Programming Instruction References
This appendix lists all of the available programming instructions along with their parameters, valid addressing modes, and file types.
Valid Addressing Modes and File Types
The following addressing modes are available. Table D.1 Available Addressing Modes Addressing Mode
Example
Direct
N7:0
Indexed Direct
#N7:0
Indirect
N7:[N10:3]
Indexed Indirect
#N7:[N10:3]
The following file types are available. Table D.2 Available File Types
1
Abbreviation
File Type
O
Output
I
Input
S
Status
B
Binary
T
Timer
C
Counter
R
Control
N
Integer
F
Float(1)(2)
A
ASCII(1)(2)
ST
String(1)(2)
M
M0/M1(3)
Immediate indicates that a constant is a valid file type
(1)
Supported only by SLC 5/03 (OS301 and higher), SLC 5/04, and SLC 5/05 processors.
(2)
Not supported by Fixed SLC, SLC 5/01, and SLC 5/02 processors.
(3)
Not supported by Fixed SLC and SLC 5/01 processors.
Publication 1747-RM001G-EN-P - November 2008
Page 602
D-2
Programming Instruction References
Understanding the Different Addressing Modes The following descriptions will help you understand how to structure a specific type of address.
Direct Addressing The data stored in the specified address is used in the instruction. For example: N7:0 ST20:5 T4:8.ACC
Indexed Addressing You may specify an address as being indexed by placing the “#” character in front of the address. When an address of this form is encountered in the program, the processor takes the element number of the address and adds to it the value contained in the Index Register S:24, then uses the result as the actual address. For example: #N7:10 where S:24 = 15 The actual address used by the instruction is N7:25.
Indirect Addressing You may specify an address as being indirect by replacing the file number, element number, or sub-element number with a [Xf:e.s] symbol. The word address inside of the bracket is queried for a value. The queried value then becomes the file, element, or sub-element portion of the indirect address. For example: B3:[N10:2] states that the element address of Bit file 3 is contained in address N10:2. Therefore, if N10:2 contains the value 5, B3:[N10:2] indirectly refers to address B3:5. Other examples include: N7:[N7:0] N7:[T4:0.ACC] N[N7:0]:[N7:1] C5:[N7:0]
Indexed Indirect Addressing You may specify a combination of indirect and indexed addressing. The processor first resolves the indirect portion of the address and then adds the offset from the Index Register S:24 to come up with the final address. For example:
Publication 1747-RM001G-EN-P - November 2008
Page 603
Programming Instruction References
D-3
#N7:[N10:3] where N10:3 = 20 and S:24 = 15 The actual address used by the instruction is N7:35.
Table D.3 Available Addressing Modes Instruction
Description
Instruction Parameter
ABL(1)
ASCII Test Buffer for Line channel control
Valid Addressing Mode(s)
Valid File Types
0 direct
R characters ABS(2)
ACB(1)
Absolute Value
ASCII Number of Characters in Buffer
ACI
ACL(1)
ACN
(1)
ACS(2)
ADD
AEX(1)
ASCII String to Integer
ASCII Clear Buffer
ASCII String Concatenate
Arc Cosine
Add
ASCII String Extract none 0-1024 source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none channel control
0 direct
R characters (1)
Immediate Values none 0 to 1024 source direct, indirect
ST none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none channel
0 transmit buffer
0=no or 1=yes receive buffer
0=no or 1=yes source A direct, indirect
ST none source B direct, indirect
ST none destination direct
ST none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source direct, indirect
ST none index direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
1 to 82 number direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
1 to 82 destination direct
ST none
Publication 1747-RM001G-EN-P - November 2008
Page 604
D-4
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
AHL(1)
ASCII Set/Reset Handshake Lines channel
Valid Addressing Mode(s)
Valid File Types
0
AND mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
0 to FFFF
OR mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
0 to FFFF control direct
R none channel status AIC(1)
AND
ARD(1)
ARL(1)
ASC(1)
ASN(2)
ASR(1)
ASCII Integer to String
Logical AND
ASCII Read Characters
ASCII Read Line
ASCII String Search
Arc Sine
ASCII String Compare
Publication 1747-RM001G-EN-P - November 2008
Immediate Values
0 to 001F source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct
ST none source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none channel
0 destination direct
ST none control direct
R none string length
0 to 82 characters read
0 to 82 channel
0 destination direct
ST none control direct
R none string length
0 to 82 characters read
0 to 82 source direct, indirect
ST none index direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
1 to 82 search direct, indirect
ST none result direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source A direct, indirect
ST none source B direct, indirect
ST none
Page 605
Programming Instruction References
D-5
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
ATN(2)
Arc Tangent source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
AWA(1)
AWT
BSL
(1)
ASCII Write with Append channel
ASCII Write
Bit Shift Left
0 source direct
ST none control direct
R none string length
0 to 82 characters sent
0 to 82 channel
0 source direct
ST none control direct
R none string length
0 to 82 characters sent
0 to 82 file indexed direct indexed indirect
O, I, S, B, N, A, ST none control direct
R none bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none length BSR
Bit Shift Right
0 to 2048 file indexed direct indexed indirect
O, I, S, B, N, A, ST none control direct
R none bit address direct, indirect
