Page 1 of SLC 500 Instruction Set Reference Manual

Manual · Allen-Bradley

SLC 500 Instruction Set Reference Manual

Manual694 pagesPDF 7.2 MB

Instruction set reference manual for SLC 500 programmable controllers, from the 1747-L20x fixed units to the 1747-L553 processor.

What this file really is

The old site listed this file as a manual for the Allen-Bradley 1746-HS, 1746-IA16 and 13 more models. The file is named as a 1746-HS reference manual, but it is the general SLC 500 Instruction Set Reference Manual and does not mention the 1746-HS.

Download the PDF7.2 MB

Names · 1 model

The models it names

Filed with · 14 models

Also filed with these models on the old site

Summary

What is in it

The reference manual for the SLC 500 instruction set, for anyone who designs, programs or troubleshoots SLC 500 control systems. It covers processor data files, then every ladder logic instruction: bit, timer and counter, comparison, math, data handling, program flow, sequencer, block transfer, PID and ASCII instructions. Later chapters explain interrupt routines, communication instructions and channels, passthru, messaging examples and fault troubleshooting, with appendices on the status file, memory usage and addressing.

Its parts

  1. Processor Files
  2. Basic Instructions
  3. Comparison Instructions
  4. Math Instructions
  5. Data Handling Instructions
  6. Program Flow Instructions
  7. Application Specific Instructions
  8. Block Transfer Instructions
  9. Proportional Integral Derivative Instruction
  10. ASCII Instructions
  11. Understanding Interrupt Routines
  12. SLC Communication Instructions
  13. SLC Communication Channels
  14. SLC Passthru Communications
  15. Troubleshooting Faults

From the manual

Key facts from this manual

Each line names its page in the PDF.

Rockwell Automation's SLC 500 Instruction Set Reference Manual (publication 1747-RM001G-EN-P, November 2008) for the SLC 500 processors, catalog numbers 1747-L20x, -L30x, -L40x, -L511, -L514, -L524, -L531 to -L533, -L541 to -L543 and -L551 to -L553. It explains processor data files, addressing, the ladder logic instruction set and the processor fault codes with their causes and fixes. It is a processor programming reference, not a manual for the 1746-HS or the 1746 I/O modules the site also files it under.

Read for this summary: pages 1 to 5, 23 to 27 and 483 to 492 of 694.

What it is
Reference for SLC 500 controllers: status file functions and the instructions used in ladder logic programs p. 23
Processors covered
1747-L20x, -L30x, -L40x, -L511, -L514, -L524, -L531, -L532, -L533, -L541, -L542, -L543, -L551, -L552, -L553 p. 1
Publication
1747-RM001G-EN-P, November 2008 p. 2
Memory layout
Data files and program files; data files 9 to 255 can be bit, timer, counter, control or integer files (float, string and ASCII on SLC 5/03 and higher) p. 25
I/O addressing
Slot 0 holds the processor; I/O slots are numbered 1 to 30, addressed as O:e.s/b and I:e.s/b p. 26
Bit file B3
Up to 256 one-word elements, 4096 bits p. 27
Fault code types
Powerup, going-to-run, run and user program instruction errors, each with hex code, cause and action p. 485
Error 0001
NVRAM error, from noise, lightning, poor grounding or power, or loss of battery or capacitor backup p. 485
Errors 0003 and 0007
Memory module corrupted: reprogram it, and replace it if the error persists p. 485
Errors 0010 and 0018
Processor revision or operating system too old for the program; an upgrade kit is needed p. 486, 488
Error 0021
Power lost on an expansion I/O chassis p. 489
Error 0022
User watchdog scan time exceeded: raise the watchdog time (S:3H) or fix a program loop p. 489
Nested subroutines
At most 4 levels (8 on a 5/02 or 5/03); more gives error 0030 p. 491
Error 003B
Motherboard and daughter card firmware do not match; flash upgrade both as a pair p. 492

What this manual walks you through

  • Looking up processor fault codes, causes and corrective actions p. 483, 485
  • Addressing output and input data files p. 26
  • Addressing bits and words in the status file p. 27
  • Clearing faults automatically at powerup p. 483
  • Reloading a program from a memory module with the autoload bits p. 483
  • Declaring an application-specific major fault p. 483
  • Clearing faults manually p. 484
  • Using a user fault routine to recover from a fault p. 484
  • Finding the related SLC 500 installation manuals p. 24

Good to know

  • On SLC 5/03 and higher, clearing the fault bits with the keyswitch in RUN puts the processor straight into Run mode. p. 484
  • The user fault routine does not run for non-user faults. p. 484
  • An over-voltage or over-current power supply can show up as I/O error codes, with the power supply LED off. p. 489
  • Error 0021 is the only error code that clears itself. p. 489
  • Indexed addressing errors 0029 and 002A cannot be fixed by writing to the index register word. p. 490

Questions this manual answers

What does SLC 500 error code 0022 mean?

