The text of a manual · part 5 of 5
Digital I/O Modules Installation Instructions, pages 41 to 48
Pages 41 to 48 of 48
The original document is the PDF (775 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1746-IA16, Allen-Bradley 1746-IB8, Allen-Bradley 1746-IB16, Allen-Bradley 1746-IO8, Allen-Bradley 1746-ITB16, Allen-Bradley 1746-IV16, Allen-Bradley 1746-OA8, Allen-Bradley 1746-OA16, and 3 more models
Page 41
Digital I/O Modules
41
Specifications for Output Modules 1746-OV8, 1746-OV16, and 1746-OVP16 Attribute
Value 1746-OV8
1746-OV16(1)
1746-OVP16(1)(2)(3)(4)
Number of outputs
8
16
16
Points per common
8
16
16
Voltage category
24V dc Signal Output
Voltage, operating (V dc) Backplane current consumption
10...50 (sink)
5V dc
0.135 A
24V dc
0.0 A
Signal delay, max. resistive load.
On = 0.1 ms Off = 1.0 ms
Off-state leakage, max(6)
1 mA
Load current, min
20.4...26.4 (sink) 0.270 A
0.250 A
On = 0.1 ms(5) Off = 1.0 ms
1 mA
Continuous current per point
1.0 A at 30 °C (86 °F) 0.50 A at 30 °C (86 °F) 1.5 A at 30 °C (86 °F)(8) 0.50 A at 60 °C (140 °F) 0.25 A at 60 °C (140 °F) 1.0 A at 60 °C (140 °F)
Continuous current per module
8.0 A at 30 °C (86 °F) 4.0 A at 60 °C (140 °F)
On-state voltage drop, max
1.2V at 1.0 A
(7)
(9)
Surge current per point
6.4 A at 0...60 °C (32...140 °F) 1.2V at 0.5 A
3.0 A for 10 ms
1.0V at 1.0 A 4.0 A for 10 ms(10)
(1)
Removable terminal block.
(2)
A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.
(3)
Use the following ID Code when configuring your system with programming software or the HHT: 1746-OVP16 = 2922.
(4)
Certified for Class 1, Division 2 hazardous location by CSA.
(5)
Fast turn-off modules (1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16) provide fast OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin 100-B110 (24Ws sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.
(6)
To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For transistor outputs, 24V dc operation, use a 5.6 KΩ, 1/2 W resistor.
(7)
Recommended surge suppression: For transistor outputs when switching 24V dc inductive loads, use a 1N4004 diode reverse-wired across the load (also see footnote 9). Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747UM011, for more information on surge suppression.
(8)
Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.
(9)
Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).
(10)
Surge current = 32 A per module for 10 ms.
Publication 1746-IN027C-EN-P - August 2008
Page 42
42
Digital I/O Modules
ATTENTION
A transient pulse occurs in transistor outputs when the external dc supply voltage is applied to the output common terminals (for example, via the master control relay). This can occur regardless of the processor having power or not. For most applications, the energy of this pulse is not sufficient to energize the load. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on transient pulses and guidelines to reduce inadvertent processor operation.
Specifications for Output Module 1746-OG16 Attribute
Value(1)
Number of outputs
16
Points per common
16
Voltage category
5V dc TTL Signal Input (sinking)
Voltage, operating (VDC to DC COM)
4.5...5.5V dc(2) 50 mV peak to peak ripple (max.)
Backplane current consumption
5V dc
0.180 A
24V dc
0.0 A
Signal delay, max resistive load
On = 0.25 mA Off = 0.50 mA
Off-state voltage
4.5...5.5V dc(2)
Off-state leakage, max
0.1 mA
Load current, min
0.15 mA
Continuous current per point
24 mA
(1)
Removable terminal block.
(2)
TTL outputs are inverted (0...0.4V dc = low voltage = True = ON). Use a NOT instruction in your ladder program to convert to traditional True = High logic.
ATTENTION
To avoid potential damage to TTL modules, handle them by the ends of the module, not metallic surfaces. Electrostatic discharges can damage the module. Take care to prevent exposure of terminals or components to electrostatic charges.
Careful wire routing within the enclosure helps cut down electrical noise between I/O lines. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for recommended wiring procedures for TTL modules. Limit cable length to 3 m (10 ft) per point for outputs in standard environments. Publication 1746-IN027C-EN-P - August 2008
Page 43
Digital I/O Modules
43
Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines, publication 1770-IN041, for complete information.
