Page 337
A–7 Quick Start Example
Apply power to the system and ensure the CPU PWR indicator is on. If the indicator is not on, disconnect the system power and check the wiring connections. If the wiring connections are correct, refer to Chapter 13 for additional assistance. WARNING: To minimize the risk of electrical shock, make sure the power source is disconnected before you check the power wiring.
The switch wired to the input module and status indicator (LED) on the face of the output module will be the two I/O points used in the simple rung of ladder logic you will enter. The following diagram shows the ladder logic representation of the the program which will be entered on the handheld programmer. output 010 input 000
Enter the key sequences on the handheld programmer as shown below. CLR
SHF
3
4
STR
SHF
0
ENT
OUT
SHF
1
0
8
ENT
DEL
NXT
(Clears the CPU memory) (Stores input 000) (Outputs an on or off state to address 010)
With the programmer’s key switch in the PRG position, open and close the field input switch and observe that only the 0 LED on the input module turns on and off. This indicates the input signal is being received. Now put the programmers key switch in the run position. The RUN LED on the programer’s display will turn on. Open and close the field input switch and observe the 0 LED on the face of the input module and the 0 LED on the face of the output module both turn on and off. This indicates the program is accurately reflecting the signals which it is receiving from the field device.
Appendix B DL405 Product Cross Ref.
Step 10: Enter the Example Program
Appendix A Quick Start Example
Step 9: Connect the Power Source
Page 338
Page 339
DL305 Error Codes
In This Appendix. . . .
Ċ Error Code Table
1B
Page 340
B–2
Appendix B DL305 Error Codes
Appendix A DL305 Error Codes
DL305 Error Codes
DL305 Error Code
Description
E01 Invalid Keystrokes
Invalid keystroke or series of keystrokes entered into the handheld programmer. Refer to the DL305 Handheld Programmer manual for assistance in the operation you are trying to perform.
E02 An I/O point dedicated to an input module has been used as an output in the Input Point Programmed application program. Change the I/O reference number in the program which is as Output causing the error. E03 Stack Overflow
The maximum number of instructions utilizing the internal stack has exceeded eight. These instructions can be a combination of AND STRs, OR STRs and MCS/MCR groups. Reduce the number of these instructions which are pushed onto the stack at one time.
E05 (NON Stage) Duplicate Coil Reference
Two or more output coils have the same data type and number. Change the duplicate coil to correct the error. Duplicate coil references are valid with the SET instruction. E05 will be generated at the address of the second duplicated output.
E05 (Stage) Duplicate Stage Reference
Two or more Stages have the same reference number. Change the duplicate Stage number to correct the error. E05 will be generated at the address of the second duplicated stage number.
E06 MCR/MCS Mismatch
The number of MCR instructions do not match the number of MCS instructions. Each MCR must have an accompanying MCS.
E07 Missing CNT or SR Contact
A required input contact is missing from a CNT (example, RESET input) or a SR instruction.
E08 Invalid Data Values
The required data values for a TMR, CNT or SR are missing or incorrect. Refer to the DL305 Programming Manual Set for details on these instructions.
E09 Incomplete Program Rung
The rung does not terminate with an output as required. Program an output to terminate the rung properly.
E11 Program Full
There is no available program addresses in memory. Reduce the size of the program.
E21 Program Memory Parity Error
A parity error has occurred in the program memory of the CPU. Clear the memory and reload the program. If the error reoccurs replace the CPU. Severe electrical noise will cause this problem.
E22 Password Error
The password stored in the CPU is invalid. Press the “CLR” key twice on the handheld programmer and the password will be reset to 0000. Re-enter the password if required.
E25 A mismatch was found when a compare was performed on the program in CPU Tape/Program Mismatch memory and the program stored on tape. E28 Volume Incorrect On Tape Device.
The volume is incorrect on the tape player being used to load the program to the CPU. Adjust the volume and retry the operation. Refer to the DL305 Handheld Programmer manual for details on tape operation.
E31 RAM Limit Exceeded
The application program required more RAM for execution than is available. Reduce the length of the program.
E377 EEPROM Write Error
Write of EEPROM failed because EEPROM is write protected (remove write protect jumper), the EEPROM is bad (replace EEPROM), or UVPROM is installed instead of EEPROM (install EEPROM).
E99 Instruction Not Found
A search was performed and the specified instruction was not found in the application program.
Page 341
Instruction Execution Times In This Appendix. . . .
