Page 41

4-6

Installing Your SLC Servo Module

Figure 4.4 Termination Panel and its Dimensions

D R IV E D R IV E DR RET SHLD ENCODER C H A . HI CH A. LO AB SHL D C H B . HI CH B. LO Z SHL D C H Z. HI C H Z. L O E NC O D E R P O W E R +5V RET +15V SHLD E XT PO W ER +5V RET +15V _ RET + - 15V +24 +24 R E T EG ND

292mm (11.5 in.)

A X IS

D R IV E E N A B L E

E S TO P +24 V R ES. PB R ES. PB RESET S T R IN G IN S T R IN G O U T F A S T I/O F I .1 +24V F I .2 +24 F I .3 RET F O .1 174 6H T R E V 0 1 T E R M IN A T IO N P A N E L

70mm (2.75 in.)

Publication 1746-6.1.2 - July 2000

89mm (3.5 in.)

Page 42

Installing Your SLC Servo Module

Connecting the Termination Panel

4-7

After mounting the termination panel, connect it to the SLC Servo Module with the 1746-HCA cable. To connect the termination panel to the SLC Servo Module: 1. Set the locking latches above and below the connector so the latch reads OPEN. 2. Open the door of the SLC Servo Module. 3. Hold the connector as shown in Figure 4.5 (left) and insert it into the D-sub connector on the SLC Servo Module until the connector is seated. 4. Insert a small, flat-edge screwdriver next to the locking latch located between the module door and connector. 5. Slide the locking latch to the right with your screwdriver. 6. Insert the small, flat-edge screwdriver next to the locking latch located between the module door and connector. 7. Slide the locking latch to the left with your screwdriver. 8. Connect the other end of the cable to the 1746-HT termination panel, as shown in Figure 4.5 (right).

Publication 1746-6.1.2 - July 2000

Page 43

4-8

Installing Your SLC Servo Module

Figure 4.5 Connecting the 1746-HCA-Cable Connecting to the 1746-HT

OP EN

Connecting to the 1746-HSRV

1746-HCA Cable

Publication 1746-6.1.2 - July 2000

1746-HCA Cable

Page 44

Chapter

5

Wiring the SLC Servo Module

Overview

After mounting and connecting the termination panel, you wire fast inputs, outputs, and your Estop string to the termination panel when you wire the system power supply, encoders, and drives. This chapter includes the following topics: • Complying with European Union directives • Wiring fast inputs and outputs • Wiring hardware overtravels • Connecting home limit switch as a fast input • Wiring Estop connections • Wiring power supplies • Wiring encoders • Wiring Allen-Bradley drive connections • Connecting the velocity command

Complying with European Union Directives

If this product is installed within the European Union or EEA regions and has the CE mark, the following regulations apply.

EMC Directive If this apparatus is tested to meet Council Directive 89/336 Electromagnetic Compatibility (EMC) in accordance with Article 10 (1), the following standards apply in whole: • EN 50081-2 EMC-Generic Emission Standard, Part 2-Industrial Environment • EN 50082-2 EMC-Generic Immunity Standard, Part 2-Industrial Environment The product described in this document is intended for use in an industrial environment and is not intended for use in a residential, commercial or light industrial environment. IMPORTANT

1

To meet CE requirements, you must use the specified Allen-Bradley cables and termination panel for the SLC Servo Module (catalog number 1746-HSRV).

Publication 1746-6.1.2 - July 2000

Page 45

5-2

Wiring the SLC Servo Module

Wiring Fast Inputs and Outputs

On the termination panel, the +24V DC fast inputs and outputs of the SLC Servo Module are routed from the connector (37-pin D-shell) to the fast I/O connector (7-pin pluggable) on the termination panel. The fast I/O consists of: • Fast inputs FI.1 through FI.3 • Fast output FO.1 • +24V DC and +24V DC return signals We recommend 18 AWG wire for wiring fast I/O because it allows two wires for each connection point. The termination panel accepts 12 AWG wire, but this allows only one wire per point. Figure 5.1 shows a diagram of typical fast I/O connections. For electrical dampening, a snubber is required to filter out electrical spikes. The snubber is used for inductive and comparative loads on the fast output. Figure 5.2 and Figure 5.3 shows equivalent fast input and output circuits. IMPORTANT

Publication 1746-6.1.2 - July 2000

The input device must connect between +24V DC and the appropriate fast input. Fast inputs are +24V DC referenced. The fast output is ground-referenced. The output load must connect between the fast output and ground.

Page 46

Wiring the SLC Servo Module

5-3

Figure 5.1 Typical Fast I/O Connections

E S TO P +2 4 RES. PB RES. PB RESET S T R IN G IN S T R IN G O U T F A S T I /O F I .1 +2 4V F I .2 +2 4V F I .3 RET 14 AWG

F O .1 GND

Electrical Cabinet GND Snubbing is required for inductive and capacitive loads on the fast output.

