Square D's July 1995 instruction bulletin (30598-193-02B1) for the SY/MAX Class 8030 Type HOM221, an 8-function 120 VAC output module. It gives specifications, typical wiring, application considerations, fuse replacement, keying and installation. The text comes from a scan; the bulletin counts four pages, but this copy has three.
- Device
- SY/MAX output module with 8 optically isolated outputs for loads such as motor starters, solenoids or pilot lights p. 1
- Voltage range
- 50-138V, 50/60 Hz p. 1
- Isolation
- Optical, 2500 V rms p. 1
- Commons
- One common per group of 4 outputs (2 per module): outputs 1-4 on 1A, 5-8 on 2A p. 1, 2
- Fuses
- Each output fused, AGC-3, 3A, 250V; reached through openings in the module side p. 1, 2
- Indicators
- Red LED per output; two neon lamps, one per group of 4 outputs, show a blown fuse p. 1
- Off-state leakage
- 2.0 mA max at 138 V, 50/60 Hz p. 1
- Surge current
- 25 A for one cycle (60 Hz), no more than one per second p. 1
- Switching times
- Turn on less than .1 ms at 120V; turn off 8.3 ms max at 60 Hz, 10 ms max at 50 Hz p. 1
- Current draw
- 225 mA at 75% duty cycle, 270 mA at 100% duty cycle, from the SY/MAX power supply p. 1
- Environment
- 0-60°C ambient; 0-95% humidity, non-condensing p. 1
- Racks
- HRK100, HRK150, HRK200 p. 1
- Compatible inputs
- HIM101, CIM101, DIM101 input modules p. 1
- Keying
- Keying pin kit Class 8030 Type CBP104; pin between pins 20 and 22 p. 3
What this sheet walks you through
- Wiring output devices and the blown fuse indicator supply p. 1, 2
- Replacing an output fuse p. 2
- Keying the rack connector for the module p. 3
- Inserting and latching the module in the rack p. 3
Good to know
- The module has internal noise suppression; added suppression may turn outputs on for half a cycle at power-up. p. 2
- Below 90 VAC the blown fuse indicator lamp does not work. p. 2
- No minimum load current is needed, but the leakage current must not be enough to turn on the load. p. 2
- Voltage can be present at the terminal block even when the module is unpowered. p. 2
Questions this sheet answers
What fuse does the Square D HOM221 use?
Each output has its own AGC-3, 3A, 250V fuse; the bulletin says lower-rated fuses may be fitted to suit the output devices. p. 1, 2
What voltage can the 8030-HOM-221 switch?
50 to 138 V AC at 50/60 Hz. p. 1
How do I replace a fuse in the HOM221 output module?
Halt the processor or remove rack power, remove terminal block power, pull the module, pry out the fuse, press the new one in by its metal part, then reinstall. p. 2
Why does the HOM221 blown fuse lamp not light?
The lamp does not work below 90 VAC, and the B terminals must be wired to L2 to power it. p. 1, 2
Which racks take the HOM221 module?
HRK100, HRK150 and HRK200 rack assemblies. p. 1
The file
Size and text
Every page · 3
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 3
Open in the PDF
The text of page 1, read from a scan by OCR; it may hold reading errors
Instruction Bulletin
Bulletin: 30598-193-02B1 Page: | of 4 Date: July, 1995
sujecs SYVMNAH
CLASS 8030 TYPE HOM221
8 FUNCTION 120 VAC OUTPUT MODULE
DESCRIPTION
The Type HOM221 120 VAC Output Module contains 8 optically isolated outputs, each capable of driving loads such as motor starters, solenoids, or pilot lights.
A red LED indicator on the front of the module for each output illuminates when the processor issues a command to energize that output. Two neon lamps on the front of the module, one for each group of 4 outputs, illuminate when a blown fuse is detected. A marking area is provided next to each LED for output identification.
SPECIFICATIONS Outputs per module ..... 8 Type of isolation ....... optical Isolation rating......... 2500 V rms Voltage range.......... 50-138V 50/60 Hz Maximum current ...... 1A per output, 8 A per module Minimum load current.....Jsee “Application Considerations” Maximum On state voltage drop across output 2.0 V at 2 A load Maximum Off state leakage current......... 2.0 mA at 138 V, 50/60 Hz
Maximum surge current. . 25 A for one cycle (60 Hz), no more than one per second
Turn on time........... less than .1 ms at 120V
Turn off time .......... 8.3 ms max. at 60 Hz, 10 ms max. at 50 Hz
FUSe cee eee eee AGC-3, 3A, 250V
LED operation......... Red LED illuminated when receiving “ON” signal from processor
Rated module current draw on SY/MAX power
supply...........0000, 225 mA per module at 75% duty cycle 270 mA per module at 100% duty cycle
Ambient temperature
ratiNg . 6... eee eee 0-60°C
Humidity rating ........ 0-95% non-condensing
Replaces 30598- 193-02, dated 6/87
© 1995 Square D All Rights Reserved
Weight (unpackaged)... . 1.8 lb/.806 kg
Rack assemblies in which module may be used..... HRK100, HRK150, HRK200
Compatibility with input modules.......... HIM101, CIM101, DIM101
TYPICAL WIRING
ELECTRICAL SHOCK OR BURN HAZARD
There is danger of electrical shock or burn when coming in contact with terminal strip or field wiring. Always turn off power supplying this equipment before servicing this module.
Failure to observe this precaution will result in death, severe personal injury, or equipment damage.
Output devices are wired to the terminal block on the front of the module.| Figure 1 on the next page illustrates the typical wiring for the Type HOM221 Output Module.
