Supported Block Transfer Messages

Fault Command Write

B–17

Fault Command Write activates the Clear Fault, Clear Fault Queue, and Drive Reset functions.

PLC Block Transfer Instruction Data PLC request instruction length: 4 words Drive response instruction length: 4 words Figure B.11

Message Structure

PLC Request Drive Response

Message Length 4 PLC Decimal Value➀ –30976

Header Word 0

Message Length 4 PLC Decimal Value➁

Header Word 1

1792, Message OK –30976, Message Error

0

Header Word 2

Fault Command

Data Word 3

Value

Fault Command

00 01 02 03

Not Used Clear Fault Clear Fault Queue Drive Reset (1336 FORCE Only)

Header Word 0 Header Word 1

0

Header Word 2

0 or Error Code

Data Word 3

Message Operation The specified fault command function sends a fault handling request to the device. • A Clear Fault request clears the last fault that occurred. • A Clear Fault Queue clears the entire fault buffer. Certain devices may store more than one fault. • A Drive Reset is used with the 1336 FORCE drive product only. This function resets the drive; it clears the fault queue and writes the parameter information stored in NVS Storage to RAM. Data File Format 0

1

2

3

PLC request

4

–30976

0

0, 1, 2, or 3

Drive response

4

1792

0

0*

4

5

6

7

8

9

➀ For Warning Clear messages, the PLC decimal value is -30720. You can use three values:

0 = Not used, 1 = Clear Warning, and 2 = Clear Warning Queue. ➁ For Warning Clear messages, a message OK returns 2048, and a message error returns

-30720. * Example only, These values vary depending on parameters and products.

Page 82

B–18

Supported Block Transfer Messages

Fault Queue Entry Read Full

Fault Queue Entry Read Full reads the contents of the specified fault queue entry. A message is returned which includes the fault text and fault code associated with the fault. The 1336 FORCE drive also returns the time stamp associated with the fault.

PLC Block Transfer Instruction Data PLC request instruction length: 3 words Drive response instruction length: 12 or 16 words Figure B.12

Message Structure

PLC Request Drive Response

Message Length 3

Header Word 0

PLC Decimal Value➀ 1792

Header Word 1

Fault Queue Entry Number

Header Word 2

1792, Message OK –30976, Message Error

Header Word 0 Header Word 1

Fault Queue Entry Number

Header Word 2

Message Length 12 or 16 PLC Decimal Value➁

Char 2

Char 1

Data Word 3

Char 4

Char 3

Data Word 4

Char 6

Char 5

Data Word 5

Char 8

Char 7

Data Word 6

Char 10

Char 9

Data Word 7

Char 12

Char 11

Data Word 8

Char 14

Char 13

Char 16

Char 15

Fault Text

1336 FORCE Drive Only➂

Data Word 9 Data Word 10

Fault Code Value

Data Word 11

SES

REF

Data Word 12

Hour

Minute

Data Word 13

Date

Day

Data Word 14

Year

Month

Data Word 15

Clock Time

➀ For Warning Queue Read Full messages, the PLC decimal value is 2048. ➁ For Warning Queue Read Full messages, a message OK returns 2048, and a message error returns -30720. ➂ Other drives return zeros.

Page 83

Supported Block Transfer Messages

B–19

Message Operation Fault Queue Entry Read Full reads the contents of the fault queue specified in word 3 of the request. The response returns the fault text which can be ASCII text. Every two characters of text are in reverse order. Also, the 1336 FORCE drive returns a time stamp, indicating the day and time the fault occurred. If an error has occurred, word 1 of the response returns a negative value.

Example In this example, Fault Queue Entry number 3 was retrieved from a 1336 PLUS drive. The fault code for this example is 22, and the fault name is Drive Reset Flt. The fault code (22) is word 11 (12th word) in the decimal drive response. The fault name (Drive Reset Flt) is in the ASCII drive response. Note that every other character is reversed. Data File Format 0

1

2

3

4

5

6

7

8

9

PLC request

3

1792

3*

Drive response (Decimal)

12

1792

3*

29252*

20313*

8293*

25938*

25971*

8308*

27718*

8303*

22*

Drive response (ASCII)

\00\12

\07\00

\03\00 rD vi e eR es t lF t

\00\16 * Example only, These values vary depending on parameters and products.

