The text of a manual · part 18 of 70

SLC 500 Instruction Set Reference Manual, pages 171 to 180

Pages 171 to 180 of 694

The original document is the PDF (7.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L514

Page 171

Block Transfer Instructions

8-11

Comparison to the PLC-5 BTR and BTW BTR/BTW in SLC processors are quite similar to the instructions in the PLC-5. However, some differences exist between them, as shown in the table below.

Table 8.6 Block Transfer Comparison Parameter

SLC

PLC-5

Control Block

3-element integer (N) type

5-element integer (N) type or 1-element block transfer (BT) type.

EN (Enable Bit)

Follows BT rung state.

Gets set when BT rung goes true. Remains set until the BT finishes or fails, and the BT rung goes false.

NR (No Response bit)

None

This bit is in control block word 0 bit 9.

CO (Continuous bit)

None

This bit is in control block word 0 bit 11.

FILE (File Number)

None

This word is control block word 3.

ELEM (Element Number)

None

This word is control block word 4.

Error Codes

7 error codes

11 error codes

BTR/BTW number limitation for one scanner/channel

32

64

BT Status Bits

Can only change when BT rung is scanned.

Can change at any point in the program scan.

IMPORTANT

Do not manipulate the I/O image words of the RIO scanner for modules you are block transferring to. These words are used by the RIO scanner and the remote device as block transfer handshake bits. Any manipulation of them by the user program while a block transfer is in progress causes the block transfer to fail.

Publication 1747-RM001G-EN-P - November 2008

Page 172

8-12

Block Transfer Instructions

Notes:

Publication 1747-RM001G-EN-P - November 2008

Page 173

Chapter

9

Proportional Integral Derivative Instruction

This chapter describes the Proportional Integral Derivative (PID) instruction.

This is an output instruction that controls physical properties such as temperature, pressure, liquid level, or flow rate using process loops.

Overview PID PID Control Block Process Variable Control Variable Control Block Length Setup Screen

The PID instruction normally controls a closed loop using inputs from an analog input module and provides an output to an analog output module. For temperature control, you can convert the analog output to a time proportioning on/off output for driving a heater or cooling unit. An example appears on pages 9-30 through 9-31.

N18:0 N18:23 N18:24 23

Fixed SLC SLC SLC SLC SLC 5/01 5/02 5/03 5/04 5/05 •

•

Output Instruction

The PID Concept

•

•

The PID instruction can be operated in the timed mode or the STI mode. In the timed mode, the instruction updates its output periodically at a user-selectable rate. In the STI mode, the instruction should be placed in an STI interrupt subroutine. It then updates its output every time the STI subroutine is scanned. The STI time interval and the PID loop update rate must be the same in order for the equation to execute properly.

PID closed loop control holds a process variable at a desired set point. A flow rate/fluid level example is shown below.

Feed Forward or Bias Set Point

∑

Error

Flow Rate

PID Equation

Process Variable

∑ Control Output

Level Detector Control Valve

1

Publication 1747-RM001G-EN-P - November 2008

Page 174

9-2

Proportional Integral Derivative Instruction

The PID equation controls the process by sending an output signal to the control valve. The greater the error between the setpoint and process variable input, the greater the output signal, and vice versa. An additional value (feed forward/bias) can be added to the control output as an offset. The result of PID calculation (control variable) drives the process variable you are controlling toward the set point.

The PID Equation

The PID instruction uses the following algorithm: Standard equation with dependent gains is shown below.

1 D ( PV ) Output = K C ( E ) + ---- ∫ ( E ) dt + T D ⋅ ---------------- + Feed Forward/Bias TI df

Standard Gains constants are listed in the following table.

Table 9.1 Standard Gain Constants Term

Range (Low to High)

Reference

Controller Gain KC

0.1 to 25.5 (dimensionless)(1)

Proportional

0.01 to 327.67 (dimensionless)(2)

Reset Term 1/TI

25.5 to 0.1 (minutes per repeat)(1) 327.67 to 0.01 (minutes per repeat)(2)

Integral

Rate Term TD

0.1 to 25.5 (minutes)(1)

Derivative

0.01 to 327.67 (minutes)(2) (1)

SLC 5/02 processors.

