Page 1 of Bulletin 1203 Remote I/O Communications Module User Manual

Manual · Allen-Bradley

Bulletin 1203 Remote I/O Communications Module User Manual

Manual96 pagesPDF 3.4 MB

User manual for the Allen-Bradley Bulletin 1203 Remote I/O communications modules 1203-GD1, 1203-GK1 and the 1336-GM1 board.

Download the PDF3.4 MB

Covers · 1 model

The models it covers

Summary

What is in it

Rockwell Automation installation and user guide for the Bulletin 1203 Remote I/O communications modules (1203-GD1, 1203-GK1 and 1336-GM1 board), firmware 1.xx to 4.xx, which link one SCANport product such as a drive to an Allen-Bradley programmable controller over Remote I/O. It covers DIP switch configuration, cables and termination, installation, ladder logic examples for PLC, SLC and Logix5550 controllers, block transfer messages, LED troubleshooting and specifications.

Its parts

  1. Overview
  2. Configuring the Module
  3. Installing the Module
  4. Creating Ladder Logic Programs
  5. Using Block Transfer Messages
  6. Troubleshooting

From the manual

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley user manual for the Bulletin 1203 Remote I/O communications modules 1203-GD1 and 1203-GK1 and the 1336-GM1 board, firmware 1.xx to 4.xx. Each one links a single SCANport product, such as a 1336 drive, to an Allen-Bradley programmable controller over Remote I/O. It covers DIP switch setup, cables and termination, mounting, ladder logic and block transfer messages, LED troubleshooting and specifications.

Read for this summary: pages 1 to 2, 5 to 6, 11 to 19, 31 to 33 and 61 to 64 of 96.

Device
Remote I/O communications module linking one SCANport product to an Allen-Bradley programmable controller p. 11
Power
1203-GD1: 85-264V AC (1203-GK1: 24V DC) p. 14
Connectors
1203-GD1 and 1203-GK1: 8-pin mini-DIN SCANport connector and 3-pin Remote I/O connector p. 14
Mounting
1203-GD1 and 1203-GK1: 35 x 7.5 mm DIN rail p. 16
Baud rates
Remote I/O at 57.6, 115.2 or 230.4 kbps, set with switches SW2.7 and SW2.8 p. 18, 19
I/O words
Up to 8 words of I/O; each enabled datalink uses two words p. 12, 13
Controllers
Logix5550, PLC-2/30 with SD2, PLC-3, PLC-5 families, PLC-5/250, PLC scanner modules, SLC 500 with 1747-SN scanner p. 13
SCANport products
1305, 1336 IMPACT, PLUS, PLUS II, FORCE and SPIDER drives, 1336 REGEN, 1394, SMC Dialog Plus, SMP-3, 1397, 1557, 2364F p. 13
SCANport cables
Male to male 1202-C03, 1202-C10, 1202-C30, 1202-C90 (1/3, 1, 3, 9 m); male to female 1202-H03, 1202-H10, 1202-H30, 1202-H90 p. 31
Remote I/O cable
Twinaxial 1770-CD Belden #9463 p. 32
Termination
82 ohm resistor between terminals 1 and 2 of the Remote I/O connector, or 150 ohm where a device requires it; 82 ohm required at 230.4 kbps p. 32
DIP switches
SW1.3 to SW1.8 rack address; SW2.1 to SW2.2 starting module group; SW3.1 block transfer; SW3.4 to SW3.7 datalinks A to D p. 18
LEDs
Fault, SCANport STS, Health, Rem I/O ACT and Rem I/O STS p. 61
Firmware
1.xx to 4.xx p. 1

What this manual walks you through

  • Setting the DIP switches for rack address, baud rate, datalinks and fault action p. 18, 19
  • Choosing SCANport and Remote I/O cables p. 31, 32
  • Selecting a termination resistor for the Remote I/O link p. 32
  • Mounting a 1203-GD1 or 1203-GK1 module on DIN rail p. 33
  • Using datalinks to pass data between controller and drive p. 12
  • Troubleshooting with the module LEDs p. 62

Good to know

  • The module does not work with complementary I/O configurations. p. 17
  • Firmware 4.01 modules used only for block transfer need switches SW 3.1 and SW 3.3 on and the rest of SW3 off. p. 17
  • Keep total SCANport cable to 10 m (33 ft) or less between the product and all peripherals. p. 31
  • Do not wire the Remote I/O link as a star; only two cables may meet at any wiring point. p. 32
  • The modules cannot be repaired. p. 63

Questions this manual answers

What power does the 1203-GD1 need?

85 to 264V AC. The 24V DC version is the 1203-GK1. p. 14

What baud rates does the 1203-GD1 support?

57.6, 115.2 or 230.4 kbps on Remote I/O, chosen with switches SW2.7 and SW2.8. p. 18, 19

Which termination resistor does a 1203-GD1 Remote I/O link need?

An 82 ohm resistor unless a device on the link requires 150 ohm; at 230.4 kbps 82 ohm is required. p. 32

Which controllers work with the 1203-GD1?

Logix5550, PLC-2/30 with SD2, PLC-3, the PLC-5 families and PLC-5/250, PLC scanner modules, and SLC 500 with a 1747-SN scanner. p. 13

What cable connects the 1203-GD1 to the Remote I/O link?

Twinaxial 1770-CD Belden #9463, the only cable tested and approved for RIO and DH+. p. 32

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front cover1
  2. Important User Information2
  3. Summary of Changes3
  4. Preface7
  5. Chapter 111
  6. Chapter 217
  7. Chapter 331
  8. Chapter 439
  9. Chapter 553
  10. Appendix A63
  11. Appendix B65
  12. Index89
  13. Trademark95
  14. Back cover96

From the PDF’s own bookmarks.

The whole text · 11 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 41-4
  2. Pages 5 to 105-10
  3. Chapter 111-16
  4. Chapter 217-30
  5. Chapter 331-38
  6. Chapter 439-52
  7. Chapter 553-62
  8. Pages 63 to 7163-71
  9. Pages 72 to 8072-80
  10. Pages 81 to 8881-88
  11. Pages 89 to 9689-96

The file

Revision and size

Part no.1203-5.16
RevisionAugust 2006
PublisherRockwell Automation
Pages96
PDF3.4 MB
TextText from the PDF itself.
1203-5.16

The first pages · 3 of 96

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 96
Page 2
Page 2of 96
Page 3
Page 3of 96