Page 84

B–20

Supported Block Transfer Messages

Fault Queue Size Read

Fault Queue Size Read gets the number of fault entries allowed in the fault queue.

PLC Block Transfer Instruction Data PLC request instruction length: 3 words Drive response instruction length: 4 words Figure B.13

Message Structure

PLC Request Drive Response

Message Length 3

Header Word 0

PLC Decimal Value 1793

Message Length 4

Header Word 1

PLC Decimal Value

0

Header Word 2

Header Word 0

1793, Message OK –30975, Message Error

Header Word 1

0

Header Word 2

Fault Queue Size or Error Code

Data Word 3

Message Operation Fault Queue Size Read reads back the size of the fault queue available in the product. Each product may have a different number of fault queue entries available for storage. If an error has occurred, word 1 of the response returns a value of -30975.

Example In this example, a 1336 PLUS drive was used. This product has a fault queue of four storage locations available to store faults. This value is seen in word 3 of the response header message. Data File Format 0

1

2

PLC request

3

1793

0

Drive response

4

1793

0

3

4

5

6

7

8

4* * Example only, These values vary depending on parameters and products.

9

Page 85

Supported Block Transfer Messages

Trip Fault Queue Number Read

B–21

Trip Fault Queue Number Read provides the fault queue number of the fault that caused the device to trip.

PLC Block Transfer Instruction Data PLC request instruction length: 3 words Drive response instruction length: 4 words Figure B.14

Message Structure

PLC Request Drive Response

Message Length 3

Header Word 0

PLC Decimal Value 1794

Header Word 1

0

Header Word 2

Message Length 4 PLC Decimal Value 1794, Message OK –30984, Message Error

Header Word 0 Header Word 1

0

Header Word 2

Number of Trip Fault or Error Code

Header Word 3

Message Operation Trip Fault Queue Number Read provides the number of the entry in the fault queue that tripped the device in word 3 of the drive response. The fault queue number is 0 when the device is not faulted. If an error has occurred in the block transfer, word 1 of the response is negative.

Example In this example, the device has stored a fault in the first entry of the fault queue that caused the drive to trip. Word 3 of the response indicates the entry number. Data File Format 0

1

2

PLC request

3

1794

0

Drive response

4

1794

0

3

4

5

6

7

8

1* * Example only, These values vary depending on parameters and products.

9

Page 86

B–22

Supported Block Transfer Messages

Block Transfer Quick Reference

Class Parameter Read

Word 0 Word 1 Message Decimal Message Length Value Continuous Parameter Value 4 1 Read Parameter Read Full 3 768 Parameter Value Read

Parameter Write

Fault Queue

Warning Queue

EE Memory Request Link Read

Link Write

The following table provides a list of block transfers and a description of the data that is entered in the first few words.

3

Scattered Parameter Value 5 – 64 Read Continuous Parameter Value 5 – 64 Write

769 3 -32767

Parameter Value Write

4

-31999

Scattered Parameter Value Write

5 – 64

-32765

Fault Command Write

4

-30976

Word 2

Word 3

Word 4

Word 5

Word 6

Data Number of Parameters Parameter Number Parameter Number Number of Parameters Number of Parameters

Data Starting Parameter ➀

Data ➀

Data ➀

Data ➀

Example B-14

➀

➀

➀

B-5

➀

➀

➀

➀

B-3

First Parameter Starting Parameter

0

Parameter Number Number of Parameters

Parameter Value First Parameter

0

Second 0 B-10 Parameter ➁ First Second Second Parameter Parameter Parameter Value Value B-4 ➀ ➀ ➀ First Second Parameter Parameter Value ➀ ➀

