A four-page Siemens data sheet, dated 30.06.2015, for the SIRIUS 3RV1031-4EB10 motor protection circuit breaker in size S2 with screw connections. It gives the current settings, voltage and breaking capacity ratings, ambient limits, mounting, dimensions and conductor sizes, with a dimension drawing and circuit symbol. A reader can use it to check that the breaker suits a motor circuit and a panel.

Type
SIRIUS circuit breaker for motor protection, size S2, class 20, standard breaking capacity p. 1
Overload setting
22 to 32 A adjustable; instantaneous (N) release 416 A p. 1
Rated voltage
690 V p. 1
AC-3 at 400 V
32 A, 15 kW p. 2
Breaking capacity Icu
100 kA at 240 V, 50 kA at 400 V, 10 kA at 500 V, 4 kA at 690 V p. 2
Release design
Thermomagnetic p. 2
Mounting
Screw or snap-on onto 35 mm standard rail (DIN EN 50022), any position p. 2
Dimensions
140 mm high, 55 mm wide, 149 mm deep p. 2
Terminals
Screw-type with box terminals on the main circuit; screw-type on auxiliary and control circuit p. 2
Main conductors
Solid 2x (0.75 to 16 mm²); stranded 2x (0.75 to 25 mm²) or 1x (0.75 to 35 mm²); AWG 2x or 1x (18 to 2) p. 3
Ambient temperature
-20 to +60 °C operating; -50 to +80 °C storage and transport p. 1
Power loss
15 W typical p. 1
Mechanical life
50 000 switching cycles typical (main contacts) p. 1
Accessories
Can be expanded with an auxiliary switch p. 1

What this sheet walks you through

  • Main circuit ratings at AC-3 p. 1, 2
  • Short-circuit breaking capacity by voltage p. 2
  • Mounting, dimensions and side-by-side spacing p. 2
  • Conductor cross-sections for the main contacts p. 3
  • Dimension drawing and circuit symbol p. 4

Good to know

  • Maximum installation altitude is 2 000 m. p. 1
  • At AC-3 the maximum operating frequency is 15 per hour. p. 2
  • Side-by-side mounting needs 0 mm spacing at the side and backwards. p. 2

Questions this sheet answers

What current range does the 3RV1031-4EB10 cover?

Its overload release adjusts from 22 A to 32 A, and it is a trip class 20 breaker. p. 1

What motor size can the 3RV1031-4EB10 protect at 400 V?

At AC-3 and 400 V it is rated 32 A and 15 kW. p. 2

What is the breaking capacity of the 3RV1031-4EB10?

Icu is 100 kA at 240 V, 50 kA at 400 V, 10 kA at 500 V and 4 kA at 690 V. p. 2

How big is the 3RV1031-4EB10?

140 mm high, 55 mm wide and 149 mm deep; it mounts on 35 mm rail. p. 2

The file

Size and text

Pages4
PDF344 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Siemens 3RV1031-4EB10 Spec Sheet

The text of page 1, from the PDF itself

Data sheet

3RV1031-4EB10 CIRCUIT-BREAKER, SIZE S2, FOR MOTOR PROTECTION, CLASS 20, A-RELEASE 22...32 A, N-RELEASE 416 A, SCREW CONNECTION, STANDARD BREAKING CAPACITY

product brand nameSIRIUSProduct designationcircuit breakerDesign of the productfor motor protection

General technical data: Product expansion

  • Auxiliary switch

Yes

Active power loss total typical

15 W

Surge voltage resistance Rated value

6 000 V

Protection class IP

  • on the front

IP20

Mechanical service life (switching cycles)

  • of the main contacts typical

50 000

Ambient conditions: Installation altitude at height above sea level maximum

2 000 m

Ambient temperature

  • during operation

-20 ... +60 °C● during storage-50 ... +80 °C● during transport-50 ... +80 °C

Main circuit: Adjustable response value current of the currentdependent overload release

22 ... 32 A

Operating voltage

  • Rated value

3RV1031-4EB10 Page 1/4690 V30.06.2015

Changes preserved © Copyright Siemens AG

Page 2 of Siemens 3RV1031-4EB10 Spec Sheet

The text of page 2, from the PDF itself

  • at AC-3 Rated value maximum

690 V

Operating current

  • at AC-3, at 400 V Rated value

32 A

Operating power

  • at AC-3, at 400 V Rated value

15 kW

Operating frequency

  • at AC-3 maximum

15 1/h

Auxiliary circuit: Number of CO contacts

  • for auxiliary contacts

0

Protective and monitoring functions: Trip class

CLASS 20

Maximum short-circuit current breaking capacity (Icu)

  • at AC at 240 V Rated value

100 kA

  • with AC at 400 V Rated value

50 kA

  • at AC at 500 V Rated value

10 kA

  • at AC at 690 V Rated value

4 kA

Short-circuit: Design of the overcurrent release and short-circuit release

thermomagnetic

Installation/ mounting/ dimensions: mounting position

any

Mounting type

screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022

Height140 mmWidth55 mmDepth149 mm

Required spacing

  • with side-by-side mounting, Backwards

0 mm, at the side

0 mm

Connections/ Terminals: Product function

  • removable terminal for auxiliary and control circuit

No

Type of electrical connection

  • for main current circuit

screw-type terminals with box terminals

  • for auxiliary and control current circuit

screw-type terminals3RV1031-4EB10 Page 2/430.06.2015

Changes preserved © Copyright Siemens AG

Page 3 of Siemens 3RV1031-4EB10 Spec Sheet

The text of page 3, from the PDF itself

Arrangement of electrical connectors for main current circuit

front side

Type of connectable conductor cross-section

  • for main contacts, solid

2x (0.75 ... 16 mm²), stranded

2x (0.75 ... 25 mm²), 1x (0.75 … 35 mm²), finely stranded with core end processing

2x (0.75 ... 16 mm²), 0.75 ... 25 mm²

  • for AWG conductors for main contacts

2x (18 ... 2), 1x (18 ... 2)

Mechanical data: Size of the circuit-breaker

S2

Certificates/ approvals: General Product Approval

Declaration of Conformity

Test Certificates

Shipping Approval

spezielle Prüfbescheinigunge n

Shipping Approvalother Bestätigungensonstig

other Umweltbestätigung

Further information Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system) http://www.siemens.com/industrymall

Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV10314EB10

Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RV10314EB10

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV10314EB10&lang=en

3RV1031-4EB10 Page 3/4

30.06.2015

Changes preserved © Copyright Siemens AG

Page 4 of Siemens 3RV1031-4EB10 Spec Sheet

The text of page 4, from the PDF itself

30∅55512945 100 140SIEMENS5 864 144-F1/L1 3/L2 5/L3I>I>I>

2/T1 4/T2 6/T3 last modified
3RV1031-4EB10 Page 4/4

29.06.2015

30.06.2015

Changes preserved © Copyright Siemens AG