Page 21
1-2
Overview of the SLC Servo Module
Figure 1.1 Example of an SLC Wiring
SLC 17465/04 HSRV
CR-LPS-0503 +5V & –12V DC Power Supply CR-IOPS-241 +24V DC Power Supply
1746-HCA Cable
1746-HT Termination Panel
A-B 845 Encoder
Motor
Tach
SLC Servo Module Operation
1746IW16
Drive Amplifier
The SLC Servo Module, compatible with the SLC family, is used with SLC 5/03 FRN 5.0 (and above) processors using RSLogix 500, AI500 or APS (version 5.0 or higher) software. Once the SLC processor is initiated, the execution of the motion block is independent of the scan time of the processor. Blended motion allows for complicated move profiles consisting of two to thirty-two segments. The blended move profiles are stored in the SLC Servo Module’s memory as a series of absolute moves and can be executed more than once. Other move or homing operations can be performed between blended move profiles. The SLC Servo Module controls absolute position over a range of 32 bits. The SLC Servo Module performs an origin search (also called homing) and automatically resets the absolute position to the home position when the SLC processor requests a search function after detecting one of the following: • Encoder marker • Limit switch • Limit switch and marker
Publication 1746-6.1.2 - July 2000
Page 22
Overview of the SLC Servo Module
1-3
The SLC Servo Module operates in two modes: • Configuration • Command When operating in the configuration or the command mode, the status of the module is reported to the SLC processor.
Configuration Mode Operation You can enter configuration mode only if the system is in Estop. In the SLC Servo Module, you configure the SLC Servo Module by using M files containing data provided by the SLC 5/03 (or versions listed above) processors. All configuration parameters are internal to the SLC Servo Module and stored in non-battery backed RAM. In configuration mode, you select the proper setup configuration to match the servo drive and motor without setting switches and without special software. If you do not set up your own configuration, the configuration is set to the default setting.
Command Mode Operation Motor operations are performed in command mode. To operate in this mode, set the mode flag (bit 15 in output word 0) to 0. In the command mode, the SLC processor issues commands and activates the following operations or moves: • Absolute moves • Incremental moves • Speed moves • Monitor moves • Hold moves • Unhold moves • Blend moves • Emergency stop operations • Homing operations • Preset operations • Clear faults • Alternate home moves
Publication 1746-6.1.2 - July 2000
Page 23
1-4
Overview of the SLC Servo Module
SLC Servo Module Specifications and Compatibility
Selected specifications for the SLC Servo Module appear in the table below.
1
SLC Servo Module
Specification
Class
3
Number of Input Words
12
Number of Output Words
12
Selection for Configuration
OTHER (with 10114 as the number specified)
Configuration Mode
Uses M files
Recommended I/O Slot in SLC Rack
Slot 1 or the lowest numbered I/O slot for SLC applications using the module interrupt option.1,2
Number of HSRVs in one rack
12 with proper power supply
There must not be other modules that generate module interrupts. Also, the STI and FAULT routines execute at a higher priority than the module interrupt routine that is linked to the SLC Servo Module interrupt.
2 The SLC Servo Module does not function in a remote I/O rack.
The SLC Servo Module is compatible with: • SLC 5/03 FRN 5.0 (and above) processors. • RSLogix 500, AI500, or APS (version 5.0 or higher) software.
Publication 1746-6.1.2 - July 2000
Page 24
Chapter
2
Selecting Power Supplies, Encoders, and Drives
Overview
In this chapter we explain how to select the hardware you need to support an SLC Servo Module system. This chapter includes the following topics: • Selecting a power supply for the backplane • Selecting a user-side power supply • Using fast inputs and outputs • Selecting an encoder • Selecting a drive The amount of hardware you need depends on how many axes your application uses. Consult your local Allen-Bradley sales engineer or distributor to help you select the equipment for your application. IMPORTANT
Selecting a Power Supply for the Backplane
The term user-side refers to the control circuitry on the SLC Servo Module card that is powered by customer-supplied power sources and isolated from the control circuitry that is powered by the backplane of an SLC rack.
Before you select a power supply, calculate the current requirements for your backplane. Use the table below for SLC Servo Module backplane current requirements: Voltage
Current Requirement
+5V
.300A
+24V
.104A
In your calculations, include the current requirements of the I/O modules in your chassis. Refer to your SLC 500 documentation.
