Page 611
Programming Instruction References
D-11
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
LFL(3)
LIFO Load source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M(4)
-32,768 to 32,767
LIFO array indexed direct indexed indirect
O, I, S, B, N, A none
LIFO control direct
R none
LFU(3)
LIM(3)
LN(2)
LOG(2)
LIFO Unload
Limit Test (circ)
Natural Log
Log to the Base 10
MCR
Master Control Relay
MEQ
Mask Compare Equal To
MOV
Move length
1 to 128 position
0 to 127
LIFO array indexed direct indexed indirect
O, I, S, B, N, A none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M(4)
none
LIFO control direct
R none length
1 to 128 position
0 to 127 low limit direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max test direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max high limit direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 compare direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
Publication 1747-RM001G-EN-P - November 2008
Page 612
D-12
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
MSG (5/02 only)
Message read/write
0=read,1=write target device
2=500CPU, 4=485CIF control block
Valid Addressing Mode(s)
direct
Valid File Types
N control block length local address message length
Publication 1747-RM001G-EN-P - November 2008 none 7 direct
O, I, S, B, T, C, R, N, A target node target address
Immediate Values none 0 to 31 direct
O, I, S, B, T, C, R, N, A
0 to 255
T, C, R
1 to 13
I, O, S, B, N
1 to 41
Page 613
Programming Instruction References
D-13
Table D.3 Available Addressing Modes (Continued) Instruction
Description
MSG Message (5/03, 5/04, and 5/05(7))
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values type
64=peer-to-peer read/write
0=read, 1=write target device
2=500CPU, 4=485CIF, 8=PLC5 local/remote
16=local, 32=remote control block direct
N none control block length
14(8)
channel number
5/03 and 5/04: 0 or 1 5/05: 0 only target node
0 to 31, 0 to 254 if 485CIF remote bridge link ID
0 to 254, 0 when local remote bridge node address
0 to 254, 0 when local local bridge node address
0 to 254, 0xFFFF when local local file address direct
O, I, S, B, T, C, R, N, F, A, ST, M(9)
none target file address direct
O, I, S, B, T, C, R, N, F, A, ST, M(9)
0 to 255 message length
O, I, B, N, A(9)
1 to 103
S(9)
5/03 and 5/05: 1 to 83 5/04: 1 to 164
F(9)
1 to 51
T
1 to 34 (if PLC5: 1 to 20)
C, R
1 to 34
ST(9)
2 (if PLC5: 1)
message timeout
0 to 255 (SLC 5/05-23 seconds, read only)
Publication 1747-RM001G-EN-P - November 2008
Page 614
D-14
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
MSG (5/05 Ethernet)
Message type
64=peer-to-peer read/write
0=read, 1=write target device
2=500CPU, 4=485CIF, 8=PLC5 local
16=local control block
Valid Addressing Mode(s)
direct
Valid File Types
N
Immediate Values none control block length
51 (93 if logical ASCII addressing is used)
channel number
1 (Ethernet)
not applicable target node, remote bridge link ID, local and remote bridge node address IP address (ww.xx.yy.zz) local file address any legal IP address direct
O, I, S, B, T, C, R, N, F, A, ST, M none target file address direct
O, I, S, B, T, C, R, N, F, A, ST, M
0 to 255 message timeout (1)
Supported only by SLC 5/03 (OS301 and higher), SLC 5/04, and SLC 5/05 processors.
(2)
Supported only by SLC 5/03 (OS302), and SLC 5/04 (OS401), and SLC 5/05 processors.
(3)
Not supported by SLC 5/01 processors and Fixed controllers.
(4)
Indexed addressing is not allowed when using T, C, R, or M addresses.
(5)
Supported only by L20, L30, and L40 Fixed SLC processors with DC inputs.
(6)
Supported only by SLC 5/02, SLC 5/03, SLC 5/04, and SLC 5/05 processors.
(7)
SLC 5/05 Channel 0 (RS-232 serial port) only.
(8)
For SLC 5/05, control block length = 55 if logical ASCII addressing is used.
(9)
File types F, A, and ST only apply to SLC 5/03 (OS301 or later), SLC 5/04, and SLC 5/05 processors.