Ċ Introduction Ċ DL330 Instruction Execution Times Ċ DL330P Instruction Execution Times Ċ DL340 Instruction Execution Times
1C
Page 342
C–2 Introduction This appendix contains several tables that provide the instruction execution times for the DL330, DL330P, and DL340 CPUs. One thing you will notice is that many of the execution times depend on the type of data being used with the instruction. For example, some of the instructions have different execution times if you use a regular data register instead of a constant. You’ll also notice that some of the data instructions (such as DSTR) require differing amounts of execution time depending on the type of data. There are generally three options. S Data Registers S I/O Data Registers S Constants The following paragraphs may help you understand the differences between the register types. Data Registers
Appendix D Inst. Execution Times
Appendix C Inst. Execution Times
Appendix B DL405 Error Codes
Appendix A DL405 Error Codes
Instruction Execution Times
Some data registers are primarily used to hold variable data and are considered true data registers. For example, the registers that store the timer or counter current values, or just regular variable data would be considered as a data register. Don’t think that you cannot load a bit pattern into these types of registers, you can. It’s just that their primary use is as a data register. The following locations are considered as data registers. Type of Data
I/O Data Registers
DL330
DL330P
DL340
Timer / Counter Current Values
R600 – R677
R600 – R677
R600 – R677
User Data Words
R400 – R563
R400 – R563
R400 – R563 R700 – R767
You may recall that the I/O points are automatically mapped into data register locations. The following locations that contain this data are considered I/O registers and will take longer to execute with most instructions. Type of Data I/O Points
DL330 R000 – R016* R070 – R 076
DL330P R000 – R016* R070 – R076
DL340 R000 – R017* R070 – R076
NOTE: 160 – 167 can be used as I/O in a DL330 or DL330P CPU under certain conditions. 160 – 177 can be used as I/O in a DL340 CPU under certain conditions. You should consult Chapter 4 to determine which configurations allow the use of these points. These points are normally used as control relays. You cannot use them as both control relays and as I/O points. Also, if you use these points as I/O, you cannot access these I/O points as a Data Register reference.
Page 343
C–3 Instruction Execution Times
Some of the instructions can have more than one parameter so the table shows execution times that depend on the amount and type of parameters. For example, the when you use the SET instruction to set a range of stages in a DL330P CPU, the execution time depends on how many stages are being set by the instruction. Two Locations Available X0
X1
S10 – S17 SET
Appendix A DL405 Error Codes
How to Read the Tables
C0
Stage Instruction
Stage Instruction not activated by a Jump instruction (ex. power flow)
SET SG
26.3 + 13.1ms x (n–1)
18.8 ms
Does not apply
RST SG
26.3 + 13.1ms x (n–1)
18.8 ms
Does not apply
Appendix C Inst. Execution Times
Execution depends on numbers of locations and types of data used
Appendix B DL405 Error Codes
Instruction
Appendix D Inst. Execution Times
Page 344
C–4 DL330 Instruction Execution Times Basic Input Instructions
Appendix D Inst. Execution Times
Appendix C Inst. Execution Times
Appendix B DL405 Error Codes
Appendix A DL405 Error Codes
Instruction Execution Times
Output Type Instructions
Instruction
Execute
Disabled by MCR
STR
6.6 ms
N/A
STR NOT
9.1 ms
N/A
AND
5.3 ms
