The text of a manual · part 3 of 6

PanelMate Modicon Communication Driver Manual: Modicon PLCs Using Modbus, pages 11 to 19

Pages 11 to 19 of 49, from PanelMate Modicon Communication Driver Manual

The original document is the PDF (719 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon J375, AEG J375, Gould J375 and Schneider J375

Page 11

Chapter 2: Modbus PLCs Using Modbus

Modicon PLCs Using Modbus

2 This chapter explains how to use your PanelMate operator station with Modicon PLCs in Modbus ASCII or RTU mode. Specifically, this chapter includes: •

Introduction

•

Memory

•

Possible Configurations

•

PLC & communications module setup

•

Cable diagrams

•

Communications parameters

•

Modicon word and bit references

•

Maintenance access

•

PLC cabling cross reference list

9

Page 12

10

Modicon Communication Driver Manual

Introduction The Operator Station can be used with any of the Modicon PLCs that have Modbus capability. You may use the Modbus ASCII mode driver or the Modbus RTU mode driver to communicate Modbus to Modicon PLCs. The driver takes responsibility for communications to this programmable controller, generating the protocol necessary to request information from and send information to the PLC. The PLCs simply respond to these requests and commands. No ladder logic is required in the PLC to support the interface to the Operator Station. The information in this manual is for the Modbus ASCII and Modbus RTU mode drivers only. Depending on the driver selected in the PLC Name and Port Table, you must select either ASCII or RTU mode to communicate to an Operator Station.

Memory The following memory types are supported by the Modbus ASCII and Modbus RTU (Micro 84, 184, 384, 484, 584, 884, and 984) mode drivers. 0XXX Coils/discrete outputs 0XXXX 0XXXXX 1XXX Discrete inputs (read only) 1XXXX 1XXXXX 3XXX Input registers (read only) 3XXXX 3XXXXX 4XXX Holding/output registers 4XXXX 4XXXXX Note:

For Modicon PLCs, “F”: must precede all holding registers to designate a floating point number.

Page 13

Chapter 2: Modbus PLCs Using Modbus

Possible Configurations Examples of possible connections are described and shown in the following pages.

Direct A direct connection to a Modicon PLC with built-in Modbus, without the need for any additional modules.

Models without built-in Modbus require a Modbus adapter.

11

Page 14

12

Modicon Communication Driver Manual

Multiple PLCs on a Single Modbus If the Operator Station is to communicate with multiple PLCs on a single Modbus network, it requires its own Modbus modem to provide the necessary interface.

Page 15

Chapter 2: Modbus PLCs Using Modbus

Adapters and Cable Connectors for Modicon PLCs The following table shows the Modicon PLCs, adapters, and cable connectors. Consult the proper Modicon manual for any information not contained in this manual. Model

984-X 984-381 –480/680 780 984-380 984-1XX 884 584 484 µ84 Micro

Modbus Ports Built-In 3 2 2

1 1 2 2 None None 1

Modbus Adapter N/A N/A N/A

N/A N/A N/A N/A J474 J375 N/A

Modbus Modem S978 S978 J878

J878 J478 J478 J478 J474/475 J378 JXXX

* 984-120, 984-130, 984-145 ** Models 984-385/485/685/785 have one Modbus port and one Modbus Plus port

Cable Connector DB-25P DB-25P DE-9P

Port(s)

DB-9P DB-9P DB-25P Military 30-pin DB-25P RJ45

1 1 1,2 1,2 1,2 1 1

1,2,3 1,2 1,2

13

Page 16

14

Modicon Communication Driver Manual

Cable Diagrams Communications between the Operator Station and Modbus is RS232C. The recommended maximum cable length is 50 cable feet. You should construct a communications cable of the desired length for each connection to be made. Note that the cable configuration is similar for the various Modicon PLCs and modems. (You may also use a standard Modicon W190 cable instead of constructing your own.) A 15-foot PLC cable can be purchased from Cutler-Hammer. Contact the Customer Support Center at (614) 883-3282 or your local distributor for more information. Refer to the PLC Cabling CrossReference List section for cabling catalog numbers. The Operator Stations that have 9-pin female connectors (DB-9S) must have cables configured with male connectors (DB-9P). Note:

For PanelMate PC applications, a female 9-pin connector is required for connecting to a male 9-pin port. To quickly convert a Cutler-Hammer cable for PC use, simply attach the 9-pin Gender Changer found in the PanelMate PC Runtime Kit.

Modbus 25-Pin Ports

Modbus 9-pin Ports

MB21

Page 17

Chapter 2: Modbus PLCs Using Modbus

Micro RJ45 Connector

MB22

TD RD SG

584 Military Connector

25-Pin Modems (J478)

15

Page 18

16

Modicon Communication Driver Manual

The Operator Stations that have RJ-11 6-wire modular jacks must have cables configured with male modular connectors.

Modbus 25-Pin Ports

Modbus 9-Pin Ports

Micro RJ45 Connector

Page 19

Chapter 2: Modbus PLCs Using Modbus

17

584 Military Connector

25-Pin Modems (J478)

For applications requiring additional Modbus ports, it is recommended that Modbus expanders be used. Modbus Port Expanders from Modicon may be used to connect multiple Operator Stations to a single PLC. The Operator Station communications cable previously described may be used to connect the Operator Station and the PLCs to a Modbus Port Expander.

Communications Parameters For each Modicon port used, certain parameters must be set in order to establish communications with the Operator Station. This is accomplished either through dipswitch settings on the individual module or programming selections using the Modicon P230 Programmer. Standard communication parameters for communicating with Modicon PLCs using Modbus are: 7 data bits for ASCII mode and 8 data bits for RTU mode 1 stop bit* 9600 baud rate ASCII or RTU mode** No parity *2 stop bits for 984-38X, 984-48X, 984-68X **Depending on the driver selected in the PLC Name and Port Table, you must select either ASCII or RTU mode to communicate to an Operator Station. All other parameters should be configured as listed above. Note:

The following is a summary of the information available at the time of this manual’s printing, describing the necessary settings for each PLC model. Be sure to check with Modicon for any possible updates or changes if you encounter any difficulty.