Wiring terminals 1-4 share a common “1A” terminal. Wiring terminals 5-8 share common terminal “2A.” Likewise, wiring terminals 9-16 share common terminals “3A” and “4A.” The “B” terminals are wired directly to L2 to provide the power required for the blown fuse indicators.
Page2of 3
Open in the PDF
The text of page 2, read from a scan by OCR; it may hold reading errors
Page 2
30598-193
L1 TYPEHOMMODULE 2 TERMINAL BLOCK
1 BQ | frat 1O+-@ - } 20+} 3@+-“~- - “4+ 40+ BO. mi 7X0) £2+-O@ - cot 70+-@ - Figure 1: Typical wiring
A hinged plastic flap covers the wiring terminals on the front
of th (se
module. Labels are provided for both sides of this flap Figure 2). Place the label with 8 marking areas on the
outside of the flap to identify I/O devices, wire numbers, etc.
Two One
wiring terminal labels are included with the module. is for terminals 1-8, the other for terminals 9-16. If the
module is inserted in an ODD numbered slot, place the label
for t
erminals 1-8 on the inside of the flap. If the module is
placed in an EVE ered slot, use the label for terminals 9-16. See|Figure 3
FLAP CLOSEDBLANKFLAP OPEN
REGISTER SLOT CPU SLOT TERMINAL LABEL PLACED ON INStOE OF FLAP
TYPE HRK
1]2]3] 4] 5/6] 7)8
I FTI PET UT TT Tt rT Te
“i - q - VO MODULE SLOTS 1,3,5,7 USE TERMINAL LABEL 1-8 2,4,6,8 USE TERMINAL LABEL 9-16
J
MARKING
LABEL PLACED ON OUTSIDE OF FLAP
Figure 3: Terminal label placement
Figure 2: I/O terminal labels
APPLICATION CONSIDERATIONS
The Type HOM221 Output Module has one common for each set of 4 outputs (2 commons per module).
The maximum current rating of each output is 2 A. Total module output current rating is 12 A from 0-50°C and 10 A from 50-60°C.
The Type HOM221 Output Module has internal transient noise suppression. It may be wired in series or parallel with hard contact switches to control an inductive load (such as a motor starter or a solenoid). Do not install additional noise suppression. Additional suppression may cause outputs to turn ON for 1/2 cycle when AC power is applied.
Depending on the size and routing of wire to the terminals, it may be necessary to remove an adjacent terminal strip before removing an I/O module.
ui L2
When using the output module below 90 VAC, the blown fuse indicator lamp will not operate.
Although the output module does not require a minimum load current, be sure the maximum leakage
current (given in the} specifications|on page 1) will not turn on the load. Contact Square D Company for
application assistance.
Each of the 8 output circuits is individually fused. Each fuse is rated at 3 A. Lower-rated fuses may be installed, depending on the output devices being controlled. Fuses are accessible through openings in the side of the module. To replace fuses, use the following procedure: 1. Turn the processor keyswitch to “HALT” or “DISABLE OUTPUTS,’ or remove power from the power supply feeding the rack assembly. See Figure 4.
2. Because voltage can be present at the terminal block on the module even when the module is unpowered, all power to the terminal block should also be removed to avoid electrical shock.
3. Remove the output module from the rack assembly by loosening the module mounting screw and pulling the module from the rack assembly.
4. Use a fuse puller or small screwdriver to pry up one end of the fuse, being careful not ta damag the printed circuit board underneath. Se¢ Figure 5.
5. Position the replacement fuse on a fuse clip and push into place with the screwdriver, Push on the metal, not the glass, portion of the fuse.
6. Reinstall the output module in the rack assembly and tighten the mounting screws. Lock the latching clamp over the top of the module.
7. Turn the processor keyswitch to “RUN” or reapply power to the power supply. Also reapply power to the module terminal block
[ooPOWER SUPPLY 3Tt ~N
OPEN DISCONNECT BEFORE REMOVING sists OUTPUT MODULE ote leleole
VO RACK ASSEMBLY
Figure 4: Removing power from the power supply
Page3of 3
Open in the PDF
The text of page 3, read from a scan by OCR; it may hold reading errors
Figure 5: Fuse removal MODULE KEYING
Each connector on the I/O module slots may be keyed to prevent the insertion of other module types. A keying pin kit, Class 8030 Type CBP104, is available for this purpose. The correct position of the keying pin for the Type HOM221 Output Module is between pins 20 and 22 (see Figure 6). The keying pin is simply inserted manually into the appropriate slot in the rack connector using the keying pin insertion tool provided with the kit. See|Figure 7|
Note: Keying may be the same or different for other output module types.
KEYING PIN
KEYINGPIN L - JL_ J] 4
LOCATION 18 \E = - - S
Figure 7: Keying pin insertion
Figure 6: Keying pin location
30598-193 Page 3
/\, CAUTION
EQUIPMENT DAMAGE HAZARD
To prevent possible equipment damage, use care to avoid touching the contact fingers within the connector when inserting or removing the keying pins. Improper insertion/ removal may damage the connector.
Failure to observe this precaution can result in equipment damage.
INSTALLATION INSTRUCTIONS
Insert the output module into the rack (holding the pull tab of the module in a horizontal position as the module is inserted) and tighten the captive screw at the bottom of the module. Lower the latching clamp to secure the top of the module.
SIMPLIFIED SCHEMATIC
illustrates one of the 8 circuits within the Type HO
M221 Output Module. The terminals marked “1A” and “1B” are common to output terminals 1-4.
BLOWN 1B) FUSE ciRcUIT
TO OTHER LoJ 3 OUTPUTS
FUSE e) AW , +1} (A) TRIAC R MOV
OUTPUT | OPTICAL TO OTHER LOGIC |ISOLATOR: 3 OUTPUTS,
I | T (4) ourpur
Figure 8: Simplified schematic of one output circuit