Page 31
Digital I/O Modules
31
• Total Watts - the Watts per point multiplied by the number of points, plus the minimum Watts (with all points energized).
Input Module Heat Dissipation Catalog Numbers
Watts per Point
Min Watts
Total Watts
1747-IA4
0.27
0.175
1.30
1746-IA8
0.27
0.250
2.40
1746-IA16
0.27
0.425
4.80
1746-IB8
0.20
0.250
1.90
1746-IB16
0.20
0.425
3.60
1746-IC16
0.22
0.425
3.95
1746-IG16
0.02
0.700
1.00
1746-IH16
0.32
0.217
5.17
1746-IM4
0.35
0.175
1.60
1746-IM8
0.35
0.250
3.10
1746-IM16
0.35
0.425
6.00
1746-IN16
0.35
0.425
6.00
1746-ITB16
0.20
0.425
3.60
1746-ITV16
0.20
0.425
3.60
1746-IV8
0.20
0.250
1.90
1746-IV16
0.20
0.425
3.60
Output Module Heat Dissipation Catalog Numbers
Watts per Point
Min Watts
Total Watts
1746-OA8
1.000
0.925
9.00
1746-OA16
0.462
1.850
9.30
1746-OAP12
1.000
1.850
10.85
1746-OB6EI
0.440
0.230
2.90
1746-OB8
0.775
0.675
6.90
1746-OB16
0.388
1.400
7.60
1746-OB16E
0.150
0.675
3.07
1746-OBP8
0.300
0.675
3.08
1746-OBP16
0.310
1.250
6.26
1746-OG16
0.033
0.900
1.50
1746-OV8
0.775
0.675
6.90
1746-OV16
0.388
1.400
7.60
1746-OVP16
0.310
1.250
6.26
1746-OW4
0.133
1.310
1.90
1746-OW8
0.138
2.590
3.70
1746-OW16
0.033
5.170
5.70
1746-OX8
0.825
2.590
8.60
Publication 1746-IN027C-EN-P - August 2008
Page 32
32
Digital I/O Modules
Combination Input/Output Module Heat Dissipation Catalog Numbers
Watts per Point
Minimum Watts
Total Watts
1746-IO4
0.27 per input point 0.133 per output point
0.75
1.60
1746-IO8
0.27 per input point 0.133 per output point
1.38
3.00
1746-IO12
0.27 per input point 0.133 per output point
2.13
4.60
1746-IO12DC
0.20 per input point 0.133 per output point
1.84
3.90
Input Modules - ac Specifications for Input Modules 1746-IA4, 1746-IA8, and 1746-IA16 Attribute
Value 1746-IA4
1746-IA8
1746-IA16(1)
Voltage category
100/120V ac signal input
Number of inputs
4
8
16
Points per common
4
8
16
Voltage, operating
85...132V ac at 47...63 Hz
Backplane current consumption
5V dc
0.035 A
24V dc
0.0 A
Signal delay, max
On = 35 ms Off = 45 ms
Off-state voltage, max
30V ac
Off-state current, max
2 mA
Input current at 120V ac, nom
12 mA
Inrush current, max
0.8 A
Inrush current time duration, max
0.5 ms
(2)
0.050 A
0.085 A
(1)
Removable terminal block.
(2)
An ac input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac input-circuit will be affected.
Publication 1746-IN027C-EN-P - August 2008
Page 33
Digital I/O Modules
33
Specifications for Input Modules 1746-IM4, 1746-IM8, and 1746-IM16 Attribute
Value 1746-IM4
1746-IM8
1746-IM16(1)
Voltage category
200/240V ac signal input
Number of inputs
4
8
16
Points per common
4
8
16
Voltage, operating Backplane current consumption
170...265V ac at 47...63 Hz 5V dc
0.035 A
24V dc
0.0 A
0.050 A
Signal delay (max.)
On = 35 ms Off = 45 ms
Off-state voltage, max
50V ac
Off-state current, max
2 mA
Input current at 240V ac, nom
12 mA
Inrush current, max(2)
1.6 A
Inrush current time duration, max
0.5 ms
(1) (2)
0.085 A
Removable terminal block. An ac input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac input circuit will be affected.