Publication 1747-RM001G-EN-P - November 2008
0 to 255
Page 615
Programming Instruction References
D-15
Table D.4 Available Addressing Modes Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
MUL
Multiply source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none
MVM
NEG
NEQ
NOT
OR
Masked Move
Negate
Not Equal To
Logical NOT
Logical OR
OSR
One-shot Rising bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST none
OTE
Output Energize bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none
OTL
Output Latch bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none
OTU
Output Unlatch bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none
PID(1)
PID control block direct
N none process variable direct, indirect
O, I, B, T, C, R, N, A none control variable direct, indirect
O, I, B, T, C, R, N, A none control block length
23 always
Publication 1747-RM001G-EN-P - November 2008
Page 616
D-16
Programming Instruction References
Table D.4 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
RAD(2)
Degrees to Radians source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
REF(1)
I/O Refresh channel 0
0=no, 1=yes channel 1
0=no, 1=yes
RES
Timer/Counter Reset
RET
Return
RHC
Read High Speed Clock destination direct
N, F
RMP
Ramp control direct
N destination direct
O, I, S, B, N
RPC structure direct
T, C, R none
Read Program Checksum Proc/Mmod destination
RPI(1)
Reset Pending Interrupt slots
RTO
Retentive Timer On timer
SBR
Subroutine
SCL(3)
Scale
Publication 1747-RM001G-EN-P - November 2008 none
0=PROC-MEM, 1=MEM-MOD direct
N double hex word (list of slots)
direct
T none time base (SLC 5/01)
0.01 only time base (SLC 5/02, 5/03, 5/04, 5/05)
0.01 or 1.00 preset
0 to 32,767 accum
0 to 32,767 none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none rate direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 offset direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none
Page 617
Programming Instruction References
D-17
Table D.4 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
SCP(2)
Scale with Parameters input direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none input min.
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max input max.
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max scaled min.
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max scaled max.
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max scaled output direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none file indexed direct indexed indirect
O, I, S, B, N, A, ST none mask direct, indexed direct(4) indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 source direct, indexed direct(4)
O, I, S, B, T, C, R, N, A, ST, M none
R none
SIN(2)
SQC
Sine
Sequencer Compare indirect, indexed indirect control
SQL(3)
Sequencer Load direct length
1 to 255 position
0 to 255 file indexed direct indexed indirect
O, I, S, B, N, A, ST none source direct, indexed direct(4) indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 control direct
R none length
1 to 255 position
0 to 255
Publication 1747-RM001G-EN-P - November 2008
Page 618
D-18
Programming Instruction References
Table D.4 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
SQO
Sequencer Output file indexed direct indexed indirect
O, I, S, B, N, A, ST none mask direct, indexed direct(4) indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct(4) indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none control direct
R none
SQR(3)
Square Root length
1 to 255 position
0 to 255 source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
STD(3)
Selectable Timed Interrupt Disable none
STE(3)
Selectable Timed Interrupt Enable none
STS(3)
Selectable Timed Interrupt Start
SUB
Subtract file direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
0, 3 to 255 time direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
0 to 255 (SLC 5/02), 0 to 32,767 (SLC 5/03, 5/04, 5/05)
source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,76 f-min to f-max source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
SUS
Suspend
SVC(1)
Service Communications channel 0 (SLC 5/03, 5/04, 5/05)
0=no, 1=yes channel 1 (SLC 5/03, 5/04, 5/05)
0=no, 1=yes
SWP(2)
Swap suspend ID source length
Publication 1747-RM001G-EN-P - November 2008
-32,768 to 32,767 indexed direct indexed indirect
B, N, A, ST none 1 to 128: bit, 1 to 128: integer, 1 to 41: string, 1 to 128: ASCII
Page 619
Programming Instruction References
D-19
Table D.4 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
TAN(2)
Tangent source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none start direct
N, F stop direct
N, F destination direct
N, F
TDF
Compute Time Difference
TND
Temporary End
TOD
Convert to BCD
TOF
TON
Timer Off Delay
Timer on Delay none source (SLC 5/01)
direct
O, I, S, B, T, C, R, N none source (SLC 5/02, 5/03, 5/04, 5/05)
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M destination direct
O, I. S. B. T, C, R, N, A, ST, M none timer direct
T none time base (SLC 5/01)
0.01 only time base (SLC 5/02, 5/03, 5/04, 5/05)
0.01 or 1.00 preset
0 to 32,767 accum
0 to 32,767 timer direct
T none 0.01 only time base (SLC 5/01)
0.01 or 1.00 0 to 32,767 time base (SLC 5/02, 5/03, 5/04, 5/05)
0 to 32,767 preset accum XIC
Examine On (Examine if Closed Contact)
source bit direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none
XIO
Examine Off (Examine if Open Contact)
source bit direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none
XOR
Logical Exclusive OR address A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 address B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none
Publication 1747-RM001G-EN-P - November 2008
Page 620
D-20
Programming Instruction References
Table D.4 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
XPY(2)
X to the Power of Y source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768-32,767 f-min-f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
(1)
Supported by SLC 5/02, SLC 5/03, SLC 5/04, and SLC 5/05 processors.
(2)
Supported by SLC 5/03 (OS302), SLC 5/04 (OS401), and SLC 5/05 processors.
(3)
Not supported by SLC 5/01 processors and FIxed controllers.
(4)
Indexed addressing is not allowed when using T, C, R, or M addresses.
Publication 1747-RM001G-EN-P - November 2008