Product datasheet for the XS7C4A1MPN12, an OsiSense XS general purpose inductive proximity sensor in a 40 x 40 x 117 mm PBT body with a 5 position turret head and screw-clamp terminals. It lists the 15 mm nominal sensing distance, 2-wire programmable NO or NC output, 24 to 240 V AC/DC supply, switching and timing data, LEDs, IP ratings, temperatures, certifications, dimension drawings, minimum mounting distances and the wiring scheme.
Its parts
- Characteristics
- Dimensions Drawings
- Mounting and Clearance
- Connections and Schema
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Product datasheet (dated Mar 09, 2017) for the OsiSense XS XS7C4A1MPN12, a 40 x 40 x 117 mm plastic inductive proximity sensor with a 15 mm sensing distance and screw terminals. It lists electrical and environmental characteristics, dimensions, minimum mounting distances and the 2-wire wiring scheme.
- Device
- Inductive proximity sensor, XS7 form 40 x 40 x 117 mm, PBT plastic body, flush mountable p. 1
- Sensing distance
- Sn 15 mm nominal; operating zone 0...12 mm p. 1, 2
- Supply voltage
- 24...240 V DC or 24...240 V AC 50/60 Hz (limits 20...264 V AC/DC) p. 1, 2
- Output
- 2-wire AC/DC, 1 NO or 1 NC programmable p. 1
- Switching capacity
- 5...200 mA DC; 5...300 mA AC p. 1
- Connection
- Screw-clamp terminals, 4 x 1.5 mm²; 1 tapped entry for 1/2" NPT cable gland p. 1, 2
- Detection face
- 5 positions turret head p. 1
- Switching frequency
- Up to 25 Hz AC, 50 Hz DC p. 2
- Status LEDs
- Green for supply on, yellow for output state p. 2
- Leakage and drop
- Residual current up to 1.5 mA at 120 V or 0.6 mA at 24 V when open; voltage drop up to 5.5 V when closed p. 2
- Enclosure
- IP65 and IP67 (IEC 60529), IP69K (DIN 40050) p. 1
- Temperature
- Operation -25...70 °C; storage -40...85 °C p. 2
- Weight
- 0.244 kg p. 2
- Mounting distances
- Side by side 60 mm or more; face to face 120 mm or more; facing metal 45 mm or more p. 5
What this sheet walks you through
- Dimensions and mounting holes p. 3
- Spacing sensors side by side, face to face and near metal p. 5
- Wiring the 2-wire AC or DC output p. 6
Good to know
- Terminal screws (M3,5) should be tightened to less than 1.2 Nm, and the mounting holes to less than 1.5 Nm. p. 3
Questions this sheet answers
What is the sensing distance of the XS7C4A1MPN12?
15 mm nominal, with an operating zone of 0 to 12 mm. p. 1, 2
What voltage does the XS7C4A1MPN12 run on?
24 to 240 V DC or 24 to 240 V AC at 50/60 Hz. p. 1
Is the XS7C4A1MPN12 normally open or normally closed?
Either: the 2-wire output is programmable as 1 NO or 1 NC. p. 1