(2)

Applies to SLC 5/03 and higher processors PID ranges when bit Reset and Gain Range (RG) bit is set to 1.

The derivative term (rate) provides smoothing by means of a low-pass filter. The cutoff frequency of the filter is 16 times greater than the corner frequency of the derivative term.

Publication 1747-RM001G-EN-P - November 2008

Page 175

Proportional Integral Derivative Instruction

The PID Instruction

9-3

The figure below shows a PID instruction with typical addresses for these parameters entered.

PID PID Control Process Control Control

Block Variable Variable Block Length

N10:0 N10:28 N10:29 23

Place the PID instruction on a rung without any conditional logic. If a PID instruction goes false, the integral term is cleared.

TIP

The PID instruction is an integer-only type of PID algorithm and does not allow you to enter floating point values for any of its parameters. If you attempt to move a floating point value to one of the PID parameters using ladder logic, a floating point-to-integer conversion occurs.

During programming, enter the Control Block, Process Variable, and Control Variable addresses after you have placed the PID instruction on a rung.

Entering Parameters • Control Block is a file that stores the data required to operate the instruction. The file length is fixed at 23 words and should be entered as an integer file address. For example, an entry of N10:0 will allocate elements N10:0 through N10:22. The control block layout is shown on page 9-5. Do not write to control block addresses with other instructions in your program except as described later in this chapter. If you are re-using a block of data which was previously allocated for some other use, it is good practice to first zero the data.

TIP

Use a unique data file to contain your PID control blocks (for example, N10:0). This avoids accidental re-use of the PID control block addresses by other instructions in your program.

Publication 1747-RM001G-EN-P - November 2008

Page 176

9-4

Proportional Integral Derivative Instruction

• Process Variable PV is an element address that stores the process input value. This address can be the location of the analog input word where the value of the input A/D is stored. This value could also be an integer value if you choose to pre-scale your input value to the range 0 to 16383. • Control Variable CV is an element address that stores the output of the PID instruction. The output value ranges from 0 to 16383, with 16383 being the 100% on value. This is normally an integer value, so that you can scale the PID output range to the particular analog range your application requires.

Publication 1747-RM001G-EN-P - November 2008

Page 177

Proportional Integral Derivative Instruction

PID Control Block Layout

9-5

The control block length is fixed at 23 words and should be programmed as an integer file. PID instruction flags (word 0) and other parameters are listed in the following table.

Table 9.2 Control Block Structure 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

EN

RA(1)

DN

PV

SP

LL

UL

DB

DA(2)

TF

SC

RG(2)

OL(3)

CM(3)

AM(3)

TM(3)

Word 1

PID Sub Error Code (MSbyte)

Word 2

Setpoint SP

Word 3

Gain Kc

Word 4

Reset Ti

Word 5

Rate Td

Word 6

Feed Forward/Bias

Word 7

Setpoint Max (SMax)

Word 8

Setpoint Min (SMin)

Word 9

Deadband

Word 10

Internal Use Do Not Change

Word 11

Output Max

Word 12

Output Min

Word 13

Loop Update

Word 14

Scaled Process Variable

Word 15

Scaled Error SE

Word 16

Output CV% (0 to 100%)

Word 17

MSW Integral Sum

Word 18

LSW Integral Sum

Word 19

Internal Use Do Not Change

Word 20

Internal Use Do Not Change

Word 21

Internal Use Do Not Change

Word 22

Internal Use Do Not Change

(1)

Applies to SLC 5/03 and higher processors with OS Series C FRN 11 and higher firmware.

(2)

Applies to the SLC 5/03 and higher processors.

(3)

You may alter the state of these values with your ladder program.

ATTENTION

Do not alter the state of any PID control block value unless you fully understand its function and related effect on your process.

Publication 1747-RM001G-EN-P - November 2008

Page 178

9-6

Proportional Integral Derivative Instruction

Controller Gain (Kc) Table 9.3 Controller Gain Parameter Tuning Parameter Descriptions

Address

Data Format Range

Type

KC - Controller Gain

Word 3 word (INT)

control

0 to 32,767

User Program Access read/write

Gain Kc (word 3) is the proportional gain, ranging from 0 to 3276.7 (when RG = 0), or 0 to 327.67 (when RG = 1). Set this gain to one-half the value needed to cause the output to oscillate when the reset (Ti) and rate terms (Td) (below) are set to zero.