Capacitive load Current limiting resistor required. Must be placed in series with contact load.

RET F O .1 18173

Publication 1746-6.1.2 - July 2000

Page 47

5-4

Wiring the SLC Servo Module

Figure 5.2 Equivalent Fast Input Circuit

+24V DC

47K W

1746-HCA

11K W

15K W

Control Module

Termination Panel

Figure 5.3 Equivalent Fast Output Circuit

+5V D C

+24V D C

K2 FO .1 1746-HCA

R et

C ontrol Module

Wiring Hardware Overtravels

Termination Panel

Because the system must go into Estop when a hardware overtravel is tripped, do the following to the hardware overtravel limit switches of each axis: • Wire them into the customer Estop string. • Position them outside the software overtravels (see Figure 5.4).

Publication 1746-6.1.2 - July 2000

Page 48

Wiring the SLC Servo Module

5-5

Software Overtravel Limits Software overtravel limits appear in the table below. Name

What it specifies

Default

Range

Software overtravels used

Whether control checks software overtravel limits

Yes

Yes (used) or No (not used)

When you are using a check, the SLC Servo Module tests each program for motion past an overtravel limit before the programmed motion is executed. The SLC Servo Module monitors software overtravel limits continuously during motion. Software overtravels are disabled during homing and are not active until the axis is homed. Software overtravel limits are located inside hardware overtravel limits. Hardware overtravel limits cause Estop when tripped. Figure 5.4 Software Overtravel Limits

-

+

Negative Overtravel Limit W10-W11

Positive Overtravel Limit W8-W9

Negative Hardware Overtravel Limit (causes Estop)

Positive Hardware Overtravel Limit (causes Estop)

IMPORTANT

Connecting Home Limit Switch as a Fast Input

0

Check positive and negative software and hardware overtravel limits only if Overtravels Used (word 0, bit 7) is set.

You can configure the home limit switch to come from the termination panel, or from the backplane by setting configuration word 1, bit 0. The 1 represents termination panel Fast Input 3. The 0 represents

Publication 1746-6.1.2 - July 2000

Page 49

5-6

Wiring the SLC Servo Module backplane input. Though the exact position of home is not important, it is important that the home position is: • A repeatable resting place for the axis when it is not used. • Free of obstruction from another moving axis. To connect a home limit switch: 1. Place the limit switch near the home position that you want. 2. Adjust the encoder so that the marker is approximately 1/2 revolution from the limit switch closure.

IMPORTANT

Wiring Estop Connections

If you do not adjust the encoder, home can be off by one encoder revolution.

The SLC Servo Module detects and controls Estop conditions. Each SLC Servo Module has a separate and independent Estop circuit. Refer to the documentation that came with your drive for recommendations on correctly wiring your external Estop string. A hardware Estop is caused by the following: • Broken wire in the user power cable. • Power-fail signal from chassis backplane. • Watch-dog time-out on SLC Servo Module. • Software Estop conditions. • A contact in the external Estop string or a broken/missing wire opens the string (e.g., when someone pushes the Estop push button). Specifications for Estop relay on the SLC Servo Module appear in the table below.

Publication 1746-6.1.2 - July 2000

Specification

Rating

Maximum contact voltage rating

80V DC max

Operate time

500µs average

Contact bounce less than 200µs average

Contact resistance

150 milliohms average

Contact rating

5.0VA @ 0.35A max

Page 50

Wiring the SLC Servo Module

5-7

Wiring the Estop for a One-Axis System To wire the Estop for a one-axis system connect the following: • Drive enable • Estop reset pushbuttons (Res P.B., Res P.B., and Reset) • Customer Estop String (String In and String Out) ATTENTION

!

To avoid personal injury or hardware damage, develop a fail-safe wiring design for your Estop string.

• An Estop string (Figure 5.5) is connected in series and consists of: • Axis hardware overtravels • Remote Estop • Motor thermal switch • Transformer thermal switch • Drive fault

Wiring for Normal Operation • Wire the Estop inputs for normal operation. • Bench test your SLC Servo Modules. • The Estop Reset pushbutton requires a two-pole single-throw switch.

Maintaining Electrical Continuity • Maintain electrical continuity on the termination panel between the String Out and String In terminals to change from an Estop state to a run state when pressing the Estop Reset pushbutton. • While in the run state, loss of continuity between String Out and String In places the SLC Servo Module in an Estop state. • All motion is inhibited in the Estop state.

Verifying Connections and Operation • Verify that the Estop wiring is connected correctly. • Check the operation of devices wired between String Out and String In. Publication 1746-6.1.2 - July 2000