A four-page Siemens data sheet, dated 30.06.2015, for the SIRIUS 3RV1031-4EB10 motor protection circuit breaker in size S2 with screw connections. It gives the current settings, voltage and breaking capacity ratings, ambient limits, mounting, dimensions and conductor sizes, with a dimension drawing and circuit symbol. A reader can use it to check that the breaker suits a motor circuit and a panel.
- Type
- SIRIUS circuit breaker for motor protection, size S2, class 20, standard breaking capacity p. 1
- Overload setting
- 22 to 32 A adjustable; instantaneous (N) release 416 A p. 1
- Rated voltage
- 690 V p. 1
- AC-3 at 400 V
- 32 A, 15 kW p. 2
- Breaking capacity Icu
- 100 kA at 240 V, 50 kA at 400 V, 10 kA at 500 V, 4 kA at 690 V p. 2
- Release design
- Thermomagnetic p. 2
- Mounting
- Screw or snap-on onto 35 mm standard rail (DIN EN 50022), any position p. 2
- Dimensions
- 140 mm high, 55 mm wide, 149 mm deep p. 2
- Terminals
- Screw-type with box terminals on the main circuit; screw-type on auxiliary and control circuit p. 2
- Main conductors
- Solid 2x (0.75 to 16 mm²); stranded 2x (0.75 to 25 mm²) or 1x (0.75 to 35 mm²); AWG 2x or 1x (18 to 2) p. 3
- Ambient temperature
- -20 to +60 °C operating; -50 to +80 °C storage and transport p. 1
- Power loss
- 15 W typical p. 1
- Mechanical life
- 50 000 switching cycles typical (main contacts) p. 1
- Accessories
- Can be expanded with an auxiliary switch p. 1
What this sheet walks you through
- Main circuit ratings at AC-3 p. 1, 2
- Short-circuit breaking capacity by voltage p. 2
- Mounting, dimensions and side-by-side spacing p. 2
- Conductor cross-sections for the main contacts p. 3
- Dimension drawing and circuit symbol p. 4
Good to know
- Maximum installation altitude is 2 000 m. p. 1
- At AC-3 the maximum operating frequency is 15 per hour. p. 2
- Side-by-side mounting needs 0 mm spacing at the side and backwards. p. 2
Questions this sheet answers
What current range does the 3RV1031-4EB10 cover?
Its overload release adjusts from 22 A to 32 A, and it is a trip class 20 breaker. p. 1
What motor size can the 3RV1031-4EB10 protect at 400 V?
At AC-3 and 400 V it is rated 32 A and 15 kW. p. 2
What is the breaking capacity of the 3RV1031-4EB10?
Icu is 100 kA at 240 V, 50 kA at 400 V, 10 kA at 500 V and 4 kA at 690 V. p. 2
How big is the 3RV1031-4EB10?
140 mm high, 55 mm wide and 149 mm deep; it mounts on 35 mm rail. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Data sheet
3RV1031-4EB10 CIRCUIT-BREAKER, SIZE S2, FOR MOTOR PROTECTION, CLASS 20, A-RELEASE 22...32 A, N-RELEASE 416 A, SCREW CONNECTION, STANDARD BREAKING CAPACITY
product brand nameSIRIUSProduct designationcircuit breakerDesign of the productfor motor protection
General technical data: Product expansion
- Auxiliary switch
Yes
Active power loss total typical
15 W
Surge voltage resistance Rated value
6 000 V
Protection class IP
- on the front
IP20
Mechanical service life (switching cycles)
- of the main contacts typical
50 000
Ambient conditions: Installation altitude at height above sea level maximum
2 000 m
Ambient temperature
- during operation
-20 ... +60 °C● during storage-50 ... +80 °C● during transport-50 ... +80 °C
Main circuit: Adjustable response value current of the currentdependent overload release
22 ... 32 A
Operating voltage
- Rated value
3RV1031-4EB10 Page 1/4690 V30.06.2015
Changes preserved © Copyright Siemens AG
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
- at AC-3 Rated value maximum
690 V
Operating current
- at AC-3, at 400 V Rated value
32 A
Operating power
- at AC-3, at 400 V Rated value
15 kW
Operating frequency
- at AC-3 maximum
15 1/h
Auxiliary circuit: Number of CO contacts
- for auxiliary contacts
0
Protective and monitoring functions: Trip class
CLASS 20
Maximum short-circuit current breaking capacity (Icu)
- at AC at 240 V Rated value
100 kA
- with AC at 400 V Rated value
50 kA
- at AC at 500 V Rated value
10 kA
- at AC at 690 V Rated value
4 kA
Short-circuit: Design of the overcurrent release and short-circuit release
thermomagnetic
Installation/ mounting/ dimensions: mounting position
any
Mounting type
screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Height140 mmWidth55 mmDepth149 mm
Required spacing
- with side-by-side mounting, Backwards
0 mm, at the side
0 mm
Connections/ Terminals: Product function
- removable terminal for auxiliary and control circuit
No
Type of electrical connection
- for main current circuit
screw-type terminals with box terminals
- for auxiliary and control current circuit
screw-type terminals3RV1031-4EB10 Page 2/430.06.2015
Changes preserved © Copyright Siemens AG
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Arrangement of electrical connectors for main current circuit
front side
Type of connectable conductor cross-section
- for main contacts, solid
2x (0.75 ... 16 mm²), stranded
2x (0.75 ... 25 mm²), 1x (0.75 … 35 mm²), finely stranded with core end processing
2x (0.75 ... 16 mm²), 0.75 ... 25 mm²
- for AWG conductors for main contacts
2x (18 ... 2), 1x (18 ... 2)
Mechanical data: Size of the circuit-breaker
S2
Certificates/ approvals: General Product Approval
Declaration of Conformity
Test Certificates
Shipping Approval
spezielle Prüfbescheinigunge n
Shipping Approvalother Bestätigungensonstig
other Umweltbestätigung
Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system) http://www.siemens.com/industrymall
Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV10314EB10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV10314EB10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV10314EB10&lang=en
3RV1031-4EB10 Page 3/4
30.06.2015
Changes preserved © Copyright Siemens AG
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
30∅55512945 100 140SIEMENS5 864 144-F1/L1 3/L2 5/L3I>I>I>
- 2/T1 4/T2 6/T3 last modified
- 3RV1031-4EB10 Page 4/4
29.06.2015
30.06.2015