Manual · Schneider
Schneider 8030-RIM-101 and Square D 8030-RIM-101 Manual
Manual3 pagesPDF 197 KB
All 3 pages are below, each with its text.
Covers · 2 models
The models it covers
From the manual · read page by page
Key facts from this manual
Much of this manual is scanned with little readable text, so this says only what its text supports. Each line names its page in the PDF.
Square D instruction bulletin 30598-282-01C1 (September 1989) for the SY/MAX Class 8030 Type RIM-101, a 16-input 120 VAC/DC input module for register slots of SY/MAX rack assemblies. It gives the specifications, typical wiring, application notes, module keying, installation in a rack and how many registers the module takes. The pages are scans read by OCR, so some figure text is garbled.
- What it is
- 16-input 120 VAC/DC input module, optically isolated, for SY/MAX register racks p. 1
- Voltage range
- 90-138VAC at 50/60 Hz, or VDC of either polarity p. 1, 2
- Turn-on and turn-off
- On at 90V RMS and 6mA; off at 30V RMS p. 1
- Isolation
- Optical, 2500V RMS; four groups of four inputs, each group isolated p. 1, 2
- Power supply draw
- 275 mA per module at 75% duty cycle, 300 mA at 100% p. 1
- Input impedance
- 14.4K ohms resistive p. 1
- Rack assemblies
- Any register slot of a Class 8030 CRK, DRK, GRK, HRK or RRK rack p. 3
- Commons
- Terminals 1-4 on 1A, 5-8 on 2A, 9-12 on 3A, 13-16 on 4A; B terminals unused p. 1
- Wire size
- Two #14 gauge wires per terminal p. 2
- Indicators
- One red LED per input p. 1
- Keying pin kit
- Class 8030 Type CBP-104, optional p. 2
- Register usage
- One register; four assigned (one used) right of a Model 500 or 700 processor p. 3
What this manual walks you through
- Wiring field input devices to the terminal block p. 1, 2
- Adding surge suppression for inductive loads in parallel p. 2
- Keying a register slot for the module p. 2, 3
- Installing and removing the module in a rack p. 3
- Assigning registers with Model 300, 500 and 700 processors p. 3
Good to know
- Not for slot 1 of a register rack, slots 17 and 18 of an RRK-300, or the register slot of a digital rack. p. 1
- If a field device leaks more than 2mA in the off state, the bulletin says to consult the factory. p. 2
- High-leakage solid-state input devices may make an LED glow while the input is off. p. 2
- In the processor's own rack, only Model 300, 400 and 600 processors can force these inputs. p. 2
- Remove power from the rack before installing or removing the module. p. 3
Questions this manual answers
What voltage does the Square D RIM-101 accept?
90-138VAC at 50/60 Hz, or DC in that range with either polarity. p. 1, 2
How many inputs does the 8030 RIM-101 have?
Sixteen optically isolated inputs in four groups of four, each with its own common. p. 1, 2
Can the RIM-101 go in slot 17 of an RRK-300?
No. Slots 17 and 18 of an RRK-300 are not addressable by any SY/MAX processor. p. 3
How much power does the RIM-101 draw from the SY/MAX supply?
275 mA at 75% duty cycle and 300 mA at 100% duty cycle. p. 1
The file
Size and text
Every page · 3
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 3
Open in the PDF
The text of page 1, read from a scan by OCR; it may hold reading errors
Instruction Bulletin
Bulletin: 30598-282-01C1
Date: September, 1989
SWINAH'
CLASS 8030 TYPE RIM-101 16 FUNCTION 120 VAC/DC INPUT MODULE
DESCRIPTION
The Type RIM-101 120VAC/DC Input Module contains 16 optically isolated inputs which are capable of handling signals from such field input devices as limit switches, push buttons, and selector switches. The module may be inserted into any slot of a register rack except slot 1 (or slots 17 and 18 of an RRK-300) or the register slot of a digital rack.
Each of the sixteen inputs has a red LED on the front of the module which illuminates when receiving an “ON” signal from the field input device (proper voltage applied to the wiring terminal).
