The operating instructions (Edition 02.98) for the Siemens AS-I power supply unit 3RX9307-0AA00, printed as 3RX9307-OAAOO. They describe what the unit does, its technical data, and how to install, connect, store and maintain it. They let a reader set the mains voltage, mount and wire the unit, and look after it safely.

Device
Power supply unit for AS-I systems with integrated data link p. 1
Output
Stabilized DC 30 V with low residual ripple p. 1
Mains input
AC 230 V or AC 115 V, set by a changeover switch; factory setting AC 230 V p. 2
Operating principle
Primary switched-mode regulator, switching at 100 kHz, with electrical isolation between mains and output p. 1
Short circuit
Output is short-circuit-proof and restarts automatically once the short is cleared p. 2
Mounting
Snaps onto a 35 mm top-hat rail with ventilation slots at top and bottom p. 2
Terminals
Cage-clamp terminals, finger safe to DIN VDE 0106, Part 100 p. 2
Wiring tool
Screwdriver to DIN 5264 (3.5 x 0.5 mm) to open the terminal p. 2
Safety class
Class I, metal housing must be earthed p. 2
Storage
Store dry; after up to 3 years of storage it may go on full mains voltage without preparation p. 2

What this manual walks you through

  • How the power supply works p. 1
  • Setting the mains voltage switch p. 2
  • Mounting on a top-hat rail and connecting the leads p. 2
  • Incoming inspection, transport and storage p. 2
  • Servicing and cleaning p. 2

Good to know

  • A unit left at AC 230 V on a 115 V supply works at first, then faults under load after a time. p. 2
  • Because the unit restarts by itself, loads also restart automatically; guard against damage or injury. p. 2
  • The exposed metal housing can become live in a fault, so the unit must be earthed. p. 2
  • Disconnect the unit from the mains and secure it against switching on before servicing. p. 2
  • Do not exceed the insulation-stripping length shown in figure 3. p. 2

Questions this manual answers

What voltage does the Siemens 3RX9307-0AA00 put out?

A stabilized DC 30 V for AS-I systems. p. 1

Can the 3RX9307-0AA00 run on 115 V?

Yes, a changeover switch sets it to AC 230 V or AC 115 V; it leaves the factory set to AC 230 V. p. 2

How is the AS-I power supply mounted?

It snaps onto a 35 mm top-hat rail with the ventilation slots at the top and bottom. p. 2

What happens if the 3RX9307-0AA00 output is shorted?

The output is short-circuit-proof, and the unit restarts by itself once the short is removed. p. 2

The file

Size and text

Pages2
PDF294 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Siemens 3RX9307-0AA00 Manual

The text of page 1, from the PDF itself

SIEMENS AS-l-PowerOperating instructionssupply unitCC3RX9307-OAAOO1NOTE

These operating instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the Purchaser’s purposes, the matter should be refered to the local Siemens Sales Cffice. The contents of these operating instructions shall not become part or modify any prior or existing agreement, commitment or relationship. The Sales Contract contains the entire obligations of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements contained herein do not create new warranties or modify the existing warranty.

A !

WARNING Hazardous voltages are present in this electrical equipment during operation. Non-observanceofthesafetyinstructionscanresuit in severe personal injury or property damage. Only qualified personal should work on or around this equipment after becoming thoroughly familiar with all warnings, safety notices and maintenance procedures contained herein. The successful and safe operation of this equipment is dependent on proper handling installation, operation and maintenance.

GIUALIFIED PERSON For the purpose of these operating instructions and product labels, a “qualified person” is one who is familiar with the installation, construction and operation of the equipment and the hazards involved. In addition, he has the following qualifications: a)

Is trained and authorized to energize, denergize, clear, ground and tag circuits and equipment in accordance with established safety practices

b)

Is trained in the proper care and use of protective equipment in accordance with established safety practices

c)

Is trained in rendering first aid

Edition 02.98

DANGER For the purpose of this operating instructions and product labels, “Danger” indicates death, severe personal injury or substantial property damage will result if proper precautions are not taken. WARNING For the purpose of this operating instructions and product labels, “Warning” indicates death, severe personal injury or substantial property damage can result if proper precautions are not taken CAUTION For the purpose of this operating instructions and product labels, “Caution” indicates minor personal injury or property damage can result if proper precautions are not taken. NOTE For the purpose of this operating instructions, “Note” indicates information about the product or the respective part of the operating instruction which is essential to highlight.

