Page 31
2-8
Selecting Power Supplies, Encoders, and Drives
Publication 1746-6.1.2 - July 2000
Page 32
Chapter
3
Planning Hardware Installation
This chapter provides guidelines regarding your hardware installation and includes the following topics: • Understanding general wiring practices • Routing wires • Classifying your conductors • Placing your SLC Servo Module Refer to your SLC 500 documentation for more information on these topics.
General Wiring Practices
General wiring practices include: • Using shielded cables • Routing wires
Using Shielded Cables For many connections, we recommend shielded cable. Using shielded cables and properly connecting their shields to ground protects against electromagnetic noise interfering with signals transmitted through the cables.
ATTENTION
!
To avoid personal injury or equipment damage caused by unpredictable axis motion in your system, use shielded cable as directed in this manual.
Within a cable, pairs of wires are twisted together. Using a twisted pair for a signal and its return path provides further protection against noise. Shield wires should be terminated at one end only. The termination panel is a convenient place to connect all shield wires while providing the necessary ground connection. 1
Publication 1746-6.1.2 - July 2000
Page 33
3-2
Planning Hardware Installation
Cut the shield wires on the opposite end at the cable jacket and tape it to prevent contact with ground. We also recommend keeping the length of leads that extend beyond the shield as short as possible. In high noise environments, you connect shield wires at both ends of the cable to improve the noise immunity of the system. If this is done, terminate one end of the shield to ground through a 0.1 µf capacitor to avoid ground loops in the system.
Routing Wires
When you plan your wire route, classify wires and cables connecting your SLC Servo Module system using the information in this table. The table also tells you how to classify conductors and route cables. IMPORTANT
Remember to keep low-level signal conductors separate from high-level power conductors.
Follow the practices outlined in Programmable Controller Wiring and Grounding Guideline (publication 1770-4.1) to learn how to route other conductors.
Publication 1746-6.1.2 - July 2000
Page 34
Planning Hardware Installation
Classifying Your Conductors For these wires and cables:
3-3
Use the table below for cable routing guidelines and determining wire and cable functions.
To:
Follow these guidelines for routing inside or outside an enclosure:
AC power lines
• Connect high-power AC I/O lines to AC I/O modules that are rated for high power and high noise immunity. • Connect high-power DC I/O lines to DC I/O modules that are rated for high power or have input circuits with long time constant filters for high noise rejection. They typically connect to devices such as hard-contact switches, relays, and solenoids.
• Route these high-power AC lines with machine power conductors of up to 600V AC (feeding up to 100 hp devices) if this does not violate local codes. • Article 300-3 of the National Electrical Code requires that all conductors (AC and/or DC) in the same raceway are insulated for the highest voltage applied to any one of the conductors in the raceway.
SLC Servo Module cable (1746-HCA) and termination panel wiring
• Connect serial communication cables to programming terminals or data terminals, and connect them from the scanner to remote I/O adapter modules or PLC processors. • Connect low-power AC/DC I/O lines to I/O modules that are rated for low power such as low-power contact-output modules. • Connect low-power DC I/O lines to DC I/O modules that are rated for low power and have input circuits with short time constant filters to detect short pulses. They typically connect to devices such as proximity switches, photo-electric sensors, TTL devices, encoders, motion control devices, and analog devices.
• Properly shield conductors, where applicable, and route them in separate raceways. If conductors must cross power feed lines, they should do so at right angles. • Route these lines at least 1 foot from 110V AC power lines, 2 feet from 240V AC power lines, and 3 feet from 480V AC power lines. • Route these lines at least 3 feet from any electric motors, transformers, rectifiers, generators, arc welders, induction furnaces, or sources of microwave radiation. • If the conductor is in a metal raceway or conduit, that raceway or conduit must be grounded along its entire length.
Placing Your SLC Servo Module
When you plan your SLC Servo Module placement: • Divide modules, as much as possible, into the following types:
•
AC
•
High-level DC
•
Low-level digital DC (TTL, encoder, pulse output)
•
Analog I/O
•
Intelligent I/O modules (for example, the SLC Servo Module)
• Place the SLC Servo Module as close to the SLC processor as possible. • Keep your SLC Servo Module as far away as possible from DC and AC I/O modules. Distance protects the intelligent (CPU-based) modules from the heat and electrical noise of the DC and AC I/O modules.
Publication 1746-6.1.2 - July 2000
Page 35
3-4
Planning Hardware Installation
Publication 1746-6.1.2 - July 2000
•
Place the SLC Servo Module on the left side of the chassis along with other intelligent I/O modules and the CPU.
•
Place DC and AC I/O modules on the right side of the chassis and allow empty slots to remain between them and the SLC Servo Module.