Relay Contact Output Modules Specifications for Output Modules 1746-OW4, 1746-OW8, 1746-OW16, and 1746-OX8 Attribute
Value 1746-OW4(1)
1746-OW8(1)
1746-OW16(1)(2) 1746-OX8(1)(2)
Number of outputs
4
8
16
8
Points per common
4
4
8
Individually Isolated
Voltage category Operating voltage Backplane current consumption ac/dc Relay 5V dc
5...125
24V ac
5...265
5V dc
0.045 A
0.085 A
0.170 A
0.085 A
24V dc
0.045 A
0.090 A
0.180 A
0.090 A
Signal delay, max Resistive load
On = 10.0 ms Off = 10.0 ms
Off-state leakage, max
0 mA
Load current, min
10 mA at 5V dc
Continuous current per point(3)
See relay contact ratings. (Table and Table on page 44)
Continuous current per module
8.0 A ac 8.0 A /Common
16.0 A ac 8.0 A /Common
16.0 A ac 8.0 A /Common
(4)
(1)
Certified for Class 1, Division 2 hazardous location by CSA.
(2)
Removable terminal block.
(3)
Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication 1747-UM011. Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.
(4)
The continuous current per module must be limited so the module power does not exceed 1440VA.
Publication 1746-IN027C-EN-P - August 2008
Page 44
44
Digital I/O Modules
Relay Contact Ratings Relay Contact Rating Table for Output Modules 1746-OW4, 1746-OW8, and 1746-OW16 Voltages
Amperes(2)
Volts (ac), max Volts (dc), max
Volt-Amperes Make
Break 180
Make
Break
Amperes(2) Continuous
120
15
1.5
2.5
1800
240
7.5
0.75
125
0.22(3)
1.0
28
24
1.2(3)
2.0
28
Relay Contact Rating Table for Output Module 1746-OX8 Voltages
Volts (ac), max Volts (dc), max
Amperes(1)
Amperes
Volt-Amperes
Make
Break
Continuous(2)
Make
Break
120
30
3.0
5.0
3600
360
240
15
1.5
125
0.22
(3)
1.0
28
24
1.2(3)
2.0
28
(1)
Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication 1747-UM011. Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.
(2)
The continuous current per module must be limited so the module power does not exceed 1440 VA.
(3)
For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28VA by the applied dc voltage. For example, 28VA/48V dc = 0.58 A. For dc voltage applications less than 14V, the make/break ratings for relay contacts cannot exceed 2 A.
Input/Output Combination Modules Specifications for Combination Modules 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC Attribute
Value 1746-IO4(1)(2)
1746-IO8(1)(2)
1746-IO12(1)(3)(4) 1746-IO12DC(3)(5)(6)(7)
2 inputs 2 outputs
4 inputs 4 outputs
6 inputs 6 outputs
Points per common
2
4
6
Voltage category (inputs)
120V ac
24V dc
Voltage, operating (inputs)
85...132V ac
10...30V dc
Voltage category (outputs)
100/120V ac Relay contact output
Points per module
Publication 1746-IN027C-EN-P - August 2008
6 inputs 6 outputs 6
Page 45
Digital I/O Modules
45
Specifications for Combination Modules 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC Voltage, operating (outputs)
5...265V ac 5...125V dc
Backplane current 5V dc consumption 24V dc
0.030 A
0.060 A
0.090 A
0.080 A
0.025 A
0.045 A
0.070 A
0.060 A
(1)
Certified for Class 1, Division 2 hazardous location by CSA.
(2)
See specifications for catalog numbers 1746-IA4 and 1746-OW4. Continuous Current per 1746-IO4 Module is 4.0 A. Continuous Current per 1746-IO8 Module is 8.0 A.
(3)
Removable terminal block.
(4)
See specifications for catalog numbers 1746-IA16 and 1746-OW16. Continuous Current per 1746-IO12 Module is 8.0 A.
(5)
See specification for catalog numbers 1746-IB16 and 1746-OW16. Continuous Current per 1746-IO12DC Module is 8.0 A.
(6)
Certified for Class 1, Division 2 hazardous location by C-UL.
(7)
Use the following ID Code when configuring your system with programming software or the HHT: 1746-IO12DC = 1512.
TIP
Combination I/O modules (Catalog Numbers 1746-IO4, 1746-IO8, 1746-IO12 and 1746-IO12DC): For the first several seconds of any power-up or when power is applied to a rack that is not under processor control, the output LED indicators of the combination IO modules in the rack will be illuminated. Racks are not under processor control if one of the following conditions exist: • Modular Hardware Style (only): Processor is absent from the rack or the rack interconnect cable is not properly connected. • Modular Hardware Style and Fixed Hardware Style: The processor does not have the firmware PROM installed or the processor is not functioning properly.
Publication 1746-IN027C-EN-P - August 2008
Page 46
46
Digital I/O Modules
Notes:
Publication 1746-IN027C-EN-P - August 2008
Page 47
Digital I/O Modules
47
Notes:
Publication 1746-IN027C-EN-P - August 2008
Page 48
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States
1.440.646.3434 Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States
Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for return procedure.
You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Allen-Bradley, TechConnect, Rockwell Automation, and SLC 500 are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1746-IN027C-EN-P - August 2008 Supersedes Publication 1746-IN027B-EN-P - January 2007
PN 40071-160-01(3) Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.