A marking label that fits over the wiring terminals is provided to identify input devices.
SPECIFICATIONS
Inputs per Module ......... 16
Type ofisolation .......... Optical Isolation rating ........... 2500V RMS
- Voltage Characteristics
- Voltage Range ............ 90-138VAC at 50/60 Hz. or VDC Must-turn-on Voltage ..... 90V RMS Must-turn-off Voltage ..... 30V RMS Current Characteristics: Inputcurrentdraw ........ 6mAat 90V and 10mA at 138V Must-turn-on Current ..... 6mA (at 90V) Must-turn-off Current ..... 2.0mA (at 25 V) Rated current draw on SY/MAX Power Supply .... 275 mA per module at 75% Duty Cycle 300 mA per module at 100% Duty Cycle
Input Impedance .......... 14.4K ohms resistive
TurnonTime ............. 8 msec. Nominal
TurnoffTime ............. 8 msec. Nominal
0 - 60°C 5 - 95% non-condensing 2.7 Ibs (1.22 kg.)
Class 8030 Type CBP-116
Ambient temperature Humidity rating ..........
Weight (unpackaged) Detachable Terminal Block
Used with these rack
assemblies ................ RRK-100, RRK-200, RRK-300, HRK-100, HRK-150, HRK-200, CRK-210, CRK-300, DRK-210, DRK-300, GRK-110, GRK-210
Compatible with Output
Modules .................. ROM-221
TYPICAL WIRING
Field input devices are wired ta the terminal block on the front of the input module. | Figure 1 jillustrates the typical wiring of the RIM-101 input module.
Wiring terminals 1 through 4 share common terminal “1A,” wiring terminals 5 through 8 share common terminal “2A.” Likewise, wiring terminals 9 through 12 and 13 through 16 share common terminals “3A” and “4A” respectively. The “B” terminals are not used on the input modules.
SQUARE D COMPANY
Dedicated to Growth . Committed to Quality
Copyright © 1988 Square D Company
Supersedes 30598-282-02, June, 1987 Printed in U.S.A.
Page2of 3
Open in the PDF
The text of page 2, read from a scan by OCR; it may hold reading errors
Page 2 30598-282
Note: Surge suppression is required only when an
inductive load is in parallel with a programmable controller input.
Type RIM L1 Module L2
Terminal Block rT sSs LL 1 4 * o so _~FO 2 3 ST___fFe 4 _ |e
ae
x “T - - ) o - - - - - To. 13 as 12 14 ose @ 15 ste @ 16 4a
inductive Load
Surge Suppressor
Figure 1 - Typical Wiring
APPLICATION CONSIDERATIONS
Each four inputs sharing a common “A” terminal are electrically isolated from the other group of four inputs on the module.
By removing the top and bottom retaining screws, the terminal block may be removed from the module, allowing the module to be replaced without disturbing field wiring.
In those applications where an inductive load such as a motor starter or solenoid is wired in parallel with a Type RIM-101 Input Modul ssor must be installed as indicated in|Figure i A typical suppressor for 120VAC operation consists of a 0.5
mfd. 400 volt capacitor with a 220 ohm resistor in series.
Note that an “appreciable glow” from the LED may be seen when high leakage current, solid-state input devices are used with a RIM-101, even though the input module is actually off. The must-turn-off voltages and currents are as listed in the specifications.
If the off-state leakage current of the field input device connected to the Type RIM-101 Input Module is greater than 2mA, consult the factory for recommended signal conditioning.
When using the Type RIM-101 Input Module with DC voltage inputs, either polarity may be used, for example: Terminal 1 (+) and Terminal 1A (~) or Terminal 1 (-) and Terminal 1A (+).
Each terminal will accommodate two #14 gauge wires.
Depending on the size and routing of wiring to the I/O terminals, it may be necessary to remove an adjacent terminal strip before removing an I/O module.
The LEDs will illuminate “ON” as long as specified input voltages are present at the input terminals, regardless of whether the RIM-101 is plugged into a rack assembly or power is applied to it.
