The text of a manual · part 3 of 11
Bulletin 1203 Remote I/O Communications Module User Manual: Chapter 1
Pages 11 to 16 of 96, from Bulletin 1203 Remote I/O Communications Module User Manual
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1203-GD1
Page 11
Chapter
1
Overview Chapter Objectives
Chapter 1 provides an overview of the Remote I/O communications module (1203-GD1 module, 1203-GK1 module, and 1336-GM1 board). In this chapter, you will read about the following: • Function of the module. • Features of the module. • Compatible SCANport products and programmable controllers. • Parts and hardware of the module. • Steps for setting up the module. • Required tools and equipment.
Description of the Remote I/O Communications Modules
The Remote I/O communications module is an optional interface designed to provide a direct, digital link between an Allen-Bradley programmable controller and any one Allen-Bradley SCANport product. A module is required for each product that you want to connect to Remote I/O. There are three types of Remote I/O communications modules: Catalog Number 1203-GD1 1203-GK1 1336-GM1
Figure 1.1 1203-GD1 Module and 1203-GK1 Module
Enclosure NEMA Type 1 NEMA Type 1 Open
Required Power Supply 85 – 264V AC 24V DC +/- 10% Drive Supplied
Module and Board 1336-GM1 Board
Page 12
1–2
Overview
The 1203-GD1 and 1203-GK1 modules mount on a DIN rail. They connect to a SCANport product using a SCANport cable and to the Remote I/O link using a Remote I/O cable. The 1336-GM1 board mounts directly onto selected SCANport products. It connects to a SCANport product using an internal SCANport connector and to the Remote I/O link using a Remote I/O cable. Figure 1.2 shows how the modules connect SCANport products to the Remote I/O link. Figure 1.2 PLC-5
Remote I/O Link with Remote I/O Communications Modules
1305 Drive
PLUS Drive
SMC
1336GM1
1203-GD1
1203-GK1
Remote I/O Link
Features of the Communications Module
The 1203-GD1 module, 1203-GK1 module, and 1336-GM1 board let you connect SCANport products to Remote I/O links and devices. These modules feature the following: • DIP switches let you configure how the Remote I/O module operates before connecting it to the link. • User-configurable fault action DIP switches let you customize the module actions when communication errors occur. • LEDs report link, module, and SCANport product health. • Datalinks are supported in the module. Datalinks are a SCANport mechanism for transferring information between a controller and SCANport device. Each enabled datalink uses two words in the I/O image table unless it is truncated.
Page 13
Overview
Compatibility
1–3
SCANport Products Remote I/O modules are compatible with many SCANport products, including the following:
Product 1305 AC MICRO Drive➀ 1336 IMPACT™ Drive 1336 PLUS AC Drive 1336 PLUS II Drive 1336 FORCE™ Drive 1336 REGEN Line Regeneration Package 1336 SPIDER Drive 1394 AC Mult-Axis Motion Control System SMC Dialog Plus™ SMP-3 Smart Motor Protector 1397 Digital DC Drive 1557 Medium Voltage Drive 2364F Regenerative DC Bus Supply Unit
Number of Peripherals Supported 5 6➁ 6➁ 6➁ 6➁ 2 6➁ 5 1 2 5 5 6
I/O Words Minimum 0 0 0 0 0 0 0 0 0 0 0 0 0
Maximum➂ 8 8 8 8 8 2➄ 8 8 2➄ 2➄ 8 8 8
Module Use 1203-GD1 or 1203-GK1 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
1336-GM1 No Yes➃ Yes➃ Yes Yes➃ No Yes No No No No No No
➀ The Remote I/O modules are compatible with 1305 drives using firmware release 2.xx or greater. ➁ Lower horsepower products may not support a sixth peripheral. To connect multiple peripherals to a SCANport product, a port expander may be required. Refer to the product user manual to verify that it supports a sixth peripheral. ➂ Many SCANport products support 10 words of I/O (Command/Logic, Speed Reference, and four datalinks). Remote I/O, however, supports only 8 words of I/O. ➃ Drive must be B-frame or larger. If it is a 1336 FORCE drive, it must use a standard adapter board. ➄ Datalinks are not supported by this product.
If you intend to use datalinks to communicate with and control your SCANport product, verify that your SCANport product supports datalinks before enabling them in the module.
