Page 1 of SLC 100 Programmable Controller Processor Unit, Catalog Nos. 1745-LP101, -LP102, -LP103, -LP104

Manual · Allen-Bradley

SLC 100 Programmable Controller Processor Unit, Catalog Nos. 1745-LP101, -LP102, -LP103, -LP104

Manual12 pagesPDF 894 KB

Product data for the Allen-Bradley SLC 100 processor units 1745-LP101, -LP102, -LP103 and -LP104: features, wiring, specifications.

Download the PDF894 KB

Covers · 2 models

The models it covers

Summary

What is in it

Allen-Bradley product data for the SLC 100 Programmable Controller processor unit in its four versions (1745-LP101, -LP102, -LP103, -LP104). It describes the controller and its peripherals (EEPROM memory module, pocket programmer, personal computer software, TCAT and I/O expansion units), the processor unit's terminals, indicators and switches, installation and mounting, line, input and output wiring, output contact protection, and general, input and output specifications.

Its parts

  1. The SLC 100 Programmable Controller
  2. The Processor Unit
  3. Installation Considerations
  4. Mounting
  5. Line Wiring Connections
  6. Input Wiring Connections
  7. Output Wiring Connections
  8. Output Contact Protection
  9. General Specifications
  10. Input Specifications
  11. Output Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Product data sheet (publication 1745-2.1, October 1987) for the SLC 100 programmable controller processor unit, covering catalog numbers 1745-LP101, -LP102, -LP103 and -LP104. It explains the unit's features and indicators, mounting, line, input and output wiring, and output contact protection. It ends with general, input and output specifications.

What it is
SLC 100 processor unit: CPU, battery-backed CMOS RAM, power supply and 16 I/O circuits p. 1
Built-in I/O
10 inputs and 6 relay (hard contact) outputs p. 2
Maximum I/O
112 I/O circuits with SLC 100 or SLC 150 expansion units p. 1
Input voltage
1745-LP101: 85-132VAC, 50/60 Hz; 1745-LP102: 170-265 VAC; 1745-LP103, -LP104: 10-30V p. 10
Output voltage
10-250 VAC (50/60 Hz) or 10-125 VDC, all versions p. 11
Output fusing
Bussman 3A, 250VAC slow blow or equivalent p. 11
Memory backup
Replaceable lithium battery, about 2-3 years p. 3
Program storage
Optional plug-in EEPROM memory module p. 3
Programming
Pocket programmer, or IBM-compatible PC software through an interface converter p. 1
Status LEDs
DC POWER, PC RUN, CPU FAULT, BATTERY LOW, FORCED I/O p. 2
Temperature
0 to 60 C operating, -40 to 85 C storage p. 9
Humidity
5 to 95% without condensation p. 9
Wire size
#14 - #24 AWG stranded p. 9

What this manual walks you through

  • Identifying the terminals, LEDs, switch and ports on the processor unit p. 2, 3
  • Planning the enclosure, power and safety circuits p. 4
  • Mounting the unit with screws or on a DIN rail p. 4
  • Making the line wiring connections p. 5
  • Wiring input devices p. 6
  • Wiring output devices p. 7
  • Protecting output contacts from inductive loads p. 8
  • General, input and output specifications p. 9, 10, 11

Good to know

  • Do not jumper the 115VAC and 230VAC neutral terminals together, or an unused neutral to chassis ground. p. 5
  • On the 1745-LP103 and -LP104 the 2 mA OFF state leakage applies to inputs 1 and 2 only; inputs 3 to 10 need a 5.6K ohm, 1/2 watt resistor to COM. p. 10
  • An EEPROM memory module is recommended to guard against program loss from battery drain, malfunction or noise. p. 3
  • If line voltage is present but the DC POWER LED is off, the input power fuse may be blown. p. 2

Questions this manual answers

How many inputs and outputs does the 1745-LP101 have?

The processor unit has 10 inputs and 6 relay outputs. Expansion units can raise the total to 112 I/O circuits. p. 1, 2

What input voltage does the 1745-LP101 accept?

Its inputs take 85-132VAC at 50/60 Hz. p. 10

How long does the SLC 100 memory backup battery last?

The replaceable lithium battery backs up the CMOS RAM for about 2 to 3 years. p. 3

What does the CPU FAULT light mean on an SLC 100?

The processor has found an error in the CPU or memory, and operation stops automatically. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1745-2.1, SLC 100 Programmable Controller Processor Unit1
    1. The SLC 100 Programmable Controller1
    2. The Processor Unit1
    3. Installation Considerations4
    4. Mounting4
    5. Line Wiring Connections5
    6. Iput Wiring Connections6
    7. Output Wiring Connections7
    8. Output Contact Protection8
    9. General Specifications9
    10. Input Specifications10
    11. Output Specifications11
    12. BackCover12

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 127-12

The file

Revision and size

RevisionPublication 1745-2.1, October 1987
PublisherAllen-Bradley
Pages12
PDF894 KB
TextText from the PDF itself; page 12 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12