Page 161
10-2
Troubleshooting
Hardware Setup
Check wiring to diagram, get the FDBK/UPWR light out. This insures that you have feedback, and all of the required user power. 1. Do you have 0.00 – 0.80 for off state or 4.75 – 5.25 VDC on the encoder signals. 2. Are all of the DC commons tied together and to ground as shown in the manual. 3. Are all of the voltages present 5V, +15V, -15V, 24VDC.
Do a battery box test. (If unable to control drive) 1. This is done by pulling the DRIVE (analog voltage output) plug on the HT panel. 2. Pull the ENABLE plug, and jump the drive enable signal to the drive. 3. Tune the Drive without the HSRV, to insure the drive will accept analog commands. 4. Use a AA 1.5V battery wired between the DRIVE and DR RET(analog voltage). This should make the motor turn in one direction, swap the connections on the battery and the motor should spin in the other direction. At this point the Drive should be tuned, and have turned in both directions with the battery box test. And the FDBK/UPWR light should be off.
Software Setup
Configure the HSRV module Downloading Your Configuration When you download your configuration using the M0 file for the module that you want, the types of data that are included are: • • Discrete parameters • • Floating-point parameters
Publication 1746-6.1.2 - July 2000
Page 162
Troubleshooting
10-3
You can download to the module using two copy file instructions to the M0 file of the SLC Servo Module: • • The first copy file instruction copies discrete information. • • The second copy file instruction copies floating-point information. Depending on the values specified in the configuration, the module accepts the data or generates configuration errors through module input status words.
If CONFIG INV LED is Lit • • Errors are reported in word I:1.4 in decimal format. • • CONFIG INVALID Bit I:1.1/14 (I:1/30) is set.
Configuration Errors The CONFIG INV LED on the SLC Servo Module turns on before or after power-up to indicate an invalid configuration. The configuration error input bit (14) in configuration mode input status word 1 is set and input status word 4 of the module reports the errors detected if any one of the following occurs: • • There is no configuration file. • • The configuration is invalid. Figure 10.1 Rung Example of Download Configuration
Publication 1746-6.1.2 - July 2000
Page 163
10-4
Troubleshooting
The following diagram shows the Data Table with the values in file F8. Figure 10.2 Data table for File F8
The following diagram is of the Data table for file N7. It displays the integer values used in the rung. Figure 10.3 Data Table for file N7
The above config. is for a Y-series servo 4500 rpm motor and 2000 line encoder, units are scaled for the RPM. The bits set in the Integer are basically homing to limit sw. and marker, with the home switch connected to FIN 3 on the HT panel.
Publication 1746-6.1.2 - July 2000
Page 164
Troubleshooting
10-5
Jog the Axis Using the Speed Move Command The speed move command generates a move at the specified speed in the direction determined by the sign of the speed specified. The speed move ends if any one of the following occurs: • • The move reaches an overtravel limit if overtravel limits are specified. • • The SLC processor cancels the move. The Cancel Move bit is used to cancel the speed component of the move. Setting the Cancel Move bit does not affect an Incremental Position command component (i.e., the specified incremental position Command continues unless it is set to zero). • • An Estop occurs. • • The SLC processor sends another move from the mutually exclusive move set including a move of the same type with different % Acceleration Ramp or Speed. Figure 10.4 Ladder Rung For SPEED Move
The following diagram shows the Data table for file F44. Figure 10.5 Data table for File F44
The values for File N31 are listed in the following data table.
Publication 1746-6.1.2 - July 2000
Page 165
10-6
Troubleshooting
Figure 10.6 Data table for File N31
The above configuration is for a SPEED move at 100% accel/decel at 50 (RPM).
Troubleshooting LED Indicators
The RUN, FDBK/U. PWR, and CONFIG INV LED indicators on the SLC Servo Module serve as diagnostic tools for troubleshooting. Refer to the table below for general conditions.
General Condition
Potential Cause
The RUN LED is not green.
Indicates a major SLC Servo Module malfunction or lack of power from the backplane or the user supplies.
The FDBK/U PWR LED is red.
No user power.
The CONFIG INV LED is red.
Using default values or invalid data
Publication 1746-6.1.2 - July 2000
Possible Resolution 1. Check that power is present from the backplane. 2. If power is present, replace the SLC Servo Module. Check user power supply and connections to termination panel. • Check fault word code. • Change parameter. • Reconfigure parameters.
Page 166
Troubleshooting
10-7
The following table shows the status indicators for the LEDs and what action might need to be taken. When the LED status indicators Your system status is: are:
And the action to take is:
RUN FDBK/U.PWR CONFIG INV
On Off Off
System O.K.
Continue
RUN FDBK/U.PWR CONFIG INV
Off Off Off
Power is not applied or there is a catastrophic failure.