The user watchdog scan time was exceeded; raise the watchdog timeout in S:3H or fix a program caught in a loop. p. 489

What is SLC 500 fault 0001?

An NVRAM error, caused by noise, lightning, poor grounding or power, or loss of battery or capacitor backup; correct it, reload the program and run. p. 485

How do I clear a major fault on an SLC 5/03?

Clear S:1/13 and the error bits with a programming device, or on SLC 5/03 and higher toggle the keyswitch from RUN to PROGram and back to RUN. p. 484

Does this manual cover the 1747-L514 processor?

Yes. The 1747-L514 is among the catalog numbers on the cover. p. 1

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. SLC 500 Instruction Set Reference Manual1
    1. Important User Information2
    2. Summary of Changes3
    3. Preface23
    4. 1 - Processor Files25
    5. 2 - Basic Instructions37
    6. 3 - Comparison Instructions57
    7. 4 - Math Instructions63
    8. 5 - Data Handling Instructions97
    9. 6 - Program Flow Instructions127
    10. 7 - Application Specific Instructions137
    11. 8 - Block Transfer Instructions161
    12. 9 - Proportional Integral Derivative Instruction173
    13. 10 - ASCII Instructions205
    14. 11 - Understanding Interrupt Routines233
    15. 12 - SLC Communication Instructions267
    16. 13 - SLC Communication Channels331
    17. 14 - SLC Passthru Communications431
    18. 15 - Messaging Examples447
    19. 16 - Troubleshooting Faults483
    20. A - SLC 5/03 (OS30x), SLC 5/04 (OS40x) and SLC 5/05 (OS50x) Firmware History499
    21. B - SLC Status File521
    22. C - Memory Usage581
    23. D - Programming Instruction References601
    24. E - Data File Organization and Addressing623
    25. F - Number Systems649
    26. G - Application Example Programs655
    27. H - Supported Read/Write Commands681
    28. Index683
    29. Back Cover694

From the PDF’s own bookmarks.

The whole text · 70 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160
  17. Pages 161 to 170161-170
  18. Pages 171 to 180171-180
  19. Pages 181 to 190181-190
  20. Pages 191 to 200191-200
  21. Pages 201 to 210201-210
  22. Pages 211 to 220211-220
  23. Pages 221 to 230221-230
  24. Pages 231 to 240231-240
  25. Pages 241 to 250241-250
  26. Pages 251 to 260251-260
  27. Pages 261 to 270261-270
  28. Pages 271 to 280271-280
  29. Pages 281 to 290281-290
  30. Pages 291 to 300291-300
  31. Pages 301 to 310301-310
  32. Pages 311 to 320311-320
  33. Pages 321 to 330321-330
  34. Pages 331 to 340331-340
  35. Pages 341 to 350341-350
  36. Pages 351 to 360351-360
  37. Pages 361 to 370361-370
  38. Pages 371 to 380371-380
  39. Pages 381 to 390381-390
  40. Pages 391 to 400391-400
  41. Pages 401 to 410401-410
  42. Pages 411 to 420411-420
  43. Pages 421 to 430421-430
  44. Pages 431 to 440431-440
  45. Pages 441 to 450441-450
  46. Pages 451 to 460451-460
  47. Pages 461 to 470461-470
  48. Pages 471 to 480471-480
  49. Pages 481 to 490481-490
  50. Pages 491 to 500491-500
  51. Pages 501 to 510501-510
  52. Pages 511 to 520511-520
  53. Pages 521 to 530521-530
  54. Pages 531 to 540531-540
  55. Pages 541 to 550541-550
  56. Pages 551 to 560551-560
  57. Pages 561 to 570561-570
  58. Pages 571 to 580571-580
  59. Pages 581 to 590581-590
  60. Pages 591 to 600591-600
  61. Pages 601 to 610601-610
  62. Pages 611 to 620611-620
  63. Pages 621 to 630621-630
  64. Pages 631 to 640631-640
  65. Pages 641 to 650641-650
  66. Pages 651 to 660651-660
  67. Pages 661 to 670661-670
  68. Pages 671 to 680671-680
  69. Pages 681 to 690681-690
  70. Pages 691 to 694691-694

The file

Revision and size

RevisionPublication 1747-RM001G-EN-P, November 2008
PublisherRockwell Automation
Pages694
PDF7.2 MB
TextText from the PDF itself; page 364 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 694

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 694
Page 2
Page 2of 694
Page 3
Page 3of 694