The text of a manual · part 2 of 2
SLC 100 Programmable Controller Processor Unit, Catalog Nos. 1745-LP101, -LP102, -LP103, -LP104, pages 7 to 12
Pages 7 to 12 of 12
The original document is the PDF (894 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1745-LP101 and Allen-Bradley 1745-LP103
Page 7
7
Processor Unit - SLC 100 Output Wiring Connections
Wiring connections for output devices are shown below. Note that the diagram shows the internally-connected output contacts and parallelRC networks. The RC networks guard against possible damageby transients from external output devices. External connectionsare shown for outputs11,15, and 16. We’ve added a suppressor in parallel with two of the external devices for the purposeof contact protection. Contact protectionis discussed on Page8. Since the output contacts are isolated from each other, each output circuit can be wired independently, with own its ground return. You can applya different voltage in each output circuit, as your application might require. Power or ground wires can be jumpered betweenof sets terminals if desired. You should provide appropriate fusing to protect the output devices and wiring from short circuits and overload conditions.
I
Solenoid 15VAC 1 L l (Hi)
r
I
To limit theeffects of leakage current, use a loading resistor across the load as shown at the right.
k L2 (Lo)
5VAC 1
1
L1 (Hi)
Resistor 115VAC: 1 5 K o h r n , 2 w a t t 230VAC: 15K ohm, 5 w a t t
I
I
Page 8
8
Processor Unit - S l C 100 Output Contact Protection
Inductive output devices suchas motor starters andsolenoids may require thatyou use some type of surge suppression to protect the output contacts. Examples are shownbelow. These surge suppression circuits are connected directly across the output can device. The effect is to reduce arcingof the output contacts (arcing be voltage which occurs whenan inductive caused by the high transient device is switched offp. Suitable surge suppression methods for inductive AC output devices include a varistor, anRC network, and an Allen-Bradley surge suppressor. These components must be appropriately rated to suppress the switching transient characteristic of the particular inductive device. For inductive DC output devices,a diode is suitable.A 1N4004 diode is acceptable for most applications. A surge suppressor can also be used (refer to the User’s Manual). We recommend that you locate the suppression deviceas close as possible to the outputdevice. Suppressors recommended for use with Allen-Bradley relays, contactors, and motor starters are listed in the User’s Manual.
Page 9
9
Processor Unit - SLC 100
General Specifications
Shift Register: 8-bit groups. Noise Immunity: NEMA Standard ICs 2-230. Vibration: DIN Rail Mounting: 0.006 inch peak t o peak displacement, 1 .Og peak (max) acceleration, 1 Hr/axis. Screw Fastener Mounting: 0.01 5 inch peak t o peak displacement, 2.59 peak(max) acceleration,1 Hr/axis. Ambient Temperature Rating: 0" t o 60" C (operating). - 40"o 85" C (storage). Humidity Rating: 5 t o 95% (without condensation). Wiring: #14 - #24 AWG stranded. 3/64" insulation (max).
Page 10
10
Processor Unit - SLC 100 Input SpeCifkatiOnS
Input specifications for the various processor unit versionsare shown below. to The 2 mA OFF state leakage current specification allows direct interface solid state sensing devices. Note that the mA 2 OFF state leakage current for 24VAC circuits applies to inputs 1and 2 only. When required, you can also achieve 2a mA OFF state leakage currentfor inputs 3 thru 10, as indicated in the specifications. All input circuits include optical isolationwell as as filtering and surge by transients from external input suppression to guard against damage devices.
ON State Voltage Range and Frequency: 1745-LP101: 85-1 32VAC, 50/60 HZ. 1745-LP102: 170-265 VAC, 50/60 HZ. 1745-LP103, -LP104: 10-30V, AUDC. Maximum OFF State Voltage: 1745-LP101:35V. 1745-LP102: 50V. 1745-LP103, -LP104: 5V. '
Maximum OFF State Leakage Current: 1745-LP101,-LP102: 2 mA. 1745-LP103, -LP104: ZmA, inputs 1 and 2 only. To achieve a 2 mA 0,FF state leakage current for inputs 3 thru 10, connect a 5.6KO, 1/2 watt (min) resistor from the input terminal to the common terminal. Nominal Input Current: 1745-LP101, -LP102: 8 mA. 1745-LP103, -LP104: Inputs 1 and 2- 8 mA a t 12V, 18 mA a t 24V. Inputs 3 thru 10- 6 mA a t 12V, 14 mA at 24V. Specifications applying t o all Catalog Numbers: input Filter Time Delay: 10-25 msec. Electrical-Optical Isolation: 1500 volts between input voltage and control logic.
Page 11
11
Processor Unit - SLC 100 eationS
Output specifications for all versionsof the processor unit are shown below. Internal output circuitry includes surge suppression to guard against possible damage by transients from external outputdevices. We of contact protection when recommend that you also use some type switching inductive load devices. Refer to Pages 7 and 8.
Voltage Range and Frequency: 10-250 VAC (50/60 HZ), 10-125 VDC. Contact Ratings:
240VAC l2OVAC
0.75A 7.5A 2,5A 1.5A 15A
1800VA
180VA
125VDC
0.22A
1 .OA
28VA
24VDC
1.2A
2.5A
28VA
Contact Resistance: 20 mR (typical). Electrical Isolation: 2000 volts. OFF State Leakage Current: 2 mA (AC voltage only). To limit leakage current use a loading resistor across the loadas shown on Page7. Output Fusing for OverloadProtection: Bussman 3A, 250VACslow blow or equivalent. Internal RC Network Values: R = 120 ohms, C = 0.022 microfarad.
Page 12
(2) ALLEN-BRADLEY
WO” 4 ROCKWELL INTERNATIONAL COMPANY industrial Control Group Milwaukee, Wisconsin 53204