Page 1 of Digital I/O Modules Installation Instructions

Manual · Allen-Bradley

Digital I/O Modules Installation Instructions

Manual48 pagesPDF 775 KB

Installation instructions for Allen-Bradley 1746 SLC 500 digital input, output and combination I/O modules, with wiring and specifications.

What this file really is

The old site listed this file as a manual for the Allen-Bradley 1746-HS, 1746-IA16 and 14 more models. The file is named for the 1746-HS, but this is the installation instruction for the 1746 digital I/O modules and does not mention the 1746-HS.

Download the PDF775 KB

Names · 11 models

The models it names

Filed with · 5 models

Also filed with these models on the old site

Summary

What is in it

Installation instructions for the Allen-Bradley 1746 digital I/O modules for SLC 500 systems: input modules such as the 1746-IA16, IB8, IB16, ITB16 and IV16, output modules such as the 1746-OA8, OA16, OV16, OW8 and OW16, and combination modules such as the 1746-IO8. It covers installing and removing modules, octal labels, fuse protection and blown fuse diagnostics, electronically protected outputs, wiring diagrams for each module and full specifications.

Its parts

  1. Important User Information
  2. Overview
  3. Hazardous Location Considerations
  4. Environnements Dangereux
  5. Install and Remove the Module
  6. Octal Label Kit Installation (for PLC processors only)
  7. Fuse Protection and Blown Fuse Diagnostics
  8. Electronically Protected Modules (1746-OB6EI and 1746-OB16E)
  9. Wiring Diagrams
  10. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1746-IN027C-EN-P, August 2008) for the Allen-Bradley SLC 500 digital I/O modules: the 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IC16, -IG16, -IH16, -IM4, -IM8, -IM16, -IN16, -ITB16, -ITV16, -IV8 and -IV16 inputs, the 1746-OA8, -OA16, -OAP12, -OB8, -OB6EI, -OB16, -OB16E, -OBP8, -OBP16, -OG16, -OV8, -OV16, -OVP16, -OW4, -OW8, -OW16 and -OX8 outputs, and the 1746-IO4, -IO8, -IO12 and -IO12DC combination modules. It covers installing a module, octal labels, fuse protection and blown-fuse recovery, a wiring diagram and a specification table for each module. The 1746-HS is not among the modules it covers.

Modules covered
SLC 500 digital input, output and combination I/O modules, 1746-IA4 through 1746-OX8 and 1746-IO4 to -IO12DC p. 1
Operating temperature
0...60 °C (32...140 °F) operating, -40...85 °C storage, 5...95% humidity noncondensing p. 30
Terminal wiring
Max 2 mm2 (14 AWG), max 2 wires per terminal, max torque 0.9 Nm (8 lb-in); terminal block retaining screws 0.6 Nm (5.3 lb-in) p. 6, 8
Isolation
1500V electro-optical isolation between I/O terminals and control logic p. 30
Chassis slot
Any slot but the first, which is reserved for the processor or a 1747-ASB; cover unused slots with 1746-N2 card slot fillers p. 5, 6
Replacement fuses
1746-OBP16 and -OVP16: Littelfuse 322010 or 332010, 10A, kit 1746-F8; 1746-OAP12: SAN-O HQ 6.3A, kit 1746-F9 (five fuses per kit) p. 10, 11, 14, 15
AC input modules
1746-IA4, -IA8, -IA16: 85...132V ac; 1746-IM4, -IM8, -IM16: 170...265V ac; both 47...63 Hz p. 32, 33
DC input modules
1746-IB8, -IB16, -ITB16: 10...30V dc sinking; -IV8, -IV16, -ITV16: 10...30V dc sourcing; -IC16: 48V dc; -IH16: 90...146V dc; -IG16: 5V dc TTL; -IN16: 24V ac/dc p. 34, 35, 36
AC output modules
1746-OA8, -OA16, -OAP12 triac outputs, 85...265V ac; up to 1.0, 0.50 and 2.0 A per point at 30 °C p. 37
DC output modules
1746-OB8, -OB16: 10...50V dc sourcing; -OB16E, -OB6EI: 10...30V dc; -OBP8, -OBP16: 20.4...26.4V dc; -OV8, -OV16: 10...50V dc sinking; -OVP16: 20.4...26.4V dc sinking; -OG16: 5V TTL p. 38, 39, 41, 42
Relay contact rating
1746-OW4, -OW8, -OW16: 2.5 A continuous, 15 A make and 1.5 A break at 120V ac; 1746-OX8: 5.0 A continuous, 30 A make and 3.0 A break at 120V ac p. 44
Electronic protection
1746-OB6EI and -OB16E limit current by thermal cut-out per channel, auto-reset, and light an E-FUSE LED p. 16, 17
Blown fuse jumper
JP1 on 1746-OBP16, -OVP16 and -OAP12: factory set so the processor continues; pins 2 and 3 make a blown fuse fault the processor p. 9, 11, 12
Configuration ID codes
1746-IC16 0509, -IH16 0507, -OAP12 2803, -OB16E 2920, -OB6EI 2619, -OBP8 2721, -OVP16 2922, -IO12DC 1512 p. 34, 36, 37, 38, 39, 41, 45