Page 36
Chapter
4
Installing Your SLC Servo Module
This chapter provides guidelines for installing your SLC Servo Module and includes the following topics: • Unpacking and inspecting the SLC Servo Module system • Installing the SLC Servo Module • Grounding the SLC Servo Module • Mounting the termination panel • Connecting the termination panel
Unpacking and Inspecting Your SLC Servo Module System
ATTENTION
!
1
Before removing the contents from the shipping carton, avoid electrostatic discharge that degrades performances and damages the module by doing the following: • Touch a grounded object to eliminate static charge from your body before handling the module. • Wear a wrist strap (for example, catalog number 8000-XESD) that provides a high-resistance path to ground. • Keep the module in its static-shield bag when not in use. For more information about electrostatic discharge and how to guard against it, refer to Guarding Against Electrostatic Damage - Using the ESD Kit (publication 8000-4.5.2).
Publication 1746-6.1.2 - July 2000
Page 37
4-2
Installing Your SLC Servo Module
To verify that you received what you ordered: 1. Check the label on each shipping carton with your order. 2. Check the items received against the bill of lading by matching the equipment nameplate description with the material ordered. IMPORTANT
Installing the SLC Servo Module
Make claims for breakage and damage, whether concealed or obvious, to the carrier as soon as possible after receipt of the shipment. Allen-Bradley gives the buyer reasonable assistance in securing adjustment for damage claims.
The first component you install is the SLC Servo Module. After installation, you connect the other components. Figure 4.1 SLC Servo Module with Door Open
Not used
RUN FDBK/U. PWR CONFIG INV
To Termination Panel
Note: The two switches on back are not used. The table below provides a legend for the SLC Servo Module LEDs.
Publication 1746-6.1.2 - July 2000
When:
This LED is on:
Power is applied
RUN
The feedback signal or user-side power is lost
FDBK/U.PWR
Page 38
Installing Your SLC Servo Module
When:
This LED is on:
An invalid configuration is detected
CONFIG INV
ATTENTION
! ATTENTION
!
4-3
To avoid personal injury, equipment damage, or performance degradation, remove backplane power from the chassis and disconnect the 1746-HCA cable before installing or removing a module.
To avoid damage to a module or backplane connector, do not force modules into the backplane connector.
To insert a module into an I/O chassis: 1. Remove backplane power from the I/O chassis. 2. Remove user-side power from the SLC Servo Module. 3. Disconnect the 1746-HCA cable. 4. Align the larger of the two boards of the SLC Servo Module with the card-edge guide at the bottom of the chassis. 5. Slide the module into the chassis. 6. Press the module firmly to seat it into the backplane connector. 7. Verify that the locking latches on the top and bottom of the chassis hold the module in place. IMPORTANT
The term user-side refers to the control circuitry on the SLC Servo Module card that is powered by customer-supplied power sources and isolated from the control circuitry that is powered by the backplane of an SLC rack.
Publication 1746-6.1.2 - July 2000
Page 39
4-4
Installing Your SLC Servo Module
Grounding the SLC Servo Module
Before you install the rest of the system, you must ground the SLC Servo Module. All of the shields and signal commons (normally floating) are tied to earth ground at a single point. Use the EGND terminal on the termination panel for this purpose. Do not connect shields to earth ground at both ends to avoid causing circuit loops that are susceptible to radiated and coupled noise.
IMPORTANT
Figure 4.2 Typical Grounding and Shielding for the SLC Servo Module System Termination panel
Control Module 1746-HCA cable B a c k p l a n e
Backplane Side
Isolated User Side
User-supplied shielded cable Drive CMD Drive
Twisted pair (x10)
Channel A Axis
Axis
Encoder Channel B
Shielded twisted pair (x3)
Channel Z Encoder PWR
Earth ground through backplane
Overall cable shield
Optional EGND
External power +24V RET see ATTENTION +5V –15V RET
User-side power supply
ATTENTION
! Publication 1746-6.1.2 - July 2000
To avoid unpredictable operation of your SLC Servo Module use a separate +24V power supply and tie the +24V return to the +5V return. (The +5V, +15V, and -15V returns are tied together on the SLC Servo Module.)
Page 40
Installing Your SLC Servo Module
Mounting the Termination Panel
4-5
Refer to the Figure 4.3 and Figure 4.4 when mounting the 1746HT termination panel. To mount the 1746HT termination panel: 1. Snap the termination panel onto the DIN-type rail (1492-DR2). 2. Position an end anchor on either end of the termination panel. 3. Secure the panel by tightening the end anchor screws. The end anchor prevents the termination panel from sliding in either direction on the DIN rail. Figure 4.3 Mounting the Termination Panel DIN Rail End Anchor & Screw D R IV E D R IV E DR RET SHLD
Termination Panel
ENCODER C H A . HI CH A. LO AB SHL D C H B . HI CH B. LO Z SHL D C H Z. HI C H Z. L O E NC O D E R P O W E R
Publication 1746-6.1.2 - July 2000