Square D instruction bulletin 30598-148-01, dated April 1982, for the Class 8030 Type CRM-115 bus expander/driver and Type CRM-116 bus expander/terminator interface modules. The pair expands a SY/MAX Model 300 programmable controller to a second I/O rack assembly, and the bulletin gives ratings, compatible racks, application notes and installation steps.
- Device
- Bus expander/driver interface module for the Model 300 programmable controller p. 1
- Card set
- Works only as a pair: CRM-115 driver plus CRM-116 terminator p. 1
- I/O capacity
- Expanded system up to 128 I/O p. 1
- Slots
- CRM-115: register slot of the first I/O rack; CRM-116: CPU slot of the second p. 1, 2
- Current draw
- CRM-115: 300mA; CRM-116: 100mA, from the SY/MAX power supply p. 1
- Compatible racks
- CRM-115: CRK-210, CRK-300, DRK-300, GRK-110, GRK-210 p. 1
- Interconnect cable
- Ribbon cable permanently attached to the CRM-116, approximately 40"; no other cable needed p. 1
- Environment
- Ambient 0-60°C; humidity rating 0-95, non condensing p. 1
- Weight
- CRM-115: 0.7 lb./0.32 Kg.; CRM-116: 1.2 lb./0.54 Kg. p. 1
- Series D
- CRM-115 Series D and CRM-116 Series D needed to address the register slot in the second rack p. 1
- Bulletin
- 30598-148-01, April 1982 p. 1
What this sheet walks you through
- Plugging the modules into the register and CPU slots p. 1, 2
- Connecting and removing the interconnect cable p. 2
- Routing the cable between the racks p. 2
Good to know
- Remove power from the processor before connecting or disconnecting the cable. p. 2
- The cable plug and socket are keyed; do not force the connection. p. 2
- Factory keys in the register slot admit only the driver module; do not remove them. p. 1
- Route the CRM-116 cable away from AC power wires, AC and DC signal wires and SY/MAX power supply cables to limit noise pick-up. p. 1
Questions this sheet answers
What does the Square D 8030 CRM-115 do?
It is the driver half of a bus expander pair with the CRM-116, used to expand a Model 300 programmable controller to a second I/O rack, up to 128 I/O. p. 1
Which slot does the CRM-115 plug into?
The register slot of the first I/O rack assembly; the CRM-116 goes in the CPU slot of the second. p. 2
Do I need a separate cable for the CRM-115 and CRM-116?
No. The ribbon cable is a permanently attached part of the CRM-116 module. p. 1
Which racks does the CRM-115 work with?
CRK-210, CRK-300, DRK-300, GRK-110 and GRK-210 racks. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, read from a scan by OCR; it may hold reading errors
© [D) Instruction Bulletin
Bulletin: 30598-148-01 Page: 1 of 2
Date: April, 1982
subject: SEY INIAR *
CLASS 8030 TYPE CRM-115
BUS EXPANDER/DRIVER INTERFACE MODULE
TYPE CRM-116 BUS EXPANDER/ TERMINATOR INTERFACE MODULE
DESCRIPTION
The Class 8030 Type CRM-115 and CRM-116 Bus kxpan-der Interface Modules ure used to expand 2 Model 300 Programmuble Controller System from one to tre YO Rack Assemblies increasing the I/O capacity of the system up lo the maximum of 128. The two modules operate as i two card set. The Type CRM-J15 is the driver module and the Type CRM-116 ts the terminator module. The ribbon cable used to connect the wo modules is a permanenuy at-tached part of the Type CRM-1)6 Terminator Interface Module. No additional cable is required.
SPECIFICATIONS
Rated Module Current Draw
On SY/MAX Power Supply... CRM-1145.......... 300mA CRM-116........ . 100mA
Ambient Temperature
Rating. 0.2.0.2... -0000 2 eee 0-60°C
Humidy Rating ..........-. 0-95, non condensing
Weight {unpackuged)....... CRM-1135... 0.7 Ih./0.32 Ke.
