Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 1 of 1

B833-016 24 VDC, 16 Point Input Module (True Low) Installation Instructions, pages 1 to 5

Pages 1 to 5 of 5

The original document is the PDF (165 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B833, AEG B833, Gould B833 and Schneider B833

Page 1 read from a scan by OCR; it may hold reading errors

Modicon B833-016/24 VDC,16 Point,

Input Module (True Low) Installation Instructions

PI-B833-001 Rev. D

AEG

SI SR BES RA eS a Re Ohi

Page 2 read from a scan by OCR; it may hold reading errors

Features

Sixteen independent 24 VDC inputs per module Circuit isolation of 1500 VAC/2500 VDC

True Low operation

Field-side status indicators

Front panel ACTIVE lamp

Transient protection

Communication failures automatically detected Designed for harsh industrial environments

Safe, non-conductive module front permits easy access for test probes

General Description

The MODICON B833-016, 24 VDC True Low Input Module consists of a single group of sixteen independent inputs.

The B833-016, 24 VDC True Low Input Module senses and converts switched input signals into logic voltage levels used by the programmable controller (PC). Inputs can be received from push buttons, limit and proximity switches, and other sources. The module provides sixteen inputs that share an external supply voltage.

Input voltages are sensed by comparing the incoming voltage against a fixed threshold. The threshold is a function of the user-supplied field voltage.

A hysteresis circuit helps ensure the module of reliable operation in the presence of electrical noise. Each input is electrically isolated from the controller by optical isolators. The inputs are designed to withstand the extreme voltage transients often encountered in an industrial environment.

Field-side LEDs display each input’s on/off state. The ACTIVE lamp ts lit as long as communication exists between the module and controller. If communication fails, the ACTIVE lamp goes off and all inputs in the PC default to an off condition.

es) | (i) a ,) ari! it ee At

IaH il

Win!

Page 3 read from a scan by OCR; it may hold reading errors

Figure 1

Key Pin Locations

The B833 can be inserted into any location in the MODICON 800 Series I/O Housing. The module slides easily into the housing and does not interfere with any other module. An optional mechanical keying system can be used to match the module with a particular slot in the housing. This ensures proper module placement. User

Top - - _ - connections are made to a standard screw terminal strip. The wiring / x system permits the module to be removed or replaced without | disturbing the field wiring. | x , The module’s protective case shields logic circuitry from electrical _- - ] interference and minimizes the possibility of noise being coupled from Bottom the user side of the circuitry to adjacent modules. The housing's, 7 backplane provides an earth ground when the module is inserted into ° x the housing. | When facing housing, place the knurled end of the key pins into the Xx ° holes indicated by the “‘X’’. Use a 1/2” plastic head mallet or equivalent, _ to drive the pin into the housing approximately 1/4 of an inch. > NOTE The keying system is optional. Figure 2 Vs > Ss BIAS : Simplified Schematic | ; YOLTAGE 3 ~. COMPARATOR \ AAA | INPUT >= - - - _wwn_ 4 2 ¢ - “ww NPUT iN as, OPTICAL ISOLATOR COMMON > + 4 Specifications

Electrical Characteristics

Input Signal Requirements

<2.6 VDC or 0.13 of Vs, whichever is greater. 200 ohms max. resistance to common. Input indicator ON.

On Condition

> 21 VDC or 0.75 of Vs, whichever is less. 10,000 ohms min. resistance to common. Input indicator OFF.

Off Condition

Contact Wetting Current 6 mA at 24 VDC.

PEAS SR BES A sta Re Ohi

Ita"

Page 4 read from a scan by OCR; it may hold reading errors

Specifications (continued)

Electrical Characteristics (continued)

Power Supply Loading:* +5VDC _, 5VDC +4.3VDC_ 2/ mA O mA 1.2mA

“Refer to electrical specifications of the power supply that will be used for this module.

Maximum Input Voltage 100V for 3ms

Circuit Characteristics

Topology 16 inputs per module Isolation Voltage

Field to System,

Between Inputs and Earth Ground 1500 VAC steady state maximum at 60 Hz for one minute 2500 VDC for 60 secands

Response Time ON to OFF, 11.0 ms (max)

OFF to ON, 11.0 ms (max) Visual Indicators One LED per input. LED ON when input conditions are In excess of defined ON levels One ACTIVE LED indicator, ON for as long as good communication exists between module and PC a A)

Dilbe kame!

‘ws

Environment

Operating

Temperature 0 to 60°C (32 to 140°F)

Humidity 0 to 95% (non-condensing) at 60°C Storage

Temperature, 40 to 85°C (32 to 140°F) Humidity Q to 95% (non-condensing) at 60°C Shock

Operating +/-10 G peak, 11 ms, half - -sine wave Vibration

Operating 0.625G, 50- - 500Hz

Dimensions 2.1 x 10.47 x 8.25 in.

(W x H x D) (53.3 x 265.9 x 209.6 mm)

Page 5 read from a scan by OCR; it may hold reading errors

(= Note The B833-016 is compatible with the B832-016 24VDC True Low Output

Module. SIGNAL TERMINAL NO. INPUT 1 1 @ INPUT 2 2 °@ INPUT 3 3 ¢@ INPUT 4 4 ® INPUT5 : 5 ® INPUT 6 6 @ INPUT 7 7 @ INPUT 8 8 @ COMMON 9 @ 2 COMMON 10® INPUT 9 11°® INPUT 10 120 INPUT 11 13°@ INPUT 12 | 14® INPUT 13 15@ INPUT 14 16¢@ INPUT 15 1/® Cy) © INPUT 16 | 18¢@ ous COMMON 19¢ -, 24VDC SUPPLY | 20€ | | ey

Figure 3. Terminat Numbering and Input Connections

PEAS SR BES A sta Re Ohi