Spec sheet · Schneider
Schneider 8030-HIM-151 and Square D 8030-HIM-151 Spec Sheet
Spec sheet3 pagesPDF 170 KB
All 3 pages are below, each with its text.
Covers · 2 models
The models it covers
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Square D's 1984 instruction bulletin (30598-188-01) for the SY/MAX Class 8030 Type HIM-151, an 8-function TTL input module. It gives the module's specifications, typical wiring, application considerations, keying and installation steps. The text comes from a scan, so some words and figures are garbled.
- Device
- SY/MAX input module with 8 optically isolated inputs for TTL or other 5VDC level devices p. 1
- External power
- Needs an external 5VDC source: user supplied, or a Class 8030 Type PS power supply with a Type CC-40 cable p. 1
- User supply
- 200mA max, 100mV (p-p) ripple max p. 1
- Input groups
- Inputs 1 to 4 share terminals 1A and 1B; inputs 5 to 8 share 2A and 2B; each group can take a separate supply p. 1, 2
- Input voltage
- Logic 0: 0.0V to 0.8V; logic 1: 2.0V to 8.0V p. 1
- Isolation
- Optical, 2500V RMS between input terminal and logic p. 1
- Current level
- DIP switches on the module bottom set each input to 10.0mA (ON) or a lower level (OFF) p. 2
- Minimum pulse width
- 1.67 millisecond at 300 Hz; 1.00 millisecond at 500 Hz p. 1
- Current draw
- 32mA per module from the SY/MAX power supply p. 1
- Environment
- 0 - 60°C ambient; 0 - 95% humidity, non-condensing p. 1
- Racks
- Racks listed include HRK-100 and HRK-200 p. 1
- Compatible outputs
- COM-261, COM-271, COM-281, HOM-261, HOM-271 output modules p. 1
- Accessories
- Detachable terminal blocks CBP-110; ten terminal labels CBP-109; keying pin kit Class 8030 Type CBP-104 p. 1, 2
- Wiring
- Shielded twisted pair such as Beldon No. 8760; up to two #14 AWG wires per terminal p. 2
What this sheet walks you through
- Wiring inputs and external supplies to the terminal block p. 1, 2
- Placing terminal labels for odd and even slots p. 2
- Grounding the input commons and cable shields p. 2
- Keying the rack socket for the module p. 2
- Setting the current DIP switches and inserting the module p. 2, 3
- Replacing the module without disturbing field wiring p. 2
Good to know
- A Type PS supply used as the TTL I/O power supply may be used only for that purpose, with no other cables connected. p. 1
- Wire polarity at the A (+) and B terminals must be as shown, or the module will be damaged. p. 2
- Maximum cable length is 50 feet at the 10.0mA level and 10 feet at the lower level. p. 2
- The SY/MAX processor may need a wider input pulse than the module minimum, depending on scan time. p. 2
- When handling keying pins, avoid touching the connector contact fingers. p. 2
Questions this sheet answers
What power does the Square D HIM-151 need?
An external 5VDC source, either user supplied or a Class 8030 Type PS power supply with a Type CC-40 cable. p. 1
How many inputs does the 8030-HIM-151 have?
Eight optically isolated TTL inputs, in two groups of four with their own common terminals. p. 1, 2
What is the maximum cable length for the HIM-151 TTL inputs?
50 feet with the 10.0mA level selected and 10 feet with the lower level, using shielded twisted pair such as Beldon No. 8760. p. 2
Where does the keying pin go for the HIM-151?
Between pins 12 and 14 of the rack socket, using the Class 8030 Type CBP-104 keying pin kit. p. 2
The file
Size and text
Every page · 3
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 3
Open in the PDF
The text of page 1, read from a scan by OCR; it may hold reading errors
Instruction Bulletin
Bulletin: 30598-188-01 Page: 1 of 3
Date: February, 1984
Subject: SWIMNAH °
CLASS 8030 TYPE HIM-151 8 FUNCTION TTL INPUT MODULE
Note: This module requires an external 5VDC power source. This can be either a user supplied 5VDC source or a SY/MAX Class 8030 Type PS Power Supply with a Class 8030 Type CC-40 Cable. When used as a TTL VO Power Supply, the Class 8030 Type PS Power Supply may only be used for that purpose. To maintain electrical isolation, no other cables may be connected to the power supply. See Power Supply Instruction Bulletin (30598- 156-02).