1
Publication 1746-6.1.2 - July 2000
Page 25
2-2
Selecting Power Supplies, Encoders, and Drives
Example of Calculations for Backplane Current Requirements In this example, the system includes: • One seven-slot modular rack • One 1747-L543 CPU module • One 1746-IB8 DC input module with eight inputs @ +24V • One 1746-OV8 DC output module with eight outputs @ +24V • An SLC Servo Module system that contains: • SLC Servo Modules • Termination panels • Allen-Bradley 845H encoders • Fast inputs • Fast outputs Use the table below to find the current requirements of the devices using backplane power. Those devices that are not included in the backplane calculations are included in the example’s user-side calculations. Device
+5V
+24V
1746-L543 processor
1A
.200A
SLC Servo Module
.300A
0
1746-IB8
.040A
0
1746-OV8
.125A
0
Total = 1.465A
Total = .200A
If optional processor is used: Device
+5V
+24V
1747-L532 processor
.500A
.175A
SLC Servo Module
.300A
0
1746-IB8
.040A
0
1746-OV8
.125A
0
Total = .965A
Publication 1746-6.1.2 - July 2000
Total = .175A
Page 26
Selecting Power Supplies, Encoders, and Drives
2-3
Use the table below to find the power supplies Allen-Bradley recommends for the backplane: Power Supply
Selecting a User-Side Power Supply
Operating Voltage Requirements
Output Capacity 5V DC
24V DC
1746-P1
85-130V AC or 170-265V AC
2A
.46A
1746-P2
85-130V AC or 170-265V AC
5A
.96A
1746-P3
19.2-28.8 DC
3.6A
.87A
1746-P4
85-132V AC or 170-265V AC
10.0A
2.88A
You must provide a power supply that meets your system requirements. The following devices require user-side power: • SLC Servo Module • Encoders • I/O modules • Estop circuitry • Fast inputs and outputs You must select a power supply that meets the specifications of a NEC class 2 power supply. The power supply must have +5V, ±15V capacity, and +24V capacity for fast I/O and Estop circuitry. IMPORTANT
We recommend that you do not use the +24V included with the 1746-P1, P2, P3, or P4 to power your Estop or fast I/O.
Before you select a power supply, calculate the system’s user-side current requirements. IMPORTANT
The user-side power must be present for the SLC processor to communicate with the SLC Servo Module.
Publication 1746-6.1.2 - July 2000
Page 27
2-4
Selecting Power Supplies, Encoders, and Drives
Example of the Calculations for User-Side Current Requirements In this example, the system includes: • One seven-slot modular rack • One 1747-L541 CPU module • One 1746-IB8 DC input module with eight inputs @ +24V • One 1746-OV8 DC output module with eight outputs @ +24V • An SLC Servo Module system that contains: • Two SLC Servo Modules • Two termination panels • Two Allen-Bradley 845H encoders • Six fast inputs • Two fast outputs Use the table below to find the current requirements of the devices that draw user-side power. Device +5V +15V –15V +24V 1746-IB8 0 0 0 .064A 1746-OV8 0 0 0 .800A SLC Servo .150A .030A .030A 0 Module Estop circuitry 0 0 0 .100A 6 fast inputs 0 0 0 .015A 2 fast outputs 0 0 0 .100A 845H encoder .200A 0 0 0 845H encoder .200A 0 0 0 Total = .700A Total = .060A Total = .060A Total = 1.079A
Using Fast Inputs and Outputs
Publication 1746-6.1.2 - July 2000
The fast I/O (FIN1through FIN3, and FOUT1) are 24V DC compatible and are used with a user-side +24V power supply. Review potential
Page 28
Selecting Power Supplies, Encoders, and Drives
2-5
24V DC I/O devices for compatibility with the electrical specifications as shown in the table below. Outputs (source drivers) Specification Voh (high-level, on-state output voltage) Ioh (high-level, on-state output current for each output) Turn on time Turn off time
Inputs Specification VT (input low/high trip threshold)
VT (input high/low trip threshold)
VHYST
IIN @ 27V TPD+ (input low/high debounce filter) TPD- (input low/high debounce filter) VIN (absolute max.)
