Page 51
5-8
Wiring the SLC Servo Module
Figure 5.5 Ladder Diagram for a One-Axis System +24V D C R et.
+24V D C
C ontrol Module CR1-1
String Out P2-7
P2-6
String In
CR1
Customer Estop String 1N 4001
Estop Res. P.B. P2-8 Reset
To Estop Reset Request on Control Module
CR1-2
CR1-4 P2-9
To Estop Status on Control Module
IMPORTANT
CR1-3
In this equivalent Estop circuit, P2 is a 25-pin D-shell connector. CR1-2 and CR1-3 are auxiliary contacts of CR1 used in the drive interface. Use them for the drive enable of each drive amplifier. CR1-3 is not always required. For more information, see the drawings that accompany your drive.
Specifications for the CR1 (Allen-Bradley P/N 700-HC 14Z24) appear in the table below.
Publication 1746-6.1.2 - July 2000
CR1 Part Number
Coil
Contact
Arrangement
700-HC 14Z24
24V DC, 650 ohms
3A Resistive, 120V AC
4 form C
Page 52
Wiring the SLC Servo Module
5-9
If you do not use the relay shown in Figure 5.8, verify that your replacement relay has a coil resistance greater than or equal to 650 ohms.
ATTENTION
!
Figure 5.6 Estop Circuitry Diagram for a One-Axis System
Estop Reset Request
Control Module Estop Contacts
Estop Status
7
9
Control Module 8
6
25-Pin D-Shell Connector
Res. P.B.
Termination Panel
+24V
CR 1-4 CR 1-1 Res. P.B. String In
CR 1 String Out
CR 1-2 Reset
CR 1-3
+24V
To Customer Drive Enable Circuit
Refer to Figure 4.1 for Shield Connections String Pilot Cr 2-1
Cable Length Must Not Exceed 10 m (32 feet)
Estop Reset P.B. (Customer-Supplied)
Publication 1746-6.1.2 - July 2000
Page 53
5-10
Wiring the SLC Servo Module
Figure 5.7 String Pilot Connection Drive Fault Contact
Overtravel
Thermal Overload
Remote E-Stop CR2 String Pilot
C ustomer E- stop S tring
To wire Estop connections, refer to wiring diagrams for the drive you are using. The wiring of six different Allen-Bradley compatible drives is shown in the table below. Figure
Wiring Diagram
5.15
1386 DC Servo Drive
5.16
1388 DC PWM Servo Control
5.17, 5.18
1389 AC Servo Amplifier1
5.19, 5.20
1391 AC Servo Control Module Amplifier
5.21
1392 AC Servo Amplifier
5.22, 5.22
1394 AC Servo Control Module Amplifier
5.24 5.25 5.26
1398 ULTRA 100™/200™ Series AC Servo Control Module Amplifiers
1
The 1389 servo drive requires a 115V AC power conductor (K1) to supply main power to the drive amplifier. See the 1389 Servo Amplifier Installation Manual for details
Wiring the Estop for System with Two or More Axes For a system with two or more axes, you must have a termination panel and a SLC Servo Module for each axis. See Figure 5.8 and Figure 5.9 for the ladder diagram and Estop circuitry diagram for these systems. The Estop characteristics for this type of system are: • SLC Servo Modules must be running before the system comes out of Estop. • If an axis drops into Estop, the system drops into Estop. The power capacity of the user-supplied +24V DC power supply determines the number of axes on one Estop string. Each Estop string requires ~ 50 mA of current from the +24V supply. Publication 1746-6.1.2 - July 2000
Page 54
5-11
Wiring the SLC Servo Module
Figure 5.8 Ladder Diagram for a Two-Axes or Three-Axes System +24V DC R eturn
+24V DC
C ontrol Module #1
C ontrol Module #2
C ontrol Module #3
P2-6
CR3-1
P2-7
P2-6
P2-7
To P2-8 Control Module #1 To P2-8 Control Module #2 To P2-8 Control Module #3
P2-6
String Out
String In
CR1
Customer Estop String
P2-7
CR2 Estop Reset Request
CR1-4 To P2 Control Module #1 Estop status P2-9
CR3
CR2-4 To P2 Control Module #2 Estop status P2-9 CR3-4 To P2 Control Module #3 Estop status P2-9
IMPORTANT
P2 is the 25-pin D-shell connector on the SLC Servo Modules.