Second B-12 Parameter Value B-17 ➀

➀

➀

➀

B-18

➀ ➀

➀ ➀

➀ ➀

B-20 B-21

➀

➀

➀

B-17

Fault Queue Entry Read Full 3

1792

Fault Queue Size Read Trip Fault Queue Number Read Warning Command Write

3 3

1793 1794

Fault Command Fault Queue ➀ Entry Number 0 ➀ 0 ➀

4

-30720

0

Warning Queue Read Full

3

2048

➀

➀

➀

B-18

Warning Queue Size Read Save/Recall/Initialize

3 4

2049 -31988

Warning Queue Entry Number 0 ➀ 0 EE Command

➀ ➀

➀ ➀

➀ ➀

➁ B-16

Continuous Parameter Link Read

4

4

Number of Links

➀

➀

➀

➁

Parameter Link Read Scattered Parameter Link Read

3 5 – 64

2304 5

➀ 0

➀ 0

➁ ➁

Continuous Parameter Link Write

5 – 64

-32764

4 4 5 – 64

-30464 -30464 -32763

Third Link Number ➀ ➀ Second Link

➁

Parameter Link Clear Parameter Link Write Scattered Parameter Link Write

➀ Second Link Number Second Link Number ➀ ➀ Second Link Number

Warning Command ➀

Starting Link Number Link Number ➀ Number of First Link Links Number

Number of Links

Starting Link Number 0 1 Link Number Link Number of First Link Links Number

First Link Number ➀ ➀ First Link

➀ This word is not used. ➁ Example not available in this manual. Refer to the 1336 FORCE PLC Communications Adapter User Manual, Publication 1336 FORCE -5.13. ➂ n x 4096 + offset (bits 0 – 11) ➃ Trending is a function of the 1336 FORCE drive with a PLC adapter board.

➁ ➁ ➁

Page 87

Supported Block Transfer Messages

Class User Text String

Message User Text String Read User Text String Write

Word 0 Word 1 Message Decimal Length Value 3 261 11 -32507

Product ID Product ID Number Read 3 Number Read Clock Data Real Time Clock Data Read 3 Real Time Clock Data Write 7 Run Time Clear Run Time Accumulator 3 Accumulator Run Time Accumulator Data 3 Read Time Stamp Load Clock Info Reference 3 Stamp Reference Time Stamp Data 3 Read Reference Time Stamp Data 3 Write Trend File All Info 3 Maximum Trend Size Avail- 3 able Number of Trends Available 3 Run File Data 3 Setup Data Full 15 Trend Command 4 Trend Parameter Definition 3 Trend Status 4 Trend Triggered Setup 3 Parameter Trigger Time 3

Word 2

Word 3

Word 4

Word 5

Word 6

Data 0 0

Data ➀ char 3/ char2 ➀

Data ➀ char 5/ char4 ➀

Data ➀ char 7/ char 6 ➀

B–23

256

0

Data ➀ char 1/ char 0 ➀

2816 -29952 -29950 2817

0 0 0 0

➀ sec./100th ➀ ➀

➀ hour/min. ➀ ➀

➀ date/day ➀

➀ ➁ year/month ➁ ➁ ➀ ➁

-29950

➀

➀

➀

➀

➁

➀

➀

➀

➀

➁

➀

➀

➀

➀

➁

4098 4097

Time Stamp Number Time Stamp Number Time Stamp Number n x 4096 0

➀ ➀

➀ ➀

➀ ➀

➀ ➀

➁➃ ➁➃

4096 4100 -28670 -28672 4102 4097 4103

0 ➂ n x 4096 n x 4096 n x 4096 n x 4096 n x 4096

➀ ➀ ➀ 1–3 ➀ 1–4 ➀

➀ ➀ ➀ ➀ ➀ ➀ ➀

➀ ➀ ➀ ➀ ➀ ➀ ➀

➀ ➀ ➀ ➀ ➀ ➀ ➀

➁➃ ➁➃ ➁➃ ➁➃ ➁➃ ➁➃ ➁➃

4099 n x 4096

➀

➀

➀

➀

➁➃

2816 -29952

➀ This word is not used. ➁ Example not available in this manual. Refer to the 1336 FORCE PLC Communications Adapter User Manual, Publication 1336 FORCE -5.13. ➂ n x 4096 + offset (bits 0 – 11) ➃ Trending is a function of the 1336 FORCE drive with a PLC adapter board.

Example ➁ ➁ B-8

Page 88

B–24

Supported Block Transfer Messages

End of Appendix B