Page 41
(2) Signal specifications
Signal Symbol Function Specifications MP RDY 1 On across RDY 1 and RDY 2 when Motionpack is Read RDY 2 normal, servo error 1s not excessive and Servo- ~ 7 pack 1s not malfunctioning RDY1 = RDY2 Indicates that Motionpack and Servopack are in, - normal condition and ready to operate This | signal, when turned on trips the relay, shuts off the base of Servopack and the P-motion command Thus operation is ready Output capacity 24 VDC When this signal is turned off, perform base 100 mA max cutoff of the Servopack and initiate P-motion command Current flow direction at ON RDYI + RDY2 Condition of (RDY 1 - RDY 2) ON = {MP normal): (dEr Over} Speed REF Speed reference output of Motionpack Connect Voltage -9V to +9V this signal to the speed command input of t6V¥ output fi Reference | SCOI Servopack The plus command causes the motor at Error do = Pr42 to run in a forward direction Signal form is sawtooth waveform at 4 kHz REF reference value $G01 OV AT STOP APPROX ov ANA AA (4 200m APPROX 2504 $ Output IN MOTION APPROX WVNVL¢ [20007 SPEED APPROX 250m8 REFERENCE +Current +CL The positive signal of the current hmit command Voltage OV to +9V Limit SC02 output of Motionpack hmits current when the motor Outputs 4V im runs in reverse direction Connect to the¢ xter- at 100% current limit Reference nal current limit command input terminal of Servopack Type CPCR-MR, ,7 Cy. Waveform the same as for speed reference Note As the external current hmit command of + CL i Servopack, apply negative voltage (0 to -9V) signa to terminal for positive current and a posi- $G02 OV tive voltage (0 to 9V) to terminal for nega- tive current -Current -CL The negative signal of the current command output | Voltage OV to -9V Limit $C03 of Motionpack limits current when the motor runs Outputs -4V in forward direction at 100% current limit Reference
Connect to the external current hmit command Input terminal e) of Servopack Type CPCR-MR
La e
See the note of the + current limit reference above the same as for speed reference
Waveform
-CL signal
SG03 OV
35
Page 42
3 2 4 Servo-RELATED SIGNALS
(Cont'd)
Signal Symbol Function Specifications Without NODB The signal that permits Motionpack controller to According to the system config- DB Unit detect the presence or absence of the DB unit uration, determine whether to al connect the input terminal to 0V Without DB unit Connect OV or leave it open With DB unit Open Servo SAL This signal is 0V when the servo driver is ready (a) The input contact capacity E A to operate 1s rated at 30V and 20 mA or rror cross more Chattering time sfould Terminals SAL = 0, when, for example, Servopack 1s not exceed 5 msec CC and normal and the main circuit supply power 1s ON (ready for operation) (b) ON and OFF of input @ signal lasting for 35 msec or If this terminal is open, RDY1 to RDY2 (MP more is effective preparation end) does not turn ON [some man | 35ms MIN Current CL This signal indicates that Servopack The same as SAL CPCR-MR, 1,0, is limiting current Limit When CL=ON, Motionpack stops sending motion pulses It continues sending motion pulses during execution of G01 and G27 input ad 4 = Travel OTF Travel in forward direction 1s posstble when OTF The same as SAL In = ON The Motionpack stops in an emergency when both OTF and OTR are OFF Forward Let both OTF and OTR turn off in case of Direction power failure, servo failure, or MP failure See the sample application circuit shown in par 10 2 Travel OTR Travel in reverse direction is possible when ihe same as SAL OTR = ON in Reverse Direction
36
Page 43
3.2.5 PG SIGNALS (1)
Connections of detectors
Detectors (PG) to be combined with Motionpack should be Yaskawa produced
Connections are different depending on Type of detectors
(a) With 5V type PG roves
Feedback unit Type TFUE-,_,, .2D7