N/A
AND NOT
8.4 ms
N/A
OR
6.6 ms
N/A
OR NOT
9.1 ms
N/A
STR T/C
10.3 ms
N/A
STR NOT T/C
12.8 ms
N/A
AND T/C
5.3 ms
N/A
AND NOT T/C
8.4 ms
N/A
OR T/C
6.6 ms
N/A
OR NOT T/C
9.1 ms
N/A
STR (Comparative Contact)
50.9 ms
N/A
STR NOT (Comparative Contact)
61.5 ms
N/A
AND (Comparative Contact)
59.1 ms
6.2 ms
AND NOT (Comparative Contact)
60.3 ms
6.2 ms
OR (Comparative Contact)
60.3 ms
6.2 ms
OR NOT (Comparative Contact)
62.5 ms
6.2 ms
AND STR
3.8 ms
N/A
OR STR
3.8 ms
N/A
MCR
5.0 ms
N/A
MCS
3.0 ms
N/A
Instruction
Execute
Not Executed
OUT
7.5 ms
7.5 ms
SET OUT
10.0 ms
10.0 ms
SET
17.5 ms
17.5 ms
RST
9.3 ms
9.3 ms
SET OUT RST
19.3 ms
19.3 ms
Page 345
C–5 Instruction Execution Times
Instruction
Execute w/ Constant
Execute w/ Data Register
Execute w/ I/O Register
Not Executed
TMR
90.9 ms
458.8 ms
700.0 ms
27.1 ms
CNT
92.9 ms
465.6 ms
706.8 ms
27.1 ms
SR
64.1 ms+16.6 ms times ( # of shifts)
Data Operations
Instruction
Execute w/ Data Register
Execute w/ I/O Register
53.1 ms
Execute w/ Constant
Appendix A DL405 Error Codes
Timer, Counters, and Shift Registers
Not Executed
321.9 ms
14.3 ms
6.3 ms
DSTR1
F51
63.8 ms
140.9 ms
N/A
6.3 ms
DSTR2
F52
95.0 ms
172.2 ms
N/A
6.3 ms
DSTR3
F53
96.6 ms
173.8 ms
N/A
6.3 ms
DSTR5
F55
N/A
326.2 ms
N/A
6.3 ms
DOUT
F60
52.6 ms
329.4 ms
N/A
6.3 ms
DOUT1
F61
39.1 ms
160.1 ms
N/A
6.3 ms
DOUT2
F62
39.8 ms
116.0 ms
N/A
6.3 ms
DOUT3
F63
55.0 ms
108.1 ms
N/A
6.3 ms
DOUT5
F65
N/A
358.3 ms
N/A
6.3 ms
CMP<=>
F70
112.8 ms
354.0 ms
57.0 ms
6.3 ms
ADD
F71
456.8 ms
698.0 ms
262.0 ms
6.3 ms
SUB
F72
315.8 ms
557.0 ms
275.0 ms
6.3 ms
MUL
F73
290–2664 ms
497–2851 ms
223–2576 ms
6.3 ms
DIV
F74
742–2645 ms
1218–2851ms
720–2557 ms
6.3 ms
DAND
F75
103.7 ms
345.0 ms
55.6 ms
6.3 ms
DOR
F76
103.7 ms
345.0 ms
55.6 ms
6.3 ms
SHFR
F80
216 ms+13.4 ms times ( # of shifts)
6.3 ms
SHFL
F81
220 ms+13.4 ms times ( # of shifts)
6.3 ms
DECO
F82
56.3 ms
N/A
N/A
6.3 ms
ENCO
F83
282.0 ms
N/A
N/A
6.3 ms
INV
F84
30.0 ms
N/A
N/A
6.3 ms
BIN
F85
412.2 ms
N/A
N/A
6.3 ms
BCD
F86
746.0 ms
N/A
N/A
6.3 ms
FAULT
F20
114.0 ms
355.3 ms
72.2 ms
6.3 ms
Appendix D Inst. Execution Times
80.7 ms
Appendix C Inst. Execution Times
F50
Appendix B DL405 Error Codes
DSTR
Page 346
C–6 DL330P Instruction Execution Times Basic Input Instructions
Appendix C Inst. Execution Times Appendix D Inst. Execution Times
I/O, Control Relay
Instruction
Executed *
Appendix B DL405 Error Codes
Appendix A DL405 Error Codes
Instruction Execution Times
**
Timer, Counters, and Shift Registers
Not Executed *
Not Executed
Executed
**
*
Timer / Counter
**
*
Executed
**
*
Not Executed
**
*
STR
28.4 / 31.4ms
21.3 ms
25.6 / 30.9ms
22.2 ms
121.3/117.8ms
28.4 ms
STR NOT
28.4 / 31.4ms
21.3 ms
25.6 / 30.9ms
22.2 ms
121.3/117.8ms
28.4 ms
AND
13.4 / 20.0ms
13.4 / 20.0ms
13.4 / 20.0ms
13.4 / 20.0ms
123.1/119.6ms
20.3 ms
AND NOT
18.1 / 21.6ms
10.3 ms
18.1 / 21.6ms
10.3 ms
123.1/119.6ms
20.3 ms
OR
21.8 / 25.3ms
14.7 ms
21.8 / 25.3ms
14.7 ms
123.1/119.6ms
20.3 ms
OR NOT
20.6 / 24.1ms
14.7 ms
20.6 / 24.1ms
14.7 ms
123.1/119.6ms
20.3 ms
*
Execution time when data type is ON. For example, STR 000 takes 28.4 ms if point 000 is on.
**
Execution time when data type is OFF. For example, STR 000 takes 31.4 ms if point 000 is off. Instruction
Output Type Instructions
Stage
Executed
Not Executed
AND STR
25.9 ms
22.8 ms
OR STR
25.9 ms
22.8 ms
Instruction
Execute
Not Executed
OUT
20.6 ms
20.6 ms
SET OUT
24.3 ms
16.6 ms
SET
24.3 ms
16.6 ms
RST
24.3 ms
16.6 ms
SET OUT RST
33.8 ms
29.4 ms
Instruction
Execute
Not Executed
TMR
92.8 ms
50.9 ms
CNT
97.5 ms
46.3 ms
RST CNT
25.9 ms
16.6 ms
SR
75.9 +11.5ms x (# of shifts)
41.9 ms
**