TIP

Controller gain is affected by the reset and gain range (RG) bit. For information, see Reset and Gain Enhancement Bit (RG) on page 9-10.

Reset Term (Ti) Table 9.4 Reset Term Parameter Tuning Parameter Address Descriptions TI - Reset Term - Ti Word 4

Data Range Format word 0 to 32,767 (INT)

Type control

User Program Access read/write

Reset Term Ti (word 4) is the Integral gain, ranging from 0 to 3276.7 (when RG = 0), or 327.67 (when RG = 1) minutes per repeat. Set the reset time equal to the natural period measured in the above gain calibration. A Kc value of 1 adds the maximum integral term into the PID equation.

TIP

Publication 1747-RM001G-EN-P - November 2008

Reset term is affected by the reset and gain range (RG) bit. For information, see Reset and Gain Enhancement Bit (RG) on page 9-10.

Page 179

Proportional Integral Derivative Instruction

9-7

Rate Term (Td) Table 9.5 Rate Term Parameter Tuning Parameter Address Descriptions TD - Rate Term - Td Word 5

Data Format Range

Type word (INT)

control

0 to 32,767

User Program Access read/write

Rate Td (word 5) is the Derivative term. The adjustment range is 0 to 327.67 minutes. Set this value to 1/8 of the integral gain Ti.

TIP

This word is not affected by the reset and gain range (RG) bit. For information, see Reset and Gain Enhancement Bit (RG) on page 9-10.

Feed Forward/Bias Applications involving transport lags may require that a bias be added to the CV output in anticipation of a disturbance. This bias can be accomplished using the processor by writing a value to the Feed Forward/Bias element, the seventh element (word 6) in the control block file (See page 9-5.) The value you write is added to the output, allowing a feed forward action to take place. You may add a bias by writing a value between -16383 and +16383 to word 6 with your programming terminal or ladder program.

Mode (TM) Table 9.6 Mode Bit Parameter Tuning Parameter Descriptions TM - Mode

Address

Data Format Word 0, Bit 0 binary

Range

Type

0 or 1 control

User Program Access read/write

The mode bit specifies when the PID is in timed mode (1) or STI mode (0). This bit can be set or cleared by instructions in your ladder program. When set for timed mode, the PID executes and updates the CV at the rate specified in the loop update parameter (word 13).

Publication 1747-RM001G-EN-P - November 2008

Page 180

9-8

Proportional Integral Derivative Instruction

When set for STI mode, the PID executes and updates the CV every time the PID instruction is scanned in the control program. When you select STI, program the PID instruction in the STI interrupt subroutine. The STI routine should have a time interval equal to the setting of the PID “loop update” parameter. Set the STI period in word S:30. For example, if the loop update time contains the value 10 (for 100 ms), then the STI time interval must also equal 100 (for 100 ms).

TIP

When using timed mode, your processor scan time should be at least ten times faster than the loop update time to prevent timing inaccuracies or disturbances.

Loop Update Table 9.7 Loop Update Parameter Tuning Parameter Descriptions

Address

Data Format Range

Type

Loop Update

Word 13 word (INT)

control

1 to 1024

User Program Access read/write

The loop update (word 13) is the time interval between PID calculations. The entry is in 0.01 second intervals. Enter a loop update time five to ten times faster than the natural period of the load. The natural period of the load is determined by setting the reset and rate parameters to zero and then increasing the gain until the output begins to oscillate. When in STI mode, this value must equal the STI time interval value loaded in S:30. The valid range is 0.01 to 10.24 seconds. See page 11-12 for help entering STI setpoint.

Deadband Table 9.8 Deadband Parameter Tuning Parameter Descriptions DB - Deadband

Publication 1747-RM001G-EN-P - November 2008

Address Word 9

Data Format word (INT)

Range

Type

0 to 32,767 control

User Program Access read/write