Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of SLC Servo Control Module (Catalog No. 1746-HSRV) User Manual

Spec sheet · Allen-Bradley

SLC Servo Control Module (Catalog No. 1746-HSRV) User Manual

Spec sheet224 pagesPDF 1.8 MB

User manual for the Allen-Bradley SLC Servo Module, catalog 1746-HSRV: installing, wiring, configuring, programming and troubleshooting.

What this file really is

The old site listed this file as a spec sheet for the Allen-Bradley 1746-HS. Linked as a spec sheet for the 1746-HS, but it is the 224-page user manual for the SLC Servo Module, catalog number 1746-HSRV.

Download the PDF1.8 MB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

User manual for the Allen-Bradley SLC Servo Module (catalog number 1746-HSRV) for SLC 500 controllers. It covers selecting power supplies, encoders and drives, planning and installing the module and its termination panel, wiring fast I/O, overtravels, Estop, encoders and drives, testing, configuring and calibrating the axis, homing options, programming moves and blend move profiles from the SLC processor, status words, troubleshooting with LEDs and fault messages, and ladder examples.

Its parts

  1. Preface
  2. Overview of the SLC Servo Module
  3. Selecting Power Supplies, Encoders, and Drives
  4. Planning Hardware Installation
  5. Installing Your SLC Servo Module
  6. Wiring the SLC Servo Module
  7. Testing Your SLC Servo Module Hardware
  8. Setting Up Your SLC Servo Module
  9. Programming the SLC Processor to Run the SLC Servo Module
  10. Programming System Variables
  11. Troubleshooting

From the sheet

Key facts from this sheet

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This is the Allen-Bradley user manual for the SLC Servo Module, catalog number 1746-HSRV, a servo control module for the SLC 500 family. It walks through choosing power supplies and encoders, installing and wiring the module and its termination panel, configuring and programming moves, and troubleshooting with the LEDs and fault messages.

Read for this summary: pages 1 to 10, 20 to 24, 26 to 28, 165 to 166 and 189 of 224.

Device
1746-HSRV SLC Servo Module for incremental, absolute or speed moves p. 20
Processors
SLC 5/03 FRN 5.0 or later, SLC 5/04, SLC 5/05 p. 20, 23
Software
RSLogix 500, AI500, or APS (version 5.0 or higher) p. 23
I/O words
Class 3; 12 input words, 12 output words p. 23
Configuration selection
OTHER, with 10114 as the number p. 23
Recommended slot
Slot 1 or the lowest numbered I/O slot when using the module interrupt option p. 23
Modules per rack
12, with proper power supply p. 23
Backplane current
.300A at +5V, .104A at +24V p. 24
User-side supply
NEC class 2 supply with +5V, ±15V, and +24V capacity p. 26
User-side current
.150A at +5V, .030A at +15V, .030A at -15V p. 27
Fast I/O
Inputs FIN1 through FIN3 and output FOUT1, 24V DC p. 27
Fast output rating
+24V @ .20A resistive and inductive loads; +24V @ .10A capacitive loads p. 28
Encoders
Allen-Bradley 845H encoders; others if they meet the listed specifications p. 28
Cable and panel
1746-HCA cable, 2.1m (84in.), to the 1746-HT termination panel p. 21, 189

What this sheet walks you through

  • Selecting a backplane power supply p. 24, 26
  • Calculating user-side current requirements p. 27
  • Checking 24V DC devices for the fast inputs and outputs p. 28
  • Configuring the module with M files p. 22
  • Wiring the Estop for one axis or several axes p. 5
  • Homing to a marker, a limit switch, or both p. 7
  • Diagnosing with the RUN, FDBK/U.PWR and CONFIG INV LEDs p. 165, 166
  • Informational, minor fault and major fault messages p. 9
  • 1746-HCA cable pinout and dimensions p. 189
  • Ladder logic programming examples p. 10

Good to know

  • The module does not work in a remote I/O rack. p. 23
  • Configuration parameters are kept in RAM without battery backup. p. 22
  • Configuration mode can be entered only while the system is in Estop. p. 22
  • The manual advises against powering the Estop or fast I/O from the +24V of a 1746-P1, P2, P3 or P4. p. 26
  • User-side power must be present for the SLC processor to talk to the module. p. 26

Questions this sheet answers

Which SLC processors work with the 1746-HSRV?

The SLC 5/03 at FRN 5.0 or later, the SLC 5/04, and the SLC 5/05. p. 20

How much backplane current does the 1746-HSRV draw?

.300A at +5V and .104A at +24V. p. 24

What does a red FDBK/U PWR LED mean on the 1746-HSRV?

No user power. Check the user power supply and its connections to the termination panel. p. 165

How long is the 1746-HCA cable?

2.1m (84in.), with a 25-pin D-sub connector at one end and a 37-pin D-sub connector at the other. p. 189

How many 1746-HSRV modules fit in one SLC rack?

12, with a proper power supply. p. 23

The whole text · 23 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160
  17. Pages 161 to 170161-170
  18. Pages 171 to 180171-180
  19. Pages 181 to 190181-190
  20. Pages 191 to 200191-200
  21. Pages 201 to 210201-210
  22. Pages 211 to 220211-220
  23. Pages 221 to 224221-224

The file

Revision and size

RevisionPublication 1746-6.1.2, July 2000
PublisherAllen-Bradley (Rockwell Automation)
Pages224
PDF1.8 MB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.

The first pages · 4 of 224

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 224
Page 2
Page 2of 224
Page 3
Page 3of 224
Page 4
Page 4of 224