Selecting an Encoder
Rating Refer to the specifications for your user-side power supply +24V @ .20A (for resistive and inductive loads); +24V @ .10A (for capacitive loads) 500 µs 500 µs
Rating 10.51V (min) 12.5V (typ) 14.61V (max) 6.4V (min) 8.3V (typ) 10.3V (max) 1.9V (min) 4.1V (typ) 6.5V (max) 2.5 mA (max) .2 msec (typ) .2 msec (typ) +75V (max)
The SLC Servo Module system supports Allen-Bradley 845H encoders. Other encoders are compatible if they comply with the specifications listed in the following table.
Publication 1746-6.1.2 - July 2000
Page 29
2-6
Selecting Power Supplies, Encoders, and Drives
Specification
Rating
Maximum channel frequency
Incoming quadrature frequency is limited by the following relationship: FQUAD (Hz) = (3334)(90°–EQ) where: EQ = quadrature error (degrees, electrical) For example, for an 845H encoder with 22° quadrature error, the maximum frequency would be: FQUAD (Hz) = (3334)(90°-22° quadrature error) = 226,712 Hz Important:The maximum quadrature error is a limit, and system design should include acceptable margins.
Maximum axis speed
The SLC Servo Module decodes the incoming encoder feedback in quadrature to extract the maximum resolution with four counts per electrical cycle. The maximum number of encoder counts per second can be determined by: Maximum # of counts/second = 4 counts/cycle × FQUAD The maximum axis speed as limited by the encoder feedback would be: (maximum # of counts/second)(60) (4E)(N) where: E = the number of encoder lines per revolution N = number of revolutions of the encoder per inch or millimeter of axis travel. (For a rotary axis, N = number of revolutions of the encoder per revolution of the axis.) For a linear axis the units are inches or millimeters per minute. For a rotary axis the units are revolutions per minute.
Input signal
Encoder feedback must be differential with 5V compatible output signals, open-collector outputs are not supported (i.e., channels A, B, and Z must have source and sink current capability, 8830 line driver outputs or equivalent). The encoder input must have a 0.00 to 0.80 for off state and 4.75 to 5.25 for on state to encoder common reference.
Input sink current 7 mA (max)
Publication 1746-6.1.2 - July 2000
Marker channel
Gated markers
Cable length
Depends on the user-side power supply. Power voltage at the encoder must be greater than or equal to the power voltage requirement specified by the manufacturer. The minimum power requirement for the 845H is 4.75V, and the maximum limit is 5.25V. To meet the power requirement of the encoder and still attain maximum cable length, you can: • Raise the voltage of the power supply to meet the encoder requirement, but you cannot exceed the 5.25V limit of the control. • Increase the gage of the wire from the termination panel to the encoder (12 AWG maximum).
Page 30
Selecting Power Supplies, Encoders, and Drives
Selecting a Drive
2-7
The SLC Servo Module supports Allen-Bradley 1386, 1388, 1389, 1391, 1392, 1394, and 1398 servo drive systems. References that help you select a suitable drive system appear in the table below. Allen-Bradley Publication Title Drive Number 1386
1386-2.0
DC Servo Drive Product Data Sheet
1388
1388-2.0
DC PWM Servo Drive Product Data Series B
1389
1389-2.0
AC Servo Amplifier System Product Data Sheet
1391
1391-2.0
AC PWM Servo Controller Product Data Sheet
1392
1392-2.1
High Performance AC Drive (460V and 230V) Product Data
1394
1394-2.0
1394 Digital Multi-Axis Motion Control Systems Product Data
1398
1398-2.0
ULTRA Series Product Data
The SLC Servo Module provides a ±10V analog output to one drive amplifier for a velocity command. This analog voltage is 11 bits plus an additional sign bit (12 bits total) and interfaces to drive amplifiers with a 2K through 20K ohm range. Servo drive signal analog out specifications appear in the table below. Specification
Rating
Resolution
12 bits or 4.88 mV/bit
Output voltage swing
±10V
Load range
2K through 20K ohms
Conversion time
100 µs
Output step response (20V swing) • Rise time
110 µs typical
• Overshoot
5% typical
• Settling time
60µs typical
Differential linearity
±1 LSB Max. (monotonic over the entire temperature range)
Output offset voltage
500 µV (max)
Gain error drift
7 LSB (max)
Publication 1746-6.1.2 - July 2000