For the Allen-Bradley 1203-GD1

Page 31

Chapter

3

Installing the Module Chapter Objectives

Chapter 3 provides the information that you need to install the module (1203-GD1 module, 1203-GK1 module, or 1336-GM1 board). In this chapter, you will read about the following: • Selecting cables. • Selecting a termination resistor. • Installing a 1203-GD1 or 1203-GK1 module. • Installing a 1336-GM1 board.

Selecting Cables

Refer to the following table to determine the required cables: If Installing: 1203-GD1, 1203-GK1 1336-GM1

Required Cables SCANport and Remote I/O Remote I/O

SCANport Cables When selecting the SCANport cable to connect a module to the SCANport product, you need to: • Use an Allen-Bradley SCANport cable. Refer to the table below: Male to Male Connection Male to Female Connection➀ Length Catalog Number Length Catalog Number 1/3 m 1202-C03 1/3 m 1202-H03 1m 1202-C10 1m 1202-H10 3m 1202-C30 3m 1202-H30 9m 1202-C90 9m 1202-H90 ➀ Cables with male to female connections are generally used as extension cables.

• •

Use 10 meters (33 feet) or less of cable between the SCANport product and all peripherals. Keep SCANport cables away from high power cables to guard against introducing noise into your system.

Important: SCANport cables lock into a connection. To remove a SCANport cable, you must push it in and then pull it out.

Page 32

3–2

Installing the Module

Remote I/O Cables Remote I/O communications modules are connected to Remote I/O links with twinaxial cable used for Remote I/O and Data Highway Plus (DH+) communications. When selecting a cable, remember the following: • Only 1770-CD Belden #9463 is tested and approved for RIO and DH+ installations. Using other cables is at your own risk. • The total cable length depends on the baud rate that you are using. Refer to the following table: Baud Rate 57.6 K 115.2 K 230.4 K

•

All three of the following conductors must be connected at each node. Color Blue Shield Clear

•

Selecting a Termination Resistor

Maximum Length 3,048 m (10,000 ft) 1524 m (5,000 ft) 762 m (2,500 ft)

Description 1 SH 2

Do not use a star topology. Only two cables may be connected at any wiring point. You can use a series topology and daisy-chain two wires at a point.

You must terminate both ends of a Remote I/O link to ensure proper operation. This termination is required only at the ends of the physical cable. Each Remote I/O link should have exactly two termination resistors. If the device that you connect is an end device on the Remote I/O link, it must be terminated. Refer to the following table to select a resistor. Important: You must use an 82 ohm external termination resistor if the link is operating at 230.4 kbps. Device Programmable Controller 1336-GM1 (Using Jumpers) 1203-GD1, 1203-GK1, or 1336-GM1 (Using an external termination resistor) ➀

Description Refer to its manual. Set J2 in position 1-2 for termination and 2-3 for no termination. Refer to Figure 3.8. The jumper enables a 150 ohm resistor➀. Connect a resistor between terminals 1 and 2 on the Remote I/O connector. Refer to Figure 3.4. Use an 82 ohm termination resistor unless a device requires a 150 ohm termination resistor➀.

The following scanners require 150 ohm termination resistors on the RIO link: 1771-SN, 1772-SD, 1772-SD2, 1775-SR, 1775-S4A, 1775-S4B, 6008-SQH1, and 6008-SQH. The following adapters require a 150 ohm termination resistors on the RIO link: 1771-AS, 1772-ASB (Series A), 1771-DCM. The following devices require a 150 ohm termination resistors on the RIO link: 1771-AF.

Page 33

Installing the Module

Installing a 1203-GD1 or 1203-GK1 Module

3–3

Required Tools and Equipment To install your module, you need the following tools and equipment: • Remote I/O communications module (1203-GD1 or 1203-GK1). • 35 x 7.5 mm DIN rail. • Appropriate cables for SCANport and Remote I/O connections. Refer to the “Selecting Cables” section in this chapter. • Termination resistor (if necessary). Refer to the “Selecting a Termination Resistor” section in this chapter. • 115 V/230 V AC or 24 V DC power supply.

Installing the 1203-GD1 or 1203-GK1 Module 1. Remove power from the Remote I/O link. 2. Hook the top lip of the module DIN rail mount onto the top of the DIN rail and then rotate the module onto the DIN rail. It snaps into a locked position. Figure 3.1

Mounting a Module onto the DIN Rail

Page 34

3–4

Installing the Module

3. Connect a SCANport cable (1202-Cxx) to a module and product. Important: For the location of the SCANport connector on your product, refer to its user manual. If you are using a port expander, refer to its documentation. Figure 3.2

Connecting the SCANport Cable SCANport Product

.