2Description2.1Applicationand mode of operation

The power supply unit is used to operate AS-I systems with integrated data link. The unit generates a stabilised, highly constant direct current voltage of DC 30 V with low residual ripple. The power supply unit operates on the basis of the primary switched-mode regulator principle. The task of the DC/DC converter is to convert the high DC link voltage to the low output voltages. It also performs the task of safe electrical isolation between mains circuit and output circuit. A control IC performs all regulation and drive functions for the power switching transistor. This transistor is switched at a frequency of 100 kHz so as to produce a stabilised square-wave AC voltage in the transformer’s secondary circuit. This AC voltage is rectified and filtered in the secondary circuit. 2.2 Conformity with European Directives The DC power supply unit complies with the requirements following European Directives : Low Voltage Directive 73/23/EEC EMC Directive 89/338/EEC the following limits are met : : EN 55 081- 1 (Residential) Emission Immunity : EN 55 082-2 (Industrial)

of the

Order No. TDV BASOO30 - 76-D

Page 2 of Siemens 3RX9307-0AA00 Manual

The text of page 2, from the PDF itself

2.3 Technical data Compliance with standards Primary voltage Ul N reversible or Frequency Secondary voltage U2N Voltage range Ripple act. AS- I -specification

;sC 230V (195 . . . 253V) AC 115V ( 102 ... 132 V) : 50 ... 60 Hz : DC30V : DC 29,5 . .. 31,6 V

Current limiting Load control Interference suppression Efficiency Ambient temp. / Temp. class Degree of protection Safety class Permitted storage temperature Installation conditions Humidity stressing Mean value up to Max. value for 30 days per year Occasionally at 40 OC Installation altitude

5

< 50 mVss : 2,4A : > 2,8A :<l% : Limiting value B act. DIN VDE 0875 part 11 : > 80 % : ta550C/B : IP 20 : class I : - 25 OC . .. + 60 OC : areas with outdoor climate according to DIN 50010

The unit can be set either to AC 230 V or to AC 115 V mains Joltage using a changeover switch. The factory default setting is AC 230 V. Before setting the unit into operation, please check that it has been set to the correct mains voltage. In the event of the unit still being set to AC 230 V mains voltage despite the fact that your local mains supply is AC 115 V, the unit will initially operate correctly and will then revert to fault condition as of a certain load after a certain time. Consequently, if faults occur, please first check whether the unit is set to the correct mains voltage. The power supply unit’s output is short-circuit-proof. The unit restarts automatically after the short circuit has been eliminated.

AAIDANGER!

Owing to the fact that the unit recovers its voltage automatically, always take precautions to prevent damage oe injury from the loads which will thus also resat-t automatically.

TRANSPORT

Immediately inspect the consignment for completeness and damage on receipt. If damage has occurred, please elaborate a damage report and consult the haulage contractor. The equipment should be transported carefully and, wherever possible, in the original packaging. Store the equipment in a dry location. Within a storage period of up to 3 years, the device may be connected to full mains voltage with no further preparations as regards the smoothing capacitors.

INSTALLATION,OPERATION5

: 80 % relative humidity : 95 % relative humidity : 100 % relative humidity : up to 1 .OOOm above sea level

INCOMING INSPECTION, AND STORAGE

4

This device is designed in accordance with class I. Owing to the exposed, conductive metal housing, it may become electrically live in the event of a fault and it is thus absolutely essential that it be earthed. Non-observance can result in death or severe

personal injury.

Secondary rated current 12~

3WARNINGA!: EN 60 950 (VDE 0805)

non-observance can result in severe personal injury or substantial property demage.

SERVICING,6 /\ !4I

Safe operation is dependant upon proper handling and installation by qualified personnel under observance of all warnings contained in these operating instructions. In particular the general erecting and safety regulations (e. g. DIN, VDE, EN) and regulations regarding the correct use of hoisting gear and tools and of personal protechtive gear shall be observed. Non-observance can result In death, severe

WARNING Please disconnect the unit from the mains power supply and secure it to prevent it being switched back on again before starting servicing work.

ASSEMBLYWARNINGMAINTENANCE

Non-observance can lead to death, serious injury or substantial property demage.

Servicing and maintenance are essentially restricted to inspecting the unit for excessive dust deposits and, if necessary, cleaning it at regular intervals (e.g. once per year).

b

personal Injury or substantial property damage. Figure 1 : Block diagram The unit is designed for installation in enclosed controls and circuitry cubicles and, if wall-mounted, may be operated continuosly at temperatures up to the ambient temperature specified in the technical data. The unit must be snapped onto a 35 mm top-hat rail, in which case the ventilation slots must be at the top and bottom. Please refer to Fig. 3 for overall space required. The unit is connected by means of cage-clamp terminals in accordance with the information on the rating plate. The terminals are safe from finger touch to DIN VDE 0106, Part 100. Fig. 3 shows the position of the connection elements and the required insulation-stripping lengths for the leads. Connect the leads by operating the button to the left of the lead receptacle with a screwdriver to DIN 5264 (3.5 x 0.5 mm) and, at the same time, fully inserting the lead (see Fig. 2) from which the insulation has been stripped to the required lengh beforehand. NOTE The insulation -stripping length shown in figufe 3 shall not be exceeded since, oherwhise, the clearance and creepage distances would be less than required.

Figure 2 : Connecting 0 Siemens AG 1998

primary switch-mode

Selector switch 230 V I 115 V Fuse Fl = 5x20

f/0LED2ATPrimarySecondai_ 460 4 Snap-in ormounting

to top hat rail act. to DIN EN 50022-

Terminalsthe leadsregulatorWire range35 x 7,5 35x15mm2

Insulation stripping length mm

0,08 . .. 2,5

5 ... 6