Apply power
RUN FDBK/U.PWR CONFIG INV
Off Off On
Hardware failure
1. Troubleshoot
RUN FDBK/U.PWR CONFIG INV
Off On Off
Hardware failure
RUN FDBK/U.PWR CONFIG INV
Off On On
Power-up or RAM failure
2. Repair the hardware that failed 1. Troubleshoot 2. Repair the hardware that failed 1. Verify power supply connections for +24, ±15, +5, and encoder feedback signals 2. Troubleshoot 3. Repair power-up problem or contact Allen-Bradley for RAM failure
RUN FDBK/U.PWR CONFIG INV
On Off On
Configuration not loaded
1. Check your program configuration
RUN FDBK/U.PWR CONFIG INV
On On Off
Feedback fault (broken wire, quadrature fault) or loss of user power
1. Troubleshoot
RUN FDBK/U.PWR CONFIG INV
On On On
Configuration not loaded and loss of user power
1. Check your program configuration
2. Repair your program configuration
2. Repair the feedback wire or the reason for the loss of user power
2. Repair your program configuration 3. Repair the reason for loss of user power
Error Messages and Diagnosis
The following tables provide a numerical listing of informational messages, minor fault messages, and major fault messages accompanied by potential causes and possible resolutions.
Publication 1746-6.1.2 - July 2000
Page 167
10-8
Troubleshooting
Informational Messages Informational Potential Cause Message No.
Possible Resolution
2
Tried to exit Estop after a nonrecoverable Estop has occurred.
1. Remove watchdog disable jumper. 2. Cycle power.
3
A set Initialize Retract Position command was attempted from the SLC processor while the SLC Servo Module was in Estop. The axis is not homed, or the motion is not complete.
• If in Estop, reset Estop. • If not homed, home the axis. • If motion is not complete, wait for the motion to end.
4
Set Retract Position command was attempted from the SLC processor while the SLC Servo Module is in Estop, the axis is not homed, or the motion is not complete.
• If in Estop, reset Estop. • If not homed, home the axis. • If motion is not complete, wait for the motion to end.
5
Set Home command was attempted from the SLC processor while the SLC Servo Module is in Estop, the motion is not complete, or the axis has not seen a marker.
• If in Estop, reset Estop. • If motion is not complete, wait for the motion to end. • If motion is not complete, move the axis equal to the 4* encoder lines count to see the marker.
6
A preset operation was attempted while motion was in progress or while the motion was being held.
1. Unhold motion and/or wait for motion complete. 2. Attempt the preset operation.
7
The Home Axis bit was released before the homing operation was completed, thus the home operation was aborted.
1. Wait for the At Home bit to go true. 2. Release the Home Axis command.
8
The marker was not detected when a move to one electrical revolution (4* Encoder lines) was commanded to detect the marker.
1. Check the marker circuit (Z and Z NOT pulses). 2. Refer to installation section for the encoder signal timing diagrams.
9
The limit switch state changed too fast for the control to detect.
Check the limit switch.
10
The Retract Position command was cancelled by the SLC Servo Module.
Reinitiate the command.
11
The Retract Position command was performed successfully.
N/A
12
The Home command was performed successfully.
N/A
13
An attempt was made to home the axis when the control has been disabled.
Enable the DAC configuration bit (W0-B0).
14
Speed move encountered a software overtravel.
Clear fault and move in the opposite direction.
15
Encoder feedback is marginal. Typically this fault is due to electrical noise coupling onto the feedback lines.
1. Check that the feedback cable is isolated from electrical fields. 2. Check that relays, contactors, and solenoids are adequately suppressed.
16
Absolute move was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
17
Incremental move was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
Publication 1746-6.1.2 - July 2000
Page 168
Troubleshooting
Informational Potential Cause Message No.
10-9
Possible Resolution
18
Speed move was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
19
Monitor move was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
22
Blend move profile was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
25
Home was attempted in Estop.
1. Reset Estop. 2. Reinitiate the command.
26
Absolute move was attempted when not homed.
1. Home the axis. 2. Reinitiate the command.
29
Retract Position command was attempted when not homed.
1. Home the axis. 2. Reinitiate the command.
30
Blend move profile was configured successfully.
N/A
31
Servo configuration was performed successfully.
N/A
32
Servo configuration was attempted when not in Estop.
1. Command Estop. 2. Reinitiate the command.
33
Blend configuration was attempted when not in Estop.
1. Command Estop. 2. Reinitiate the command.
34
Blend move profile was attempted while a profile has not been downloaded.
1. Download a profile. 2. Reinitiate the command.
35
Attempt to download a blend profile with more than 32 blend points.
1. Check the blend profile. 2. Reduce number of blend points.
36
Blend segment exceeded the acceleration limit.
Reduce the acceleration limit to max of 1.0 that is 100% of configured value.
37
Blend segment exceeded the speed limit.
Reduce the segment speed to less than the configured value.
38
Blend segment position specified is less than the negative overtravel limit.
Make blend segment position greater than negative travel limit.
39
Blend segment position specified is greater than the positive overtravel limit.
Make blend segment position less than the positive travel limit.
40
Multiple on-line command bits were attempted at the same time.
Attempt one command bit at a time.
41
More than one move bit was set in command Word 4.
Attempt one command bit at a time.