DESCRIPTION
The Type HIM-151 TTL Input Module provides 8 optically isolated inputs which are capable of receiving signals from TTL (transistor transistor logic) or other 5VDC level devices. Through the use of DIP switches located on the bottom of the module, the user has the option of selecting 1.0mA or 10.0mA current levels. The module also features both capaci-tive noise filtering and built-in hysteresis to ensure greater input signal integrity.
Eight LEDs on the face of the module provide status indica-tion for the individual inputs. LED illumination indicates a logic | input voltage.
SPECIFICATIONS
Inputs per Module Type and Rated Isolation
Between Input Terminal and
Logic ...........0 0.0 Optical: 2500V RMS User Information:
PARAMETERS LOGIC 0 LOGIC 1 Signal Low High Input Voltage 0.0V min. to 2.0V min. to 0.8V max. 8.0V max. LED Operation | OFF ON Status Seen by Processor OFF ON User Current Sink Req. -1.6mA max., _ - (per input) | (DIP switch OFF)* -10.0mA, _ (DIP switch ON)* User Current Source Req., _ - 3.0mA max. (per input) (DIP switch OFF)#, 10.0mA max. (DIP switch ON)= User Supply SVDC (+ 0.25V) at 200mA Voltage Req. max. 100mV (p-p) ripple max.
*At 0.0V with User Supply Voltage at 5.25V
tAt 8.0V with User Supply Voltage at 4.75V.
fe] cm je] e
Cm jo Ca
Input Module Switching Characteristics:
5V User Input Signal OV | Sonal to. ON Turn-On Turn-Off Processor OFF_Delay} [ew Delay
0.22 millisecond 0.50 millisecond
4, Turn-On Delay and Turn-Off Delay Values are based on Input Voltage Levels indicated in the Diagram.
Typical Turn-On Delay A Typical Turn-Off Delay A
Minimum Input Pulse width=] 1.67 millisecond at 300 Hz 1.00 millisecond at 500 Hz
Rated Module Current Draw on SY/MAX Power Supply ....32mA per Module Ambient Temperature Rating 0 - 60°C
Humidity Rating .......... 0 - 95% non-condensing
Weight ..............000. 1.2 1b/0.54 kg.
Rack Assemblies in Which
Module May be Used ...... HRK-100, HRK-1507, HRK-200
Compatibility with Output Modules ..............02. COM-261, COM-271, COM-281, HOM-261, HOM-271
Detachable Terminal Blocks CBP-110 Ten Terminal Labels CBP-109
TYPICAL WIRING
Input devices are wire’ movable terminal block on the front of the module} Figure | jillustrates the typical wiring for the first four inputs © HIM-151 TTL Input Module.
Wiring terminals | through 4 share common **1A”’ and ‘1B’? terminals. Wiring terminals 5 through 8 share common
© Square D Company, 1984 c Q D + Added July, 1986 GQUARE
NEW LISTING RG Printed in U.S.A.
Page2of 3
Open in the PDF
The text of page 2, read from a scan by OCR; it may hold reading errors
Page 2. 30598-188-01
terminals *‘2A’’ and “*2B’’. Each group of four inputs on the module is capable of being connected to a separate voltage supply. If only one voltage supply is used for more than one module, the *‘1B’’ and ‘*2B’’ terminals for each terminal block may be connected together and *‘1A”* and **2A”’ termi-nals of each terminal block may be connected together.
4
Suc. 5V.0.C. 14 14 | EXTERNAL
POWER = Icl 102 | LSUPPLY 7) 1B “45 J
+ COM u us | O |ia SHIELD > 4 EXTERNAL tcl 1 > SSOS008S< \ LOGIC |
Figure 1, Typical Wiring
A hinged plastic flap covers the wiring terminals on the front of [Fiewe2} Labels are provided for both sides of the flap. Seq Figure 2] The label with eight marking areas is placed on the outside of the flap to identify I/O devices, wire numbers, ctc. Two wiring terminal labels are included with the modulc. One is for terminals | through 8, the other for terminals 9 through 16. If the module is inserted in an ODD number slot, the terminal | through 8 label is placed on the inside of the
flap. If the module is placed in an EVEN number slot, use the terminals 9 through !6 label. Seq Figure 3.