CRM-116.... 1.2 1b./0.54 Kg. Modules Plug Inte These Slots 20 ee eee CRM-1}5..... Register Slot CRM-l]6.......- CPL Slot Modules Can Be Used With These Racks. ......... CRM-115: CRK-210 CRK-300 DRK-250 DRK-300 GRK-110 GRK-210 CRM-116: CRK-100 CRK-200 CRK-210 CRK-300 DRK-21) IRK-300 GRK-110 GRK-710
CRM-116 Module Cable Length ..............--.-- Approximately 40" (02emt
£Square D Company, 1982
NEW LISTING AURPrinted in 1° 5.4.GQUARED
tAPPLICATION CONSIDERATIONS
® The cegisier slot (Type CRK-210, 300. Type DRK-210, 300 and Type GRK-110 und 210) contains facteurs installed keys wlowing only the Type CRM-114 Driver Interface Mudule to be Inserted. Do net remave these keys.
® Both the Type CRM-t15 and CRM-116 Modules are required ta complete the V/O rack assembly expansion.
® To mimmize electrical noise pick-up. the CRM-116 module cable shold be routed away fram: |. AC power wires. 2, AC and DC signal wires. and 3. S¥Y/MAX power supply cables.
@® Recommended maximum sverucal dimaunee between
- HO rack assemblies is
- Type CRK Racks: [8 inches (46 em). Type DRK and GRK Racks. ES inches (38 em)
@ The CRM-115 II Bus Expander may only be used to connect nee 4 function digital | O racks together.
® A Type CRM-115 Series Dand CR M-116 Series D must be used to address the register slot in the second rack assembly.
INSTALLATION INSTRUCTIONS
The Type CRM-E1S mndule phigs into the register slot of the first 1/0 rack assembly. The Pype CRM-116 module plugs inta the CFM sie of the sccomd (40 rack assembly.
tMinor Rev. 5/84
Page2of 2
Open in the PDF
The text of page 2, read from a scan by OCR; it may hold reading errors
Page 2 30598-148-01
When plugging in the modules, make sure they are firmly seated against the upper edge ball stud. Then, secure each module to it's rack with the captive screw. See Figure }| and 2.
After installing the module, the cable from the Type CRM-I16 Terminator Interface Module must be connected to the Type CRM-1I15 Driver Interface Module. When at-laching the cable, make sure it is inserted far enough into the socket on the front of the CRM-115 Driver Interface Module so that the socket retainers clamp over the plug. See figure 3. To remove the cable from the socket, first pull the socket retainers away from the cable, then pull the cable plug out.
CLASS-8030 TYPE CRM-II5
BUS EXPANDER / DRIVER, MODULE { PLUGGED INTO REGISTER SLOT }
cP SLOT REGISTEA SLOT @ 1/0 MOQULE SLOTS \ 4. I, LY \ ~ ~ yyy’ POWER SUPPLY CONNECTOR
Figure 1, Register/CPU Slot Locations
a CLASS - 8020 S¥/MAX MODEL 300 PROCESSOR ( PLUGGED INTO CPU SLOT)
A~---4,POWER |SUPPLY CONNECTORr/o YGDULES| FIELD WIRINGI/O RACK ASSEMBLY
CLASS - - 8030 TYPE CRM-lI6 BUS EXPANDER / TERMINATOR MODULE, INCLUDES CABLE U ( PLUGGED INTO CPU SLOT }
POAI/O RACK ASSEMBLYr i 1/o MODULESFIELD WIRING TERMINALSSECTION "A-A
Figure 2 - Two |/0 Rack System
INTERFACE = saouse~eo8
MODULE SOCKET Figure 3, Cable Insertion
NOTE: The cable plug and socket are mechanically keyed to prevent incorrect insertion. This polarity must
R. A. Auger
be observed. Do not attempt to force a connec-tion, Power must be removed from the processor before connecting or disconnecting the cable.
Recommended cable routing is to fold the cable over to the right side of the Type CRM-116 module. Then 90° fold the cable and route it up between the CRM-116 and the first I/O module in that I/O rack assembly. Route the cable up between the CRM-115 and the Mode! 300 proces-sor. Now 90° fold the cable up to the connector on the CRM-115 module. Any cable slack should be taken up by “S" bundling and securing with a wire tie. See Figure 2