42
More than one move bit was set in command Word 5.
Attempt one command bit at a time.
43
Ambiguous command was attempted.
• Check ladder logic. • Check the SLC Servo Module command specifications.
44
Unknown command was attempted.
• Check ladder logic • Check the SLC Servo Module command specifications.
Publication 1746-6.1.2 - July 2000
Page 169
10-10
Troubleshooting
Informational Potential Cause Message No.
Possible Resolution
45
Manufacturing test command was issued.
Verify that the SLC processor never initiates this command.
46
Blend move profile was attempted while Incremental Position command is enabled.
Blend move profile command can execute only if the Incremental Position command is disabled.
Minor Fault Messages Minor Fault Potential Cause Message No.
Possible Resolution
1024
Program motion queue is full.
Cycle all power to the SLC Servo Module.
1025
Planned motion queue overflow.
Cycle all power to the SLC Servo Module.
1026
The axis has surpassed the positive or negative overtravel specified in the configuration file.
Program the moves within the overtravels specified.
1027
The programmed position commanded is too large to fit into an internal position variable.
1028
The program speed does not fall within the legal limits; Reprogram the speed within the legal limits. 0 < speed < = Max_Speed, where Max_Speed is a configuration value.
1029
The program acceleration ramp does not fall within the Reprogram the acceleration ramp with the legal limits. legal limits; 0 < acceleration ramp < = 1.0.
1031
The current position of the axis is outside the positive software overtravel and a request to move the axis in the positive direction has been requested from a command file. The operation is disallowed because the positive overtravel would be further violated.
Issue a jog type command in the negative direction until the position of the axis is between the software overtravels.
1032
The current position of the axis is outside the negative software overtravel and a request to move the axis in the negative direction has been requested in a command file. The operation is disallowed because the negative overtravel would be further violated.
Issue a jog type command in the positive direction until the position of the axis is between the software overtravel.
1033
Encoder lines configuration parameter is out of range.
If the range specified is not 1 to 8000 lines, change the parameter specification.
1037
Reversal error value is out of range.
If the reversal error value is greater than the total travel for the axis (i.e., positive overtravel limit - negative overtravel limit), change the parameter specification.
1038
Reversal error value is less than zero.
If the reversal error is not a positive number, change the parameter specification.
1039
Maximum speed is too small.
If the speed specified is less than one feedback count per coarse iteration time or greater than the maximum speed configured, change the parameter specification.
Publication 1746-6.1.2 - July 2000
• Programming error; position calculation must be constrained to physical limits. • During a blend move execution, no valid blend profile number is configured.
Page 170
Troubleshooting
Minor Fault Potential Cause Message No.
Possible Resolution
1040
Speed of move off the limit switch is out of range.
If the speed specified is less than one feedback count per coarse iteration time or greater than the maximum speed configured, change the parameter specification.
1041
Speed of move to marker is out of range.
If the speed specified is less than one feedback count per coarse iteration time or greater than the maximum speed configured, change the parameter specification.
1042
Acceleration time specified is out of range.
If the acceleration time specified is less than coarse iteration time, change the parameter specification.
1043
Home position specified is out of range.
If the home position specified is greater than the positive overtravel limit or less than the negative overtravel limit, change the parameter specification.
1044
Positive travel limit specified is less than the negative travel limit.
Change the parameter specification.
1045
Negative travel limit specified is greater than the positive travel limit.
Change the parameter specification.
1046
Rollover position specified is not equal to zero when overtravels are used.
Set the rollover position to zero.
1047
Home position is outside the rollover range.
Make home position less than the rollover position.
1048
Output voltage at positive max speed is out of range.
Range is 0 to 10.0 Volts.
1049
Output voltage at negative max speed is out of range.
Range is 0 to –10.0 Volts.
1050
The velocity feedforward constant is out of range.
Range is 0 to 1.0.
1051
The acceleration feedforward constant is out of range.
Range is 0 to 1.0.
1052
Reversal error compensation is too big.
Reduce the parameter value.
1053
The maximum speed specified is too small.
If the speed specified is less than one internal unit per iteration, change the parameter specification.
1054
The maximum acceleration specified is too big.
If the acceleration specified requires system to reach maximum speed in less than one coarse iteration, change the parameter specification.
1055
The positive DAC scaling is too big.
Change maximum speed or volts at maximum speed.
1056
The positive DAC scaling is too small.
Change maximum speed or volts at maximum speed.
1057
The negative DAC scaling is too big.
Change maximum speed or volts at maximum speed.
1058
The negative DAC scaling is too small.
Change maximum speed or volts at maximum speed.
1059
The home position specified is out of range.
If the home position cannot be converted to internal resolution units, change the parameter.
1060
The home calibration specified is out of range.
If the home calibration cannot be converted to internal resolution units, change the parameter.
1061
The rollover position specified is out of range.
If the rollover position cannot be converted to internal resolution units, change the parameter.
1062
The maximum gain specified is out of range.
If the maximum gain cannot be converted to internal resolution units, increase the value.
10-11