Publication 1746-IN027C-EN-P - August 2008
Page 34
34
Digital I/O Modules
Input Modules - dc Specifications for Input Modules 1746-IB8, 1746-IB16, 1746-ITB16, and 1746-IC16 Attribute
Value 1746-IB8
1746-IB16(1) 1746-ITB16(1) 1746-IC16(1)(2)
Voltage category
24V dc signal input (sinking)
48V dc signal input (sinking)
Number of inputs
8
16
16
16
Points per common
8
16
16
Voltage, operating
10...30V dc (sinking)
Backplane current consumption
5V dc
0.050 A
24V dc
0.0 A
Signal delay, max
On = 8 ms On = 8 ms Off = 8 ms Off = 8 ms
Off-state voltage, max
5.0V dc
Off-state current, max
1 mA
Input current, nom
8 mA at 24V dc
(1) (2) (3)
16 30...60V dc at 55 °C (131 °F) sinking 30...55V dc at 60 °C (140 °F) sinking
On = 0.3 ms
On = 4 ms
Off = 0.5 ms(3) Off = 4 ms 10.0V dc
1 mA
1.5 mA
1.5 mA 4.1 mA at 48V dc
Removable terminal block. Use ID Code 0509 when configuring your system with programming software or the HHT. Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms at 24V dc.
Specifications for Input Modules 1746-IV8, 1746-IV16, and 1746-ITV16 Attribute
Value 1746-IV8
1746-IV16(1)
1746-ITV16(1)
Voltage category
24V dc signal input (sourcing)
Number of inputs
8
16
16
Points per common
8
16
16
Voltage, operating
10...30V dc (sourcing) 0.085 A
0.085 A
On = 8 ms Off = 8 ms
On = 0.3 ms
1 mA
1.5 mA
Backplane current consumption
5V dc
0.050 A
24V dc
0.0 A
Signal delay, max
On = 8 ms Off = 8 ms
Off-state voltage, max
5.0V dc
Off-state current, max
1 mA
Input current at 24V dc, nom
8 mA
(1) (2)
Removable terminal block. Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms at 24V dc.
Publication 1746-IN027C-EN-P - August 2008
Off = 0.5 ms(2)
Page 35
Digital I/O Modules
35
Specifications for Input Module 1746-IG16 Attribute
Value(1)
Voltage category
5V dc TTL signal input (sourcing)
Number of inputs
16
Points per common
16
Voltage, operating +5 V to DC COM
4.5...5.5V dc (sourcing)
Backplane current consumption
5V dc
0.140 A
24V dc
0.0 A
Signal delay, max
On = 0.25 ms Off = 0.50 ms
Off-state voltage
2...5.5 V dc (2)
Off-state current, max
4.1 mA
Input current at 5V dc, nom
3.7 mA
(1) (2)
50 mV peak to peak ripple (max)
Removable terminal block. TTL inputs are inverted (-0.2...0.8V dc = low voltage = True = ON). Use a NOT instruction in your ladder program to convert to traditional True = High logic.
ATTENTION
To avoid potential damage to TTL modules, handle them by the ends of the module, not metallic surfaces. Electrostatic discharges can damage the module. take care to prevent exposure of terminals or components to electrostatic charges.
Careful wire routing within the enclosure helps cut down electrical noise between I/O lines. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for recommended wiring procedures for TTL modules. Limit cable length to 15 m (50 ft) per point for inputs in standard environments. Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines, publication 1770-IN041, for complete information.
Specifications for Input Module 1746-IN16 Attribute
Value(1)
Voltage category
24V ac/dc Signal Input
Number of inputs
16
Points per common Voltage, operating Backplane current consumption
16 dc
10...30V dc (sinking)
ac
10...30V ac
5V dc
0.085 A
24V dc
0.0 A
Publication 1746-IN027C-EN-P - August 2008
Page 36
36
Digital I/O Modules
Specifications for Input Module 1746-IN16 Signal delay, max
Off-state voltage, max Off-state current, max Input current, nom dc
On = 15 ms Off = 15 ms ac
On = 25 ms Off = 25 ms dc
3.0V dc ac
3.0V ac dc
1 mA ac
1 mA dc
8 mA at 24V dc ac
8 mA at 24V ac
Inrush current, max (1)
0.02 A (ac only)
Removable terminal block.