Transmission distance
25 m max
Motronpack CMPC ©CM33
Osv
(b) With 12V type PG
Feedback unit Type TFUE-(,. »Z207 Optical encoder Type UPOPI-7}SAC,
Transmission distance
10 m max
Motionpack CMPC CM 33
PG
SEE PG PULSE MULTIPLIER SETTING PROCEDURE BELOW
G) (NOTE) | a 1 CAt+ 1 PBI! ' Cc v T CA 2 OPB | te 1 D ca4l PAL 4 A T T CAS, OPA. 4Pa B 1 ~T CAB} PCI 4 ' R "4 1 1 CAS opc | fP. $ 7 CA111213L sve | H CA-181920[ Oo ' fps G H 1 ‘ I | - CA7 FG ‘So CA 14 CA 15 5 CA 16] CA 174 “For PG power of 5V and OV use three leads (a) With 5V Type PG
12V POWER t SUPPLY FOR PG [. (PREPARED BY USER '
Fig 3 15
PG
(NOTE) 9» .. CA 2J OPB if \ |JPHASE B a~ CA Ey PB? } P’ |PHASE BO CA-S OPA ( 1 IPHASE A CAG. PAZ ' P| [PHASE A 0 cag] OPC ( PHASE C CA 10L PC2 ! tp PHASE C 0 H . +12V iG O1ev - 12V +12V O12v OV ___| Note for the cables (b) With 12V Type PG refer to 7 3 1 Signal Cablh
Page 44
3 2 5 PG SIGNALS (Cont'd) (a) PG +TG
(c) With manual pulse generator Standard connection
TERMINAL SYMBOL, | A B Cc D R S Mot j SIGNAL NAME, | PA1 | OPA! PB1 | OPB} PCI | OPC + 12V ohonpac: TYPE AYS 1201 | power toy G {Hie TE u 2 12V1A O5y | 5V | FG | FG TG | TG2 cA 6 4800 A B | A B ad ne CA5 ory a CA 2 (tc CA 10 | CA 9 Fig 3 16 Direction of Motor Rotation 12V cB 3 | 36kN (6809 « 28) under @ Motion Command cao ) 18 0mA MAX Reverse connection A B Cc D R S CBS PBI | OPB} PA1 | OPA | PC) | OPC CB5 G H F F 1 2 MGX 10B Oss | 5V | EG | FG TG2| [Gl DE6429769 > POWER 12V 100mA 4 B OUTPUT 12V 20mA MAX B A Zo=2kn LOA _ oO meme, = (( (au) Fig 315 (2) PG pulse multipher setting Fig 3.17 Direction of Motor Rotation under © Motion Command The setting of PG pulse multipller 1s as shown below For example, to double the PG pulses, (b) Feedback unit (Standard Type TFUE-/,2C7) short CA-14 and CA-15 Connection must be terminated inside the connector casing Standard connection
FEED BACK
Exte xtending line wire will cause malfunction UNIT TERMINAL | A B C D F : , A Y SYMBOL OPAJOPB]OPC] COM | 4 12VJO12¥| TO 17) TG 2 Terminal No xl x2 x4 A B CA-14, “J A B CA-15 __| 3 CA-~16 7 Reverse connection CA-17 ~__! A B Cc D k t ¢ H
OPRB]OPA/]OPC] COM ]4+12N]012Vv| TC 2) 7TG1
(3) Motor direction of rotation
The motor direction of rotation 1s determined by 8 the connection polarity to the motor terminals, PG terminals and the TG terminals as shown be- (c) Feedback umit (High-speed Type TEFUE-.,ZD7 low Forward direction of motor rotation 15 counterclockwise viewed from drive end as shown Standard connection below Some motors like Minertia Motor Mini x 3 TC D R § -: a series run clockwise as forward direction, check Pallopal Pri | opp] Pui | oPrc [ - : " with the motor dimension diagram separately ra A ; x G A provided os | 5¥ | FG | FG TG1| TG2 Reverse connection A B U D R 5 : B PBL] OPB] PA1] OPA] PCL | OPC i, A G H F N G H Osy | SV | IG | FG 102] 7G1
38
Page 45
3.3 Motionpack-33 CONTROLLER PARAMETER
Motionpack-33 controller can meet the control specifications of combined machine by setting parameters listed in Table 3 6, drive system
The parameters set correctly
Before operation, they must
Table 3 6 Motionpack-33 Parameter List
Parameter
No Description Unit 1 JOG, low speed Speed unit 2 JOG, medium speed Speed unit 3 JOG, high speed Speed unit 4 JOG, STEP; STEP speed Speed unit 5 group STEP distance, moved short Min command unit 6 STEP distance, moved medium Min command unit 7 STEP move distance, moved long Min command unit 8-9 Unused 10 Creep speed Speed unit 11-19 Unused 20 Coordinate 8 single correction Min command unit 2) Offset Coordinate 8 max correction Min command unit 22 group Coordinate 9 single correction Min command unit 23 Coordinate 9 max correction Min command unit 24-39 Unused 40 Max speed Speed unit 4i Acceleration time msec 42 Servo Position loop gain No of pulses 43 group Unused No of pulses 44 