The text of a manual · part 6 of 6
PanelMate Modicon Communication Driver Manual, pages 42 to 49
Pages 42 to 49 of 49: Modicon 410 Servo Controller; Index; Reader Comment Card
The original document is the PDF (719 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon J375, AEG J375, Gould J375 and Schneider J375
Page 42
40
Modicon Communication Driver Manual
Modicon 410 Servo Controller
4 This chapter explains how to use the PanelMate operator station to communicate with the Modicon 410 Intelligent Brushless Servo Controller. Specifically, this chapter includes: •
Introduction
•
Driver Installation
•
Memory
•
Possible Configurations
•
Cabling
•
Communication Parameters
•
Modicon 410 Word and Bit References
•
Maintenance Access
Page 43
Chapter 4: Modicon P410 Servo Controller
41
Introduction The PanelMate Operator Station can be used to communicate with the Modicon 410 Intelligent Brushless Servo Controller. The driver takes responsibility for communications to this controller, generating the protocol necessary to request information from and send information to the controller. The controller responds to these requests and commands. No ladder logic is required in the controller to support the interface to the PanelMate unit.
Driver Installation The driver software contains an installation program named Setup. Setup is on the diskette labeled “PanelMate Plus Modicon Driver Disk.” To install the driver on your hard disk, insert the driver disk in your computer. Under Windows in the Program Manager, choose File Run. In the Run dialog box, type: Drive:\Setup In the Command Line entry field, where drive is the letter of the floppy drive that contains the driver disk, choose the <OK> button. From the Setup program, select the directory for the driver files. (The default directory is C:|\PMCONFIG\ONLINE\DRIVER.) Once the installation is complete, you will find the following files on your computer: Filename
Description
MOD410.DLL
Used by the Configuration Editor
MOD410.DVR Downloadable driver
Memory This interface supports reading and writing 32-bit signed user registers. Register addresses must be in a decimal format, in the range of 0 to 99.
Page 44
42
Modicon Communication Driver Manual
Possible Configurations Examples of possible configurations are described and shown below.
Direct A direct connection to a Modicon 410 without the need for any additional modules uses RS232/RS422 communications.
Multiple Controllers The following figure shows multiple controllers connected on a network using RS422 communications. The RS422 communications allow a maximum of 16 Modicon 410s to be connected on a network.
Page 45
Chapter 4: Modicon P410 Servo Controller
43
Cabling A shielded cable must be used to connect the PanelMate unit to a Modicon 410. The following diagrams describe the pinouts needed for a cable using RS232 and RS422, respectively. Using RS422, you can daisy chain devices for a multidrop configuration. The first Modicon 410 and the PanelMate Plus unit must be wired as shown below. A multi-drop configuration can be wired using RS232 as long as it is used to connect the PanelMate unit to the first device only. All subsequent devices must be wired using RS422 in a daisy chain fashion.
Communications Cable for Modicon PLCs PanelMate Serial Ports
Modicon 410
Shield
1 (SHLD)
2 (RD)
3 (RD)
3 (TD)
2 (TD)
5 (GND)
7 (GND)
Modicon 410 RS232 Cabling
Communications Cable for Modicon PLCs PanelMate Serial Ports
Modicon 410
Shield
1 (SHLD)
1 (TD+)
22 (RD+)
4 (RD+)
25 (TD+)
5 (GND)
7 (GND) 23 (RS232)
6 (TD-)
21 (RD-)
9 (RD-)
24 (TD-)
Modicon 410 RS422 Cabling
Page 46
44
Modicon Communication Driver Manual
Communication Parameters For the Modicon 410, certain parameters must be set in order to establish communications with the PanelMate unit. This is accomplished through dip switch settings, used to select a Modicon 410 network address. The network address selected is the PLC ID in the PanelMate Plus unit, PLC Name and Port Tables. 0 indicates the switch should be in the down position, 1 indicates up. Switch Settings Address
1
2
3
4
0
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
Standard communication parameters for communicating with the Modicon 410 are: 8 data bits 2 stop bits 9600 baud rate no parity
Page 47
Chapter 4: Modicon P410 Servo Controller
45
Modicon 410 Word and Bit References The following section describes the use of Modicon 410 word and bit references in your configuration. The general word referencing method is: [plcname,word#format] The “plcname” is the name of the designated PLC as listed in the PLC Name and Port table. The “word” is the reference number (address) of the word or register to be read or written. The “#format” is a code that specifies the format of the data being read or written. The “plcname” and #format” are optional. The general bit referencing method is: [plcname,bit] The “plcname” is the designated PLC as listed in the PLC Name and Port table. The “bit” is the reference number (address) of the bit, coil or input to be written or read. See chapter 10 for a more detailed explanation of word and bit references, including format descriptions. This interface supports only reading and writing 32-bit signed user registers. Register addresses must be in a decimal format, in the range of 0 to 99. The default PanelMate unit read/write format is signed 32 (S32). Only 32-bit data types are allowed (S32, U32, BCD6, BCD8, BIN6, BIN8). The following is the format for a register reference: [rr] rr = PLC reference number of the register (o – 99 decimal, leading zeros not required)
Examples The following are examples of valid PLC references that may be assigned in the PanelMate expression fields. Word References: Reference
Description
[1]
Register 1
[36]
Register 36
[48]
Register 48
Note
The Modicon 410 will only perform single register reads and writes. Due to this fact, update times will be affected by the number of registers being polled by the PanelMate unit. The reason update times are slower is because a packet must be sent for each register that is read.
Maintenance Access A Maintenance Template cannot be used to monitor Modicon 410 Servo Controller references.
Page 48
46
Modicon Communication Driver Manual
Index A Adapters and Connectors, 13 C Cable Diagrams, 14 Modbus Plus, 32 Communication Parameters Modbus Plus, 34 Communications Parameters, 17 484 PLC/J474, 19 884 Modbus Ports, 18 984-38X, -48X, -68X, and -78X, 18 Micro 84/J375 Adapter, 19 Configuration Entries - Modbus Plus, 34 D Downloading Drivers to a PanelMate Unit, 7 I Installing Drivers, 6 L LEDs - Modbus Plus Interface Card, 32 M Maintenance Access, 26 Modbus, 26 Modbus Plus, 40
Memory, 10 ASCII, 10 Modbus Plus, 28 RTU, 10 Modbus Plus Interface Board, 28 P PLC Configurations, 11 Modbus - Direct, 11 Modbus Plus - Direct, 29, 43 Modbus Plus - Multiple controllers on a single Modbus Plus network, 30 Modbus Plus - Multiple controllers on multiple Modbus Plus networks, 31 Multiple PLCs on a single Modbus, 12 S Serial Transfer Cables, 7 Switch Settings - Modbus Plus, 35 U Unsolicited Writes, 39 W Word and Bit References, 23 Modbus - 584, 884, 984 PLCs, 24 Modbus - 84, 184, 384, 484 Micro, 23 Modbus - Examples, 25 Modbus Plus - 984 Series PLCs, 37
Page 49
Reader Comment Card Cutler-Hammer strives to provide quality user guides and product manuals. Please take a moment to fill out this comment card.
Title: Modicon Communication Driver Manual 01-00454-03 Excellent Good Is the document easy to follow? Does the product work as described in this document? Are the instructions easy to follow? Are the examples helpful/useful? Are there enough examples? Is the document organized logically? Is it easy to find what you are looking for? Are the illustrations clear and useful? How would you improve this document?
Please list any errors found in this document:
Other comments:
Your name and address: (optional)
Thank you for your comments. Please fax this page to: Cutler-Hammer Technical Publications Dept. FAX : 614-882-0417
Fair
Poor