Specifications for the CR1 (Allen-Bradley P/N 700-HC 14Z24) appear in the table below. CR1 Part Number
Coil
Contact
Arrangement
700-HC 14Z24
24V DC, 650 ohms
3A Resistive, 120V AC
4 form C
IMPORTANT
Use CR1, CR2, and CR3 auxiliary contacts for the drive enable of each drive amplifier. CR2 and CR3 are not always required.
Publication 1746-6.1.2 - July 2000
Page 55
5-12
Wiring the SLC Servo Module
Figure 5.9 Estop Circuitry Diagram for a Two-Axes or Three-Axes System
C ontrol Module #2
C ontrol Module #1
Estop Control’s Reset Estop Request Contacts
Estop Status
Estop Control’s Reset Estop Request Contacts
8
9
8
6
7
6
7
C ontrol Module #3
Estop Status
9
Termination Panel #1
CR1
String In String O ut R eset
R es. P .B.
+2 4 V
CR1-4
CR1-1 R es. P .B.
CR1-2
CR1-3
To Drives C usto mer Estop S tring
Wiring Power Supplies
Publication 1746-6.1.2 - July 2000
Termination P anel #2
CR2 +2 4 V
8
6
Estop Status
7
9
25-pin D-shell connector
25-pin D-shell connector R es. P.B.
Estop Control’s Reset Estop Request Contacts
R es. P .B.
+2 4 V
CR2-4
CR2-1 R es. P .B. String In String O ut R eset
Termination P anel #3
CR3 +2 4 V CR2-2
CR2-3
To Drives
25-pin D-shell connector +2 4 V
CR3-4
CR3-1 R es. P.B. String In String O ut R eset
+2 4 V CR3-2
CR3-3
To Drives Estop Reset P.B. (usersupplied)
Figure 5.10 shows how to wire a power supply for backplane and user-side requirements and a +24V power supply for Estop circuitry to the termination panel.
Page 56
Wiring the SLC Servo Module
5-13
Figure 5.10 Wiring a +5V, ±15V, and a +24V Power Supply
+5V +5V COMM L1
14 AWG
+15V
L2
+/- 15V COMM E X T P O W E R
- 15V
+5 V RET +1 5 V - /+R E T
+24V P o wer Supply
- 15V +2 4 +2 4 R E T EGND
14 AWG AC H I AC LO
+24V +24V R E T 14 AWG (3)
14 AWG
A C Line
Electrical Cabinet Ground Bus
ATTENTION
! Wiring Encoders
To avoid unpredictable operation of your SLC Servo Module, connect the +5V COMM to the +24V COMM. If voltage sources are coming from two separate isolated power supplies, tie the +24V return to the +5V return.
When you wire encoders, use a single, continuous, shielded cable segment. Wire the cable directly from the encoder to the termination panel. Cable length depends on the power supply for the user-side. Voltage at the encoder must be within the voltage requirement limits specified
Publication 1746-6.1.2 - July 2000
Page 57
5-14
Wiring the SLC Servo Module by the manufacturer. Those limits for the 845H are a minimum voltage requirement of 4.75V and a maximum voltage of 5.25V. IMPORTANT
The term user-side refers to the control circuitry on the SLC Servo Module card that is powered by user-supplied power sources and isolated from the control circuitry powered by the backplane of an SLC rack.
