What is in it
Rockwell Automation installation and user guide for the Bulletin 1203 Remote I/O communications modules (1203-GD1, 1203-GK1 and 1336-GM1 board), firmware 1.xx to 4.xx, which link one SCANport product such as a drive to an Allen-Bradley programmable controller over Remote I/O. It covers DIP switch configuration, cables and termination, installation, ladder logic examples for PLC, SLC and Logix5550 controllers, block transfer messages, LED troubleshooting and specifications.
Its parts
- Overview
- Configuring the Module
- Installing the Module
- Creating Ladder Logic Programs
- Using Block Transfer Messages
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley user manual for the Bulletin 1203 Remote I/O communications modules 1203-GD1 and 1203-GK1 and the 1336-GM1 board, firmware 1.xx to 4.xx. Each one links a single SCANport product, such as a 1336 drive, to an Allen-Bradley programmable controller over Remote I/O. It covers DIP switch setup, cables and termination, mounting, ladder logic and block transfer messages, LED troubleshooting and specifications.
- Device
- Remote I/O communications module linking one SCANport product to an Allen-Bradley programmable controller p. 11
- Power
- 1203-GD1: 85-264V AC (1203-GK1: 24V DC) p. 14
- Connectors
- 1203-GD1 and 1203-GK1: 8-pin mini-DIN SCANport connector and 3-pin Remote I/O connector p. 14
- Mounting
- 1203-GD1 and 1203-GK1: 35 x 7.5 mm DIN rail p. 16
- Baud rates
- Remote I/O at 57.6, 115.2 or 230.4 kbps, set with switches SW2.7 and SW2.8 p. 18, 19
- I/O words
- Up to 8 words of I/O; each enabled datalink uses two words p. 12, 13
- Controllers
- Logix5550, PLC-2/30 with SD2, PLC-3, PLC-5 families, PLC-5/250, PLC scanner modules, SLC 500 with 1747-SN scanner p. 13
- SCANport products
- 1305, 1336 IMPACT, PLUS, PLUS II, FORCE and SPIDER drives, 1336 REGEN, 1394, SMC Dialog Plus, SMP-3, 1397, 1557, 2364F p. 13
- SCANport cables
- Male to male 1202-C03, 1202-C10, 1202-C30, 1202-C90 (1/3, 1, 3, 9 m); male to female 1202-H03, 1202-H10, 1202-H30, 1202-H90 p. 31
- Remote I/O cable
- Twinaxial 1770-CD Belden #9463 p. 32
- Termination
- 82 ohm resistor between terminals 1 and 2 of the Remote I/O connector, or 150 ohm where a device requires it; 82 ohm required at 230.4 kbps p. 32
- DIP switches
- SW1.3 to SW1.8 rack address; SW2.1 to SW2.2 starting module group; SW3.1 block transfer; SW3.4 to SW3.7 datalinks A to D p. 18
- LEDs
- Fault, SCANport STS, Health, Rem I/O ACT and Rem I/O STS p. 61
- Firmware
- 1.xx to 4.xx p. 1
What this manual walks you through
- Setting the DIP switches for rack address, baud rate, datalinks and fault action p. 18, 19
- Choosing SCANport and Remote I/O cables p. 31, 32
- Selecting a termination resistor for the Remote I/O link p. 32
- Mounting a 1203-GD1 or 1203-GK1 module on DIN rail p. 33
- Using datalinks to pass data between controller and drive p. 12
- Troubleshooting with the module LEDs p. 62
Good to know
- The module does not work with complementary I/O configurations. p. 17
- Firmware 4.01 modules used only for block transfer need switches SW 3.1 and SW 3.3 on and the rest of SW3 off. p. 17
- Keep total SCANport cable to 10 m (33 ft) or less between the product and all peripherals. p. 31
- Do not wire the Remote I/O link as a star; only two cables may meet at any wiring point. p. 32
- The modules cannot be repaired. p. 63
Questions this manual answers
What power does the 1203-GD1 need?
85 to 264V AC. The 24V DC version is the 1203-GK1. p. 14
What baud rates does the 1203-GD1 support?
57.6, 115.2 or 230.4 kbps on Remote I/O, chosen with switches SW2.7 and SW2.8. p. 18, 19
Which termination resistor does a 1203-GD1 Remote I/O link need?
An 82 ohm resistor unless a device on the link requires 150 ohm; at 230.4 kbps 82 ohm is required. p. 32
Which controllers work with the 1203-GD1?
Logix5550, PLC-2/30 with SD2, PLC-3, the PLC-5 families and PLC-5/250, PLC scanner modules, and SLC 500 with a 1747-SN scanner. p. 13
What cable connects the 1203-GD1 to the Remote I/O link?
Twinaxial 1770-CD Belden #9463, the only cable tested and approved for RIO and DH+. p. 32