Specifications for Input Module 1746-IH16 Attribute
Value(1)(2)(3)
Voltage category
125V dc signal input (sinking)
Number of inputs
16
Points per common
16
Voltage, operating
Range: 90...146V dc
Backplane current consumption Signal delay, max
5V dc
0.085 A
24V dc
0.0 A
Points ON Simultaneously, max: 6 at 146V dc and 30 °C (86 °F) 12 at 146V dc and 50 °C (122 °F) 14 at 132V dc and 55 °C (131 °F) 16 at 125V dc and 60 °C (140 °F)
On = 9 ms Off = 9 ms
Off-state voltage, max
20.0V dc
Off-state current, max
0.8 mA
Input current, nom
2.15 mA at 125V dc 2.25 mA at 132V dc
(1)
Removable terminal block.
(2)
Use ID Code 0507 when configuring your system with programming software or the HHT.
(3)
If the input module is connected in parallel with an inductive load, use surge suppression across the load to protect the input module from damage caused by reverse voltage. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on surge suppression.
Publication 1746-IN027C-EN-P - August 2008
Page 37
Digital I/O Modules
37
Output Modules - ac Specifications for Output Modules 1746-OA8, 1746-OA16, and 1746-OAP12 Attribute
Value 1746-OA8
1746-OA16(1)
1746-OAP12(1)(2)(3)
Voltage category
120/240V ac signal input
Number of outputs
8
16
12
Points per common
4
8
6
Voltage, operating
85...265V ac at 47...63 Hz
Backplane current consumption
5V dc
0.185 A
24V dc
0.0 A
0.370 A
0.370 A
Signal delay, max resistive load.(4) On = 1 ms Off = 11.0 ms Off-state leakage, max(5)
2 mA
Load current, min
10 mA
Continuous current per point(6)
1.0 A at 30 °C (86 °F) 0.50 A at 30 °C (86 °F) 2.0 A at 30 °C (86 °F) 0.50 A at 60 °C (140 °F) 0.25 A at 60 °C (140 °F) 1.25 A at 55 °C (131 °F) 1.0 A at 60 °C (140 °F)
Continuous current per module, max
8.0 A at 30 °C (86 °F) 8.0 A at 30 °C (86 °F) 9.0 A at 30 °C (86 °F) 4.0 A at 60 °C (140 °F) 4.0 A at 60 °C (140 °F) 6.8 A at 55 °C (131 °F) 6.0 A at 60 °C (140 °F)
On-state voltage drop, max
1.50V at 1.0 A
1.50V at 0.50 A
1.2V at 2.0 A
Surge current per point(7), max
10.0 A for 25 ms
10.0 A for 25 ms
17.0 A for 25 ms(8)
(1)
Removable terminal block.
(2)
A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.
(3)
Use ID Code 2803 when configuring your system with programming software or the HHT.
(4)
Triac outputs turn on at any point in the ac line cycle, and turn off at ac line zero cross.
(5)
To limit the effects of leakage current through solid-state outputs, a loading resistor can be connected in parallel with your load. For 120V ac operation, use a 15 KΩ, 2 W resistor. For 240V ac operation, use a 15 KΩ, 5 W resistor.
(6)
Recommended surge suppression: For triac outputs when switching 120V ac inductive loads, use Harris Metal-Oxide Varistor, model number V220MA2A. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on surge suppression.
(7)
Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).
(8)
Surge current = 35 A per common for 10 ms.
Publication 1746-IN027C-EN-P - August 2008
Page 38
38
Digital I/O Modules
Output Modules - dc Specifications for Output Modules 1746-OB8, 1746-OB16, and 1746-OB16E Attribute
Value 1746-OB8
1746-OB16(1)
1746-OB16E(1)(2)
Number of outputs
8
16
16
Points per common
8
16
16
Voltage category
24V dc Signal Output
Voltage, operating (V dc)
10...50 (source)
Backplane current consumption
5V dc
0.135 A
24V dc
0.0 A
Signal delay, max. resistive load.
On = 0.1 ms Off = 1.0 ms
Off-state leakage, max(4)
1 mA
10...30 (source) 0.280 A
0.135 A
On = 0.1 ms Off = 1.0 ms
On = 1.0 ms(3) Off = 1.0 ms
Load current, min
1 mA
Continuous current per point(5)
1.0 A at 30 °C (86 °F) 0.50 A at 30 °C (86 °F) 1.0 A at 30 °C (86 °F)(6) 0.50 A at 60 °C (140 °F) 0.25 A at 60 °C (140 °F) 0.50 A at 60 °C (140 °F)
Continuous current per module
8.0 A at 30 °C (86 °F) 8.0 A at 30 °C (86 °F) 8.0 A at 4.0 A at 60 °C (140 °F) 4.0 A at 60 °C (140 °F) 0...60 °C (32...140 °F)
On-state voltage drop, max
1.2V at 1.0 A
1.2V at 0.50 A
1.0V at 0.50 A
Surge current per point(7)
3.0 A for 10 ms
3.0 A for 10 ms
2.0 A for 10 ms(8)
(1)
Removable terminal block.