O, I, S, B, T, C, R, N, A, ST, M none length BTR
BTW
Block Transfer Read
Block Transfer Write
0 to 2048 control direct
N source “Data” direct
I, O, S, B, N, A, F buffer direct M1 file address
M control direct
N source “Data” direct
I, O, S, B, N, A, F buffer direct M0 file address
M
Publication 1747-RM001G-EN-P - November 2008
Page 606
D-6
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
CEM
ControlNet Explicit Message control block direct
N none control block length
67
1747-SCNR slot
1 to 30 size in words (receive data)
0 to 248 size in words (send data)
0 to 248 data table address (receive data)
direct
N none data table address (send data)
direct
N none message timeout (x1 ms)
2 to 32767
ControlNet address
1 to 99 service service code (hex)
1 to 7F class (hex)
0 to FF instance (hex)
0 to FFFF attribute (hex)
0 to FFFF member (hex)
0 to FFFF
CLR
Clear destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none
COP
Copy File source indexed direct indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none destination indexed direct indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none length COS(2)
CPT(2)
Cosine
Compute source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none expression
Publication 1747-RM001G-EN-P - November 2008
1 to 128
<expression>
Page 607
Programming Instruction References
D-7
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
CTD
Count Down counter direct
C none
CTU
DCD
DDV
DDT
DEG(2)
DEM
Count Up
Decode 4 to 1 of 16
Double Divide
Diagnostic Detect
Radians to Degrees
DeviceNet Explicit Message preset
-32,768 to 32,767 accum
-32,768 to 32,767 counter direct
C none preset
-32,768 to 32,767 accum
-32,768 to 32,767 source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none control direct
R source “file” index direct
I, O, S, B, N, A reference “file” index direct
I, O, S, B, N, A result “file” index direct
I, O, S, B, N, A source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none control block direct
N none control block length
70
1747-SDN slot
0 to 30 size of send data (bytes)
0 to 52 message timeout (x1 sec)
0 to 255
DeviceNet address
0 to 63 service service code (hex)
1 to 7F class (hex)
0 to FF instance (hex)
0 to FFFF attribute (hex)
0 to FF
Publication 1747-RM001G-EN-P - November 2008
Page 608
D-8
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
DIV
Divide source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none control block direct
N none
EEM
EtherNet/IP Explicit Message control block length
58 size in words (receive data)
0 to 124 size in words (send data)
0 to 124 data table address (receive data)
direct
N none data table address (send data)
direct
N none service
ENC
EQU
FBC
Encode 1 of 16 to 4
Equal
File Bit Comparison
Publication 1747-RM001G-EN-P - November 2008 service code (hex)
1 to 7F class (hex)
0 to FFFF instance (hex)
0 to FFFF attribute (hex)
0 to FF source direct, indirect, index, indirect index
I, O, S, B, N, A, T destination direct, indirect, index, indirect index
I, O, S, B, N, A, C, R source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max control direct
R source “file” index direct
I, O, S, B, N, A reference “file” index direct
I, O, S, B, N, A result “file” index direct
I, O, S, B, N, A
Page 609
Programming Instruction References
D-9
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
Valid Addressing Mode(s)
Valid File Types
Immediate Values
FFL(3)
FIFO Load source direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M(4)
-32,768 to 32,767
FIFO array indexed direct indexed indirect
O, I, S, B, N, A none
FIFO control direct
R none
FFU(3)
FLL
FIFO Unload
Fill File length
1 to 128 position
0 to 127
FIFO array indexed direct indexed indirect
O, I, S, B, N, A none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M(4)
none
FIFO control direct
R none length
1 to 128 position
0 to 127 source direct, indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max destination indexed direct indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none length FRD
GEQ
GRT
From BCD to Binary
Greater Than or Equal
Greater Than
1 to 128 source (SLC 5/01)
direct
O, I, S, B, T, C, R, N, A, ST, M none source (SLC 5/02, 5/03, 5/04, 5/05)
direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N none destination direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M none source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max
Publication 1747-RM001G-EN-P - November 2008
Page 610
D-10
Programming Instruction References
Table D.3 Available Addressing Modes (Continued) Instruction
Description
Instruction Parameter
HSC(5)
High-speed Counter (SLC counter 5/01) preset counter
Valid Addressing Mode(s)
Valid File Types
Immediate Values none 1 to 32,767 direct
C none preset
-32,768 to 32,767 accum
-32,768 to 32,767 source direct
B and N none length always 5
IID(6)
I/O Interrupt Disable slots double hex word (list of slots)
IIE(6)
I/O Interrupt Enable slots double hex word (list of slots)
IIM
Immediate Input with Mask slot direct
I none mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 length (SLC 5/03, 5/04, and 5/05) INT(3)
I/O Interrupt
IOM
Immediate Output with Mask
1 to 32 none slot direct
O none mask direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, A, ST, M
-32,768 to 32,767 length (SLC 5/03, 5/04, and 5/05)
1 to 32
JMP
Jump label number
0 to 999
JSR
Jump to Subroutine subroutine file number
3 to 255
LBL
Label Declaration label number
0 to 999
LEQ
Less Than or Equal To source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max source A direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M none source B direct, indexed direct indirect, indexed indirect
O, I, S, B, T, C, R, N, F, A, ST, M
-32,768 to 32,767 f-min to f-max
LES
Less Than