Module

4. Connect a Remote I/O cable to the module and link or controller. Figure 3.3

Connecting the Remote I/O Cable PLC Controller

Blue Shield Clear

.. .

1 SH 2

Module

Clear Shield Blue

2 SH 1

Page 35

Installing the Module

3–5

5. If the module is the last device on the Remote I/O link, connect the termination resistor. If the Remote I/O link uses 230Kbps, you must use an 82 ohm termination resistor. Figure 3.4

Connecting the Termination Resistor

2 Clear Shield

I50 Ohm or 82 Ohm 1 watt +/-10%

Sh

Blue

To Another Remote I/O Link Device

1

6. Connect the power supply to the module. Figure 3.5

Connecting the Power Supply

1203-GD1 Module

Hi 115V/230V AC Low 115V/230V AC

GND

L N G

1203-GK1 Module

24V DC Supply

+ G

+ -

GND

7. Apply power to the Remote I/O link. The module is now installed. Its LEDs are as follows: LED Status Fault Red (Blinking) SCANport STS Green or amber➀ ➁ Health Green or amber➁ Rem I/O ACT Off Rem I/O STS Off ➀ This LED is off if the module use firmware 2.xx or lower. ➁ Early versions of the module use amber LEDs.

You are now ready to create a ladder logic program. Important: If your LEDs are different, refer to Chapter 6.

Page 36

3–6

Installing the Module

Installing a 1336-GM1 Board

Required Tools and Equipment To install your 1336-GM1 board, you need the following tools and equipment: • Remote I/O communications board (1336-GM1). • A kit that includes one grounding wrist strap, four Phillips mounting screws, four stand-off nylon headers, and one snap-in comm housing with mounting instructions (supplied with board). • #1 Phillips screwdriver. • Appropriate cable for the Remote I/O connection. Refer to the “Selecting Cables” section in this chapter.

Installing the 1336-GM1 Communications Board The following instructions explain how to physically install a Remote I/O communications board.

!

!

ATTENTION: The 1336-GM1 communications board contains ESD (Electrostatic Discharge) sensitive parts. Static control precautions are required when installing, testing, or servicing this board. Device malfunction may occur if you do not follow ESD control procedures. If you are not familiar with static control procedures, refer to Rockwell Automation Publication 8000-4.5.2, Guarding Against Electrostatic Damage, or other applicable ESD protection handbook. ATTENTION: Remove all power from the SCANport product before installing the 1336-GM1 board. Failure to disconnect power may result in death or serious injury. Verify all power is removed before installing the 1336-GM1 board.

Important: If you are attaching the communications board to a 1336 PLUS II, refer to the one-page insert included with the kit for mounting instructions. 1. Remove power from the SCANport product, and verify that it is not holding power. 2. Remove power from the Remote I/O link. 3. Put on the grounding wrist strap.

Page 37

Installing the Module

3–7

4. Screw the four stand-off nylon headers into the appropriate spaces on the drive main control board. Figure 3.6

Mounting the Open Style Communications Board

5. Insert the SCANport connector into the 14-pin SCANport header on the control board. The DIP switches should be facing you. 6. Screw the board securely into place, being careful not to overtighten the four screws. 7. Connect the Remote I/O cable. Figure 3.7

Connecting the Remote I/O Cable PLC Controller

Blue Shield Clear

.. .

1 SH 2

SCANport Product

J4 Blue Shield Clear

1 SH 2

. 1336-GM1 Board

Page 38

3–8

Installing the Module

8. If the module is the last device on the Remote I/O link, either user the internal termination resistor (J2) or an external termination resistor. If the Remote I/O link uses 230Kbps, you must use an external 82 ohm termination resistor. Important: Use only one type of termination (internal or external), Figure 3.8

Using a Termination Resistor

External Termination

1 Blue Shield

Sh

Clear To Another Remote I/O Link Device

2

I50 Ohm or 82 Ohm 1 watt +/-10%

3 2 1

J2

Internal Termination

Not Last Device, (Factory Default) 3 2

1

Last Device on link, Termination Resistor Inserted 3 2 1 Enables 150 ohm Termination Resistor

9. Reapply power to the SCANport product. 10. Apply power to the Remote I/O link. The module is now installed. Its LEDs are as follows: LED Status Fault Red (Blinking) SCANport STS Green or amber➀ ➁ Health Green or amber➁ Rem I/O ACT Off Rem I/O STS Off ➀ This LED is off if the module use firmware 2.xx or lower. ➁ Early versions of the module use amber LEDs.

You are now ready to create a ladder logic program. Important: If your LEDs are different, refer to Chapter 6.