(2)
Use the following ID Code when configuring your system with programming software or the HHT: 1746-OB16E = 2920.
(3)
Fast turn-off modules (1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16) provide fast OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules, when switching Bulletin 100-B110 (24W sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.
(4)
To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For transistor outputs, 24V dc operation, use a 5 KΩ, 1/2 W resistor.
(5)
Recommended surge suppression: For transistor outputs when switching 24V dc inductive loads, use a 1N4004 diode reverse-wired across the load. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on surge suppression.
(6)
Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.
(7)
Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).
(8)
Surge current = 32 A per module for 10 ms.
Publication 1746-IN027C-EN-P - August 2008
Page 39
Digital I/O Modules
ATTENTION
39
A transient pulse occurs in transistor outputs when the external dc supply voltage is applied to the output common terminals (for example, via the master control relay). This can occur regardless of the processor having power or not. For most applications, the energy of this pulse is not sufficient to energize the load. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on transient pulses and guidelines to reduce inadvertent processor operation.
Specifications for Output Modules 1746-OB6EI, 1746-OBP8, and 1746-OBP16 Attribute
Value 1746-OB6EI(1)(2)
1746-OBP8(1)(2)(3)
1746-OBP16(1)(2)(4)(5)
Number of outputs
6
8
16
Points per common
Individually Isolated
4
16
Voltage category
24V dc Signal Output
Voltage, operating (V dc)
10...30 (source)
20.4...26.4 (source)
5V dc
0.046 A
0.135 A
0.250 A
24V dc
0.0 A On = 1.0 ms(6) Off = 2.0 ms
On = 0.1 ms(6) Off = 1.0 ms
Backplane current consumption Signal delay, max Resistive load
On = 1.0 ms(6) Off = 2.0 ms
Off-state leakage, Max(7)
1 mA
Load current, Min
1 mA
Continuous current per point(8)(9)
2.0 A at 0 to 60 °C (140 °F)
2.0 A at 0 to 60 °C (140 °F)
1.5 A at 30 °C (86 °F) 1.0 A at 60 °C (140 °F)
Continuous current per module
12.0 A at 0 to 60 °C (140 °F)
8.0 A at 0 to 60 °C (140 °F)
6.4 A at 0...60 °C (32...140 °F)
On-state voltage drop, max
1.0V at 2.0 A
1.0V at 2.0 A
1.0V at 1.0 A
Surge current per point(10)
4.0 A for 10 ms
4.0 A for 10 ms
4.0 A for 10 ms
Surge current per module(10)
24.0 A for 10 ms
32.0 A for 10 ms
32.0 A for 10 ms
Electronic protection yes no no
(1)
Removable terminal block.
(2)
Use the following ID Code when configuring your system with programming software or the HHT: 1746-OB6EI = 2619, 1746-OBP8 = 2721 and 1746-OBP12 = 2921.
(3)
An external fuse can be used to protect this module from short circuits. Recommended fuse is SANO MQ4-3.15A, 5x20 mm.
(4)
A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.
Publication 1746-IN027C-EN-P - August 2008
Page 40
40
Digital I/O Modules
(5)
Certified for Class 1, Division 2 hazardous location by CSA.
(6)
Fast turn-off modules (1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16) provide fast OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin 100-B110 (24W sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.
(7)
To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For transistor outputs, 24V dc operation, use a 5.6 KΩ, 1/2 W resistor.
(8)
Recommended surge suppression: For transistor outputs when switching 24V dc inductive loads, use a 1N4004 diode reverse-wired across the load (also see footnote 9). Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on surge suppression.
(9)
Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.
(10)
Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).
ATTENTION
A transient pulse occurs in transistor outputs when the external dc supply voltage is applied to the output common terminals (for example, via the master control relay). This can occur regardless of the processor having power or not. For most applications, the energy of this pulse is not sufficient to energize the load. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on transient pulses and guidelines to reduce inadvertent processor operation.
Publication 1746-IN027C-EN-P - August 2008