What this manual walks you through

  • Installing and removing a module in the chassis p. 5, 6
  • Applying octal labels for use with PLC processors p. 6, 7, 8, 18
  • Removing the colored terminal blocks p. 7, 8
  • Setting the JP1 jumper for blown fuse behavior p. 9, 10, 11, 12, 13, 14
  • Recovering from a blown fuse processor fault p. 14
  • Replacing fuses in fused output modules p. 14, 15
  • Electronic protection and channel recovery on 1746-OB6EI and 1746-OB16E p. 16, 17
  • Wiring diagrams for every input, output and combination module p. 18, 19, 21, 23, 24, 25, 27, 28
  • Calculating system heat dissipation p. 30, 31, 32
  • Electrical specifications for each module p. 32, 34, 35, 37, 38, 41, 43, 44

Good to know

  • Never install, remove or wire a module while the chassis has power. p. 5, 15
  • The fuses on the 1746-OBP16, -OVP16 and -OAP12 protect only against short circuits, not overloads; fit external fuses for overload protection (on the -OAP12, no SAN-O HT fuse above 2.0 A). p. 9
  • The 1746-OB6EI and 1746-OB16E are not protected against reverse polarity or wiring to ac power. p. 16
  • TTL cable length is limited to 15 m (50 ft) per point for 1746-IG16 inputs and 3 m (10 ft) per point for 1746-OG16 outputs. p. 35, 42
  • On relay modules, continuous current per module must be kept so module power stays at or below 1440VA. p. 43

Questions this manual answers

What replacement fuse does a 1746-OBP16 or 1746-OVP16 take?

A Littelfuse 322010 or 332010 rated 10A, sold as kit 1746-F8 with five fuses. p. 14

How do I recover an SLC 500 after a blown fuse faults the processor?

Replace the fuse, clear major fault bit S:1/13, optionally clear the S:6 error code, and return the processor to Run mode. p. 14

What error code does a 1746 blown fuse fault show?

Status word S:6 shows xx58 on SLC 500 and 5/01 processors and xx60 on SLC 5/02 and later. p. 12

Why do 1746-IG16 inputs seem inverted?

The TTL inputs are low-true: a low voltage reads as ON. A NOT instruction in the ladder program converts to high-true logic. p. 35

Which chassis slot can a 1746 digital I/O module go in?

Any slot except the first, which is kept for the processor or a 1747-ASB module. p. 5

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1746-IN027C-EN-P Digital I/O Modules Installation Instructions1
    1. Important User Information3
    2. Overview4
    3. Hazardous Location Considerations4
    4. Environnements Dangereux5
    5. Install and Remove the Module5
    6. Octal Label Kit Installation (for PLC processors only)6
    7. Fuse Protection and Blown Fuse Diagnostics8
    8. Electronically Protected Modules (1746-OB6EI and 1746-OB16E)16
    9. Wiring Diagrams18
    10. Specifications30
  2. Back Cover48

From the PDF’s own bookmarks.

The whole text · 5 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 4841-48

The file

Revision and size

RevisionPublication 1746-IN027C-EN-P, August 2008
PublisherRockwell Automation
Pages48
PDF775 KB