Servo error deviation No of pulses 45 In-position range 46 G27 group G27 permissible error 47-49 Unused 50 Pulse ratio M 51 Umt Pulse ratio D 52 group Decimal point position No of digit columns 53 Thrust ratio (thrust rating/servo rating) x 100 54 Axis No designation 55-59 Unused 60 Overtravel -direction stored stroke limit Min position unit 61 group +direction stored stroke limit Min position unit 63-69 Unused 70 Return home mode 71 Home position coordinate No of pulses 72 Waiting position Min position unit 73 Home Return home speed Speed unit 74 position Return home creep speed 75 group Return home torque limit % 76 Coasting allowance No of pulses 77 Permissible error No of pusles 78 Butting time 10 msec 97 Tape device Baud rate setting bps must be determined in designing Motionpack-33 be
39
Page 46
3 3 1 MACHINE PARAMETERS 3.3.11 Position Command Unit (Pr50, Pr51)
The relationship between the position command unit and the position detection unit can be set arbitrary by parameters Pr50 and Pr5l], between
1 and +3999999 The value should be in the range JT. Pr50 |
50 Pl 50 Since motion distance are expressed in position detection units, some rounding error may be introduced when a com- mand value is converted into a detection value
P50 _ \o of pulses (pulse) Pr 3l Postion command valec (Pasition command unit) EXAMPLE 1 To determine Pr50 and Pr5l for a positioning device shown in Fig 3 18
REDUCTION RATIO a=
PG ry
~\ M 5 a Pye
PG 7
2000 pulse/rev {
QUADRUPLE USE
LEAD SCREW PITCH
6 mm/rev Fig 3 18 Leadscrew pitch 6 mm/rev Reduction ratio V/R = 1/7/5
PG 2000 pulses/rev, Quadruple multipher
Position command unit 1/1000 mm
PP, 50 = No of pulses = 2000 * 4 = 8000 pulse s/ter Prsi= foadserce prich mm/rervt
Postion command unit X rcoduction ratio RO
=, _o = 6000 x 2
0001 Xx 7 P, 30 8000 28 = Pat a =e [P80 = 28 Pr 51 = 15)
6000 X >
7 EXAMPLE 2 To determine Pr50 and Pr51 for the example shown
4 Hp |ieeersvouye |, mm/rev
2000 pulse/rev [3 quadruple 93
40
Leadscrew pitch 8 mm/rev
Reduction ratio 1/R R= maf yt 3 PG 2000 pulses/rev, Quadruple use
Positioning command unit 10 yu
P> 50 = 2000 X 4 = 8000 (pulses)
Leadscrew pitch (mm/rev)}
Prsls Pusttroning command unit X reduction ratio RD a 4200 001 x
“21
P50 . 8000 . 40 P51 < 4200 ~ 21
Note If Pr50 < Pr5]l, the min detecticn unit 1s coarser than the command unit, and the accuracy cannot be as good as the level of the command unit
3 3.1 2 Speed Command Unit (Parameter Pr52) This parameter is for determining the position of the decimal point in the minimum command unit The speed command unit is determined by the position of decimal point as specified by this parameter
EXAMPLE 1
Min command unit is lu, Prd2 = 3
X(U) roar 4 i, 3RD DIGIT FROM THE RIGHT
The speed unit 1s mm/min
EXAMPLE 2
Min command unit is 1p, Pr52 = 4 roqye aA roqro wr ar 4 i “hom a 4TH DIGIT FROM THE RIGHT
The speed unit is cm/min
EXAMPLE 3 Min command unit is l0u, Pr52 = 2
X(U)‘ aeoe ae yr and sas + 46 4 i X 10um mm 2ND DIGIT FROM THE RIGH1
Page 47
The speed unit is mm/min, The setting 1ange of Pr52 is from 0 to 5, specifying the position of decimal point
Speed unit = Position command unit x 10/min
If position command unit is lp, and Pr52=3 as shown in Example 1, speed command unit 1s mm/min, and feedrate when G01 x 5000,000 F10000 1200 is executed is, F = 10000mm/min
= 10 m/min
3.3.13 Thrust Ratio (Pr53)
This parameter is for setting the ratio of the programmed motor shaft torque taken as 100%, to the rated torque lmit of Servopack and ser vomotor
Programmed 100% motor shaft torque
> = Pr Rated motor torque Rated mator current xX 100 (% Serrapach 100% limetcd current 0(%) = (Rated thiusi/scrio rating) X 100%} EXAMPLE 1
Programmed 100% motor shaft torque = 60 kg-:cm
UGHMED-06, rated for 58 4 kg cm/ 6 2A
CPCR-MR Q8CT, limited at 5 7A
Servomotor