To meet the voltage requirement of the encoder and still attain maximum cable length, you can do the following: • Raise the voltage of the power supply to meet the encoder requirement without exceeding the 5.25V limit of the SLC Servo Module, measured at the module. • Increase the gage of the wire connecting the termination panel to the encoder (12 AWG maximum). Figure 5.11 shows a circuit equivalent for channel A. Figure 5.11 Encoder Feedback Equivalent Circuit +5V
A 0.01 microfarads
+
Differential Line Driver
1746-HCA
768 ohms
C h A HI C h A LO
-
221 ohms
A Customer Encoder
768 ohms +5V C ontrol Module
Publication 1746-6.1.2 - July 2000
Termination P anel
Page 58
Wiring the SLC Servo Module
5-15
To operate the encoder, wire the encoder so that marker Z is true at the same time that A and B channels are true. To wire the encoder for consistent homing of the axis, do the following: 1. Obtain the encoder output timing diagram from the vendor’s data sheets. A typical example is shown in Figure 5.12. 2. On the timing diagram, look at marker Z and its complement, marker Z. 3. Determine which signal is low for most of the encoder revolution and pulses high for the marker interval. 4. Wire the signal that was determined in Step 3 to CH Z.HI on the termination panel. 5. Wire the other to CH Z.LO on the termination panel. 6. Look at channel B and its complement, channel B. 7. Wire CH B.HI on the termination panel to the signal that is high for at least part of the marker interval. Depending on the encoder manufacturer, it is possible that both channels meet this requirement. If so, use either one. 8. Wire the complementary remaining phase to CH B.LO on the termination panel. 9. Look at channel A and its complement channel A. 10. Wire the signal that is low for most of the encoder revolution and pulses high for the marker interval to CH A.HI on the termination panel. 11. Wire the complementary signal to CH A.LO on the termination panel.
Typical Vendor Encoder Wiring See your vendor’s encoder literature for the applicable timing diagram.
Publication 1746-6.1.2 - July 2000
Page 59
5-16
Wiring the SLC Servo Module
Figure 5.12 Typical Vendor Encoder Timing Diagram See 1 in table below 1 cycle 90 Hi C hannel A Lo B See 2 in table below Z
O ptional
A
See 3 in table below
B
Z
Wire C H B, CH A, and C H Z to C H B LO, C H A LO and CH Z LO, respectively, on the termination panel.
C C W rotation viewing shaft
Location:
Shows:
1
Channel A is high for at least part of marker interval. You connect this to CH A.HI of the termination panel.
2
High marker interval. You connect this to CH Z.HI of the termination panel.
3
B is high for at least part of marker interval. You connect this to CH B.HI of termination panel.
Encoder Feedback Direction The encoder can spin either CW or CCW for a given table direction and the direction (phasing) of the feedback could be backwards. You can change the direction of the feedback by switching channel A wiring with channel B wiring. For encoder feedback connections, see Figure 5.13 and 5.14.
Publication 1746-6.1.2 - July 2000
Page 60
5-17
Wiring the SLC Servo Module
Figure 5.13 5V Encoder Feedback Connections
ENCODER CH A. HI 1
C H A . LO
A A
A B SH LD CH B. HI 1
C H B. LO
B B
Z SH LD C H Z. HI 1
C H Z . LO
Z
I
3
Optical Encoder
C J
Z
2
RET
A
B
ENCODER POWER +5 V
H
F
D
G
+5V Case Ground
+1 5 V
+5V Return
S H LD
1
Use three pair 22 gauge individually twisted and shielded cable.
2
Use one pair 18 gauge twisted and shielded cable.
3
Encoders must have +5V compatible differential line drive outputs on channels A, B, and Z (DS 8830 or equivalent (845H)).
Figure 5.14 15V Encoder Feedback Connections
ENCODER CH A. HI 1
C H A . LO
A A
A B SH LD CH B. HI 1
C H B. LO
B B
Z SH LD C H Z. HI 1
C H Z . LO
Z Z
ENCODER POWER +5 V 2
I B C
H
A 3
Optical Encoder J G F D
+15V Return
RET
Case Ground
+1 5 V S H LD
+15V
1
Use three pair 22 gauge individually twisted and shielded cable.
2
Use one pair 18 gauge twisted and shielded cable.
3
Encoders must have +5V compatible differential line drive outputs on channels A, B, and Z (DS 8830 or equivalent (845H)).
Publication 1746-6.1.2 - July 2000