Controllers This Remote I/O communications module is compatible with many programmable controllers, including the following: • Logix5550 • PLC-2/30® with SD2 (module version 1.02 or later) • PLC-3® • PLC Classic Family, including the PLC-5/10 (only with 1771-SN in Discrete Mode), PLC-5/15™, PLC-5/25™ family • PLC Enhanced family, including the PLC-5/20™, PLC-5/30, PLC-5/40™, PLC-5/40L™, PLC-5/60™, PLC-5/60L™family, PLC-5/80™ • PLC-5/250™ • PLC scanner modules and subscanners • SLC 500™ with 1747-SN scanner
Page 14
1–4
Overview
Hardware Description
The hardware included with the module depends on the module that you have.
1203-GD1 and 1203-GK1 Modules The 1203-GD1 module and 1203-GK1 module share the same parts. Figure 1.3 illustrates these parts. Figure 1.3
Parts of the 1203-GD1 and 1203-GK1 Module
1
3
2 4
6 5
# 1
Part SCANport Connection
Description Standard SCANport 8-pin mini-DIN connector for the SCANport cable. 2 Power Supply Connections Connections for the power supply. Multiple connections allow daisy-chaining. The 1203-GD1 module uses 85 – 264V AC. The 1203-GK1 module uses 24V DC. 3 Remote I/O Connection Standard 3-pin Remote I/O connector. 4 LEDs Status indicators for the module, SCANport connection, and Remote I/O connection. Refer to Chapter 6. 5 DIP Switches Switches used to configure the module. Refer to Chapter 2. 6 DIN Rail Mount Mount for securely attaching and electrically grounding the module to a DIN rail. Not Remote I/O connector One 3-pin connector for connecting the Remote I/O cable to the module. Shown Not Termination Resistors Two termination resistors for terminating the I/O link at its physical ends. Refer to Chapter 3. Shown
Page 15
Overview
1–5
1336-GM1 Board Hardware Figure 1.4 illustrates the main parts of a 1336-GM1 board. Figure 1.4
Parts of the 1336-GM1 Board 4
3
1
2
# 1 2 3
Part SCANport Connection Remote I/O Connection LEDs
4
DIP Switches
Not Kit Shown
Description Internal 14-pin female SCANport connector. Standard 3-pin Remote I/O connector. Status indicators for the module, SCANport connection, and Remote I/O connection. Refer to Chapter 6. Switches used to configure the module. Refer to Chapter 2. Materials for mounting the board to the SCANport product. These material include one grounding wrist strap, four Phillips mounting screws, four stand-off nylon headers, one 3-pin Remote I/O connector, one snap-in comm housing with mounting instructions, and termination resistors.
Page 16
1–6
Overview
Required Tools and Equipment
The tools and equipment required, depend on if you are using a 1203-GD1 module, 1203-GK1 module, or 1336-GM1 board.
1203-GD1 or 1203-GK1 Module To install and configure a 1203-GD1 module or 1203-GK1 module, you need the following: • Remote I/O communications module (1203-GD1 or 1203-GK1). • 35 x 7.5 mm DIN rail. • Termination resistor(s). • Power source. • 1/8" flathead screwdriver. • Appropriate cables for SCANport and Remote I/O connections. Refer to Chapter 3. • Software such as RSLogix5, RSLogix500, or RSLogix5000 for programming the controller.
1336-GM1 Board To install and configure a 1336-GM1 board, you need the following: • Remote I/O communications board (1336-GM1). • A kit that includes one grounding wrist strap, four Phillips mounting screws, four stand-off nylon headers, one 3-pin connector, and one snap-in comm housing with mounting instructions (supplied with board). • #1 Phillips screwdriver. • Appropriate cable for the Remote I/O connection. Refer to Chapter 3. • Software such as RSLogix5, RSLogix500, or RSLogix5000 for programming the controller.
Overview of Setting Up the Module
To set up the Remote I/O communications module, you must perform the following tasks: 1. Read the safety precautions in this manual. 2. Configure the module using the DIP switches. Refer to Chapter 2. 3. Install the module or mount the board. Refer to Chapter 3. 4. Create a ladder logic program to control the SCANport product (Chapter 4) or send messages to it (Chapter 5).