Ser vopack with 100% current
60 kg cm x £23 ca = Pr 53 58 4 ky em S7\ xX 100 = 112
EXAMPLE 2
Programmed 100% motor shaft torque = 100 kg cm
Servomotor UGHMED-12, rated for 117 kg cm/ 10 6A Servopack CPCR-MRI5CT, with 11 4A 5. eq, 100 he cm 106 \ _ P33 aT hg em iran § 10 7
The setting range of Pr53 1s between 1 and 200 However, since the torque restriction accuracy is only around +10%, detailed calculation is meaningless
To limit torque at high accuracy, measure the motor current with the machine slide butting against the stop and calculate the parameter from the measure current
3 3 1 4 Stored Stroke Limit (Pr60, Pr61)
This parameter is for setting the maximum motion range Parameter Pr60 1s for the minimum value in the - direction, and parameter Pr6l is for the maximum value in the + direction
The setting range 1s between -9999999 and +9999999 in minimum position command units
The coordinate values indicate positions on the TO coordinate system
If a feed command over the stored stroke limit is given in the AUTO mode, the command remains ineffective, and the control enters the stored limit error (MP alarm) state. In the JOG mode, the slide decelerates and stops at the stored stroke limit If further jogging is started beyond the hmit, the control enters the stored lmit error (MP alarm) state Stored stroke hmit is effective after completion of Home position return
3 3 2 SERVO-RELATED PARAMETERS 3 3 2 1 Acceleration Determination (Pr40, Pr41)
Pr40 specifies a speed and Pr4l specifies the time in which this speed is to be reached Set the maximum speed that can be programmed by parameter Pr40 Acceleration/deceleration time should be larger than that of machine including servo-drive Acceleration/deceleration time can be calculated referring to Appendix A (6) setting acceleration/deceleration time v Prag PULSE
DISTRIBUTION
ACCELERATION DECELERATION t Prat Prat Fig 320 Pr 40
\eeeloration =, deccle ration = Pr 41
Pr40 15 set 1n speed command units, and its setting range 1s between 1] and 60000 without a sign Pr4l is set in msec, and its setting range 1s between 50 and 60000 (1 minute) The 1 msec digit of Pr4l is ineffective
Example With a drilling machine
If the unit of speed command is mm/min and the maximum speed of 10 m/min is reached in 300 msec, set as follows
Pr40 = Pr4] =
10000 300
At
Page 48
3 3 2 1 Acceleration Determination (Pr40, Pr 41) (Cont'd)
Pr40=10 000
Pr41 =300 m/MIN PULSE DISTRIBUTION 10, MOTOR
é
_ and « os’, Hoe
300 300, - MS
Fig 3 21
3 3 2 2 Position Loop Gain (Pr42)
This parameter determines the DC servomotor response accuracy for pulse distribution The accuracy 1s specified by type of DC servomotor and rapid traverse rate
Pr42 1 Pr40- PULSE DISTRIBUTION y - ’ DC SERVOMOTOR | Sere \V F ere ego oN fe we etn Be Prat Pr4} s - Fig 3 22 x REFERENCE | POSITIONY | x DC SERVOMOTOR Pr42 POSITION | Pr4i Prat _ - - _ Fig 3 23
Fig 3 2] shows time-speed curve’ The area of ZZAshows Pr42 setting which 1s follow-up deviation (distance) It indicates the motor delay for reference positions at the constant spced motion shown by time-position curve in Fig 3 23
This parameter is for setting the follow-up deviation pulse (error counter) 1n motion at the rated speed to determine the position loop gain (The rated speed 1s one at a Servopack command input voltage of 6V )
Pr 42 = PPS at rated spced X, _1_ kp sec
"kp" means position loop gain and determined by type of DC servomotor
Hi-cup motor
Cup motor kp = 30s * Minertia Motor J Series Print motor kp = 40s"
42
The loop gain of ordinary machine tools range between approximately 40 sec”! for rigid machine and 20 sec”? for soft machines
EXAMPLE
With a drive system based on a Hi-Cup motor (rated speed 1000 rpm) with a PG for 3000 pulses/rev x 4 times feedback, a loop gatn with a kp of 40 sec~* 1s to be set