FLAP CLOSED FLAP OPEN, 7
a CPU SLOT f TERMINAL LABEL REGISTER SLOT- TYPE HRK PLACED ON l
INSIDE OF errs |
FLAP, = 1/0 MOQULE SLOTS
| 2a f 7
1,3,5,7 USE TERMINAL LABEL 1-8 2,4,6,8 USE TERMINAL LABEL 9-16
rpzpsyers
;
BLANK MARKING LABEL PLACED ON OUTSIDE OF FLAP
Figure 2 /O Terminal Labels
Figure 3 Terminal Label Placement
APPLICATION CONSIDERATIONS
@ External power supply connections to terminals **]A’’ and ‘*1B’’ will power inputs 1-4. Terminals ‘*2A”’ and *'2B”’ will power inputs 5-8. If one supply is to be used, *‘1A”’ and ‘‘2A’’, ‘1B’ and ‘*2B’’ terminals can be wired to-gether.
© By removing the top and bottom retaining screws the termi-nal block may be removed from the module, allowing the module to be replaced without disturbing field wiring.
@ The polarity of the wires connected to the terminals **A”’ (+) and ‘*B”’ ( - ) must be as indicated or damage to the Module will occur|(Figure 1)
® Only shielded twisted pair cable. such as Beldon No. 8760, should be used when connecting the TTL input module to an external device. With the 1.6mA current level selected. the maximum cable length is 10 feet. With the 10.0mA current level selected, the maximum cable length is 50 feet.
e Each terminal will accept up to two #14 AWG wires.
@ The input common terminal ‘*!B’’ and **2B’’ on the mod-ule should be connected to the rack chassis ground to mini-mize noise susceptibility. Each individual cable shield must also be connected to the common terminals *‘B’’ on the module. The other end of the shield must be left uncon-nected] (Figure 1)
@ If an output of a TTL output module is connected to the input of a TTL input module, the cable shields should be connected to the B terminals, (common) on the output module. The other end of the shield must be left unconnected.
© Although thd input pulse width given in the ‘‘SPECIFICA- TIONS”? is the mimimum required by the HIM-151 TTL Input Module. the SY/MAX Processor (depending on the processor scan time) may require a greater input pulse width. Consult the SY/MAX PC Planning and Installation Guide (Bulletin #30598-175-01) for I/O update consider-ations.
@ Depending on the size and routing of wiring to the termi-nals of adjacent modules, it may be necessary to remove an adjacent terminal strip before removing an I/O module.
MODULE KEYING Each socket on the I/O rack assembly may be keyed to accept
only one type of module. An optional keying pin kit, Class 8030 Type CBP-104, is available for this purpose. The cor-
rect position of the keying pin TL input module is between pins 12 and 14. See Figure Hl The keying pin is simply insert ly into the slot in the rack connector, as shown inj Figure cI using the keying pin insertion tool provided with the kit
KEYING PIN, - - _ KEYING PIN a= LOCATION, - - \ 12 14
Figure 5 Inserting Keying Pin
Figure 4 Keying Pin Location
CAUTION: When inserting or removing the keying pins, use care to avoid touching the contact fingers within the connector. Improper insertion/removal may damage the connector.
INSTALLATION INSTRUCTIONS
Insert the key mentioned above into the appropriate slot then, before inserting the module in the rack, set the DIP switches to select the 1.6mA or 10.0mA current level for each individ-ual input. The DIP switches are accessible on the bottom of the module. Simply set the switch in the ‘‘ON”’ position (towards the PC board) to select 10.0mA current level or set the switch in the “‘OFF’’ position to select 1.6ma current
Page3of 3
Open in the PDF
The text of page 3, read from a scan by OCR; it may hold reading errors
Page 3 30598-188-01
level] (Figure 6)} After setting the DIP switches to the desired SIMPLIFIED SCHEMATIC OF MODULE position, imsert the module into the rack slot (holding the
module’s pull tab in a horizontal position as the module is | Figure 7|illustrates one of eight circuits within the module. inserted) and tighten the captive screw at the bottom of the The terminals marked ‘1 A”’ and **1B”’ are common to the module. Lower the latching clamp to secure the top of the first four inputs within the module.
module.
NOTE: The switch labeled ‘‘S1’’, when closed, selects 1LGMA 10.0mA current level.
OFF . + @ _ NOTED _ ON Va 1IOMA To OTHER © | 2 3 4 5 6 7 8 ;
3 INPUTS CIRCUIT soaro_/”
620JINPUT LOGICMODULE TERMINALSDOAPCTOM- CATO
A30609-066 Figure 6, Module DIP Switches “O74 * TO OTHER 3 INPUTS
Figure 7, Simplified Schematic of One Input Module Circuit
E. G. Charland