When the Type RIM-101 Input Module is located in the same rack as the processor the only processors which will allow the inputs to be foreed ON and OFF are the Model 300, 400 and 600 processors. The Model 500 and 700 processors do not support the forcing function. Instead, they rely on the forcing capability in the Local Interface Module to provide this function. Therefore, when the input module is mounted in a remote rack the inputs may be forced ON and OFF by any processor.
When using the DISPLAY module of the Class 8010 Type SPR-2XX and SPR-3XX CRT Programmers or SY/MATE*, all contacts and coils associated with register slot mounted digital I/O modules will be shown with the prefix (R) in front of the address. These (R) designated contacts and coils are associated with actual inputs and outputs and should not be confused with contacts and coils associated with internal relays.
*Note: When using SYM-323 Series B and SYM-324
Series A or later, all contact and coils associated with digital I/O modules will be shown with the prefix (I) in format of the address if it is an input or (O) if it is an output or contact of an external output.
MODULE KEYING
Each register slot, whether on a digital or register rack, has two keying pins which are installed at the factory. These are located between slot 4 and 6. They insure only
register modules can be plugged into register slots.
Each register slot connector may be keyed to accept only one type of register module. An optional keying pin kit, Class 8030 Type CBP-104, is available for this purpose.
The keying pin is manuall using the keying pin inser keying pin location for the "
y inserted in tion tool (see
between pins 40 and 42 (seq
o the coFigure 2].nector The
-101 Input Module is Figure 3).
Page3of 3
Open in the PDF
The text of page 3, read from a scan by OCR; it may hold reading errors
CAUTION: When inserting or removing the keying pins, use care to avoid touching the contact fingers within the connector. Improper insertion or removal may damage the connector.
Keying Pin a Connector S/ an 35 | (=) 36 37 : 38 ; 39 40 Figure 2 41 . 42 Keying Pin Insertion 43 : 44 Keying Pin I x Location I r ENN Figure 3 Module Keying
INSTALLATION IN A RACK ASSEMBLY
The Type RIM-101 Input Module may be installed in any register slot of a Class 8030 Type CRK, DRK, GRK, HRK or RRK rack assembly. The module receives 5VDC power and ground from the edge connector at the back of the rack.
Power must be removed from the rack assembly before installing or removing the output module from the rack. After the removal of power, insert the module into the register slot until firmly seated against the stud (the middle post above the socket in that slot). Be sure to tighten the captive screw to insure the module is secured. To remove the module, loosen the captive screw and pull the module out of the slot using the finger tab located on the top of the module.
Refer to the Power Supply and Rack Instruction Bulletins to insure proper grounding.
- Note
- 30598-282 Page 3
REGISTER USAGE FOR RACK ADDRESSING
Each Type RIM-101 Input Module will occupy a single register in the system. When located in a register slot to the right of a Model 500 or Model 700 processor, the RIM- 101 must be assigned four registers even though only the first of the four registers is used. The remaining three registers cannot be used.
When mounted in the same rack as a Model 300 processor, a minimum of one register must be assigned to each RIM-101 Input Module. When the Model 300 processor is mounted in an RRK-200 register rack, slot 9 cannot be used for any digital I/O modules. Slot 9 cannot be addressed by the Model 300, therefore, it may be used to power any register module which requires only power and which does not require registers, such as the D-LOG or SY/NET modules.
Slots 17 and 18 on an RRK-300 (lower, right-most slots) are non-addressable by any SY/MAX processor, and therefore, the RIM-101 cannot be used in these slots.
SIMPLIFIED SCHEMATIC
| Figures 4 and Sillustrate one of the 16 circuits within the ype = nput Module. The terminal marked “1A”
is common to the first four inputs within the module., nn O - - - “~V--“V*-
N Tyo] & TT \ T
S R R L
16) @ - v - -v - - r | 8 Aly o | ¢
R
Figure 4 - Simplified Schematic of One Output Circuit
{Series A and B)
oO} y
p INPUT a T N O - V - _ o | P U T S «tofu comm, Z t 2 cy A/S T ¢
re)
R
Figure 5 - Simplified Schematic of One Output Circuit (Series C)