Assuming Pr50 = 1, Prd] = 1,
3000 P/r X 4 X 1000 r/M 1 60 s/M 40 '/sec
Pr 42
= 5000 pulses
Pr42 is the error pulse count of 200 to 30000 without signals
When a speed command is input to the auxil- lary input terminals (@)- @)) of the Servopack, loop gain is determined when Input Adjust (IN-B of the Servopack is set for the rated revolution number at 6 V. The actual value of kp varies according to the setting of Input Adjust
To obtain the actual value of kp, measure error pulse when the speed is fixed and divided PPS of feedrate by the error pulse
To determine Pr42 actually, substitute the value of the actual motor for the value of kp and calculate Pr42
Then, readjust Pr42 by measuring error pulse during trial when the motor 1s operated actually For adjustment, refer to the Motionpack-33 (SIE- C788-1 3)
3 3 2 3 Servo Error (Pr44}
It is to detect defects of the servomechanism Set an error pulse count within a normal] range when the servomechanism works properly
Normally set some twice of the parameter Pr42 determining the loop gain if error (dO) exceeds Pr44, the Motionpack gives an alarm of excessive error (dRr OuEr)
3 3 2 4 In-position Range (Pr 45)
Set allowable lag pulses to perform in-pcsition check with G04 For G04, see 3 4 2 5, in- position wait command
Ideally allowable lag pulses is zero, but it cannot become zero because of drift of D/A, error of adjustment (ZERO) of the Servcpack, etc As lag pulses are reduced, speed ts lower and more time 1s taken until coincidence Set it to the maximum within the range of precision the system requires
It is set at 30 to 60 pulse count for ordinary machine tools
Page 49
3 3 2 5 Allowable Error Amount by G27 (Pr 46)
This parameter designates the range to looking for origin pulse with a origin check command (G27) *
The unit is pulse count and 1 to 999999 can be designated
* With the G27 command, designated pulses are distributed for point A Then origin pulse 1s searched during travel from the point A to B, and the point C where the origin was read is reached
Then it 1s examined where the point C 1s within the range of the origin +/- Pr77
Inside the range --- good
Outside the range ~-- G27 Err ORIGIN PULSE Pr46 Pr46 REFERENCE HOME POSITION PULSE PULSE CHECK SPEED POINT A APOINT GC S|POINT B ON POSITION, - Pr77{Pr77 Fig 3 24
Select Pr46 to be greater than Pr45 and smaller than the pulse count of half rotation of the motor shaft
If the parameter is 0, the command position will be checked but the origin pulse coordinate not during execution of the G27 command
3.3 3 OPERATION PARAMETERS 3 3.3 1 JOG Feedrate (Pri, Pr2, Pr3)
These parameters determine the JOG feedrate The input signals JLF and JMF determine the feedrate as given in Table 3 7
The unit is that of the speed command and the range of feedrate is 0 to 60000
EXAMPLE Make Pr3 = 10000 to set JOG high speed = 10 m/min when the unit of speed com- mand is mm/min
Table 3 7 JOG Parameter
Speed Parameter JSLF SMF Low Pri ON OFF Middle Pr2 OFF ON High Pr3 ON ON
3.3 3 2 STEP Feedrate (Pr 4)
This parameter determines the STEP feedrate The unit is that of the speed command and the range of feedrate is 1 to 60000
3 3 3 3 STEP Feed (Pr5, Pr6, Pr7)
These parameters determine the unit distance of feed The input signals JLF and JMF determine the unit feed as given in Table 3 8
The unit 1s that of the position command and the range of unit feed 1s 1] to 9999999 unsigned
EXAMPLE If STEP is executed with Pr5 = 10 when the unit of position command is 0 001 mm, the distance of feed 1s 0 001 mm x 10 = 0 01 mm
Table 3 8 STEP Parameter
Parameter JLF JMF Short Pr5 ON OFF Middle Pro OFF ON Long Pr? ON ON
3 3 3 4 Creep Speed (Pr10)
When the speed limit signal (OVR) 1s ON during AUTO mode, the F command of program command is limited to the speed designated with Pr10 The F command, if it 1s smaller than Pr10, mains unchanged re-
