditions p. 2

Good to know

  • The data sheet is subject to modifications; its last change is dated 10/31/2006. p. 2

Questions this sheet answers

What current range does the 3RU1116-1GC1 cover?

Its overload release adjusts from 4.5 A to 6.3 A. p. 1

What trip class is the 3RU1116-1GC1?

Class 10. p. 1

Which contactor size does the 3RU1116-1GC1 fit?

Size S00. p. 1

What fuse goes ahead of the 3RU1116-1GC1?

The data sheet gives a rated fuse link value of 20 A. p. 1

The file

Size and text

Pages2
PDF63 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Siemens 3RU1116-1GC1 Spec Sheet

The text of page 1, from the PDF itself

3RU1116-1GC1Page 1Product data sheet

3RU1116-1GC1 OVERLOAD RELAY, 4.5...6.3 A, 1NO+1NC, SIZE S00, CLASS 10, CAGE CLAMP CONNECTION, FOR INSTALLAT. AS A SINGLE UNIT

General technical details: Operating current / of the fuse link / rated value

20 A

Adjustable response current / of the current-dependent overload release / initial value

4.5 A

Adjustable response current / of the current-dependent overload release / final value

6.3 A

Service power / for three-phase servomotors / rated value

2.2 kW

Number of NC contacts / for auxiliary contact

1

Number of NO contacts / for auxiliary contact

1

Number of change-over switches / for auxiliary contact

0Type of assignement2Type of protectionDMT 98 ATEX G 001

Mechanical design: Design of the electrical connection / for main current circuit

Cage Clamp terminals

Design of the electrical connection / for auxiliary and control current circuit

Cage Clamp terminals

Size of the contactor / can be combined / companyspecific

S00

Date: 01/11/2008

subject to modifications © Copyright Siemens AG 2008

Page 2 of Siemens 3RU1116-1GC1 Spec Sheet

The text of page 2, from the PDF itself

3RU1116-1GC1

Page 2

Type of fixing/fixation

stand-alone installation

Size of overload relay

S00

Ambient conditions: Protection class IP

IP20

last change
10/31/2006
Technical Assistance
Date: 01/11/2008
Telephone
+49 (0) 911-895-5900 (8°° - 17°° CET)
Fax
+49 (0) 911-895-5907
E-Mail
technical-assistance@siemens.com
Internet
www.siemens.de/lowvoltage/technical-assistance

subject to modifications © Copyright Siemens AG 2008