Prl0 is given in the unit of speed command and the value is 0 to 60000
3 3 4 OFFSET PARAMETERS
3.3 41 8th Coordinate Correction Amount at a Rise (Pr 20)
This parameter determines the amount of coricc-tion made at a rise of +INC9 or -INCI
The value is 1 to 255 unsigned in the minimum command unit Set 0 for it when not used
3.3 4 2 8th Coordinate Maximum Correction Amount (Pr21)
This parameter determines the maximum of the total correction made with +INC8 or -INC8
A correction signal exceeding this maximum value will not be accepted
The value is |! to 9999999 unsigned in the minimum command unit See 0 for it when not used
3.3 4 3 9th Coordinate Correction Amount at a Rise (Pr22)
This parameter determines the amount of correction made at a time with +INC9 or -INC9
The value is 1 to 255 in the minimum command unit Set 0 for it when not used
43
Page 50
3 3 4 4 9th Coordinate Correction Amount (Pr 23)
This parameter determines the maximum of total correction made in the No 9 coordinate system
The value is 1 to 9999999 in the minimum command unit Set 0 for 1t when not used
NOTE
1 The amount of correction made at a time is converted to a pulse count If the ratio of the minimum command unit to the pulse count is not an integer in the drive system, take the pulse count into consideration to set the parameter (Rounding 1s made in conversion from the amount of correction to pulse count )
2 Offset 1s correctable during feed hold and after the end of automatic opera- tion
3.3.5 HOME POSITION RETURN PARAMETERS 3 35 1 Return to Home Position Mode (Pr 70)
This 6-digit parameter selects a manner of returning to the origin
Pr70 = ABCDEF
A Presence or absence of a waiting position after the end of return to the origin
B Ensuring origin-related signals i?)
Origin LS method
D Direction of move at the beginning of return to the origin
Direction to return to the origin
Setup method
The meaning of each of A to F 1s explained below
(1) A Presence or absence of a waiting position after the end of return to the origin
A =0 Stay there after the end of return to the origin A = 1. Move to the position designated with Pr7z after the end of return to the origin and stay there
NOTE
When A = 0, the machine is not positioned at the origin after the end of return to the origin If necessary, set A = 1 and Pr72 = Pr7l
44
(2) B Ensuring origin-related signals
There are two functions defined here One 1s to check whether or not the coordinate of the position where the origin pulse has been read-in 1s equal to the coordinate of the origin (Pr/71) after return to the origin It 1s good if the coordinate is in the range of Pr7l1 + Pr7? Otherwise setup alarm results This 1s called check of origin pulse The other 1s to check the state of origin LS at the position of the origin pulse In the case of Figure 3 25, for example, it 1s checked 1f the states of the slow-down L535 and the ensuring LS are all at the ON position of the origin pulse It 1s the same with only one
LS Setup alarm results if an error 1s detected B= 0 Neither origin pulse nor origin LS 1s checked B= 1 Origin pulse ts checked but orig n LS not B =2 Origin pulse and origin LS are checked ON DECEL LS (LSA) ON HOME POSITION | PULSE CHECK LS (LSB) f] HOME POSITION PULSE Fig 3 25 (3) Origin LS method
This parameter defines the method of origin LSs (deceleration LS and ensuring LS)
C =0 £4Neither origin pulse nor origin LS 1s used C = 1 One slow-down LS 1s provided and the origin pulse is searched at low speed in the area of the LS The reference point 1s the position where the origin pulse has been read-in
DECEL LS __f
(LSA) HOME POSITION | PULSE REFERENCE POINT Fig 3 26
C = 2 When a slow-down LS 1s pressed, the tool moves at low speed and reads in the origir pulse off the slow-down LS