Page 171

10-12

Troubleshooting

Minor Fault Potential Cause Message No.

Possible Resolution

1063

The excess follower error is out of range.

If the excess FE is too big or too small, change the parameter.

1064

The in position band is out of range.

If the in position band is too big or too small, change the parameter.

1065

The loop type specified is out of range.

Valid loop types for the two bit field are: 00 - Open Loop 10 - FE Loop 01 - ZFE Loop (VFF)

1066

The home type specified is out of range.

Change the parameter.

1067

The positive overtravel limit specified is out of range.

The specified value caused an overflow error when converting the parameter to internal resolution units.

1068

The negative overtravel limit specified is out of range.

The specified value caused an overflow error when converting the parameter to internal resolution units.

1069

The counts per position unit specified is out of range.

The specified value caused an overflow error when converting the parameter to internal resolution units.

1070

The fits per CIT is out of range.

The valid values are: 3 = 4.8 msec 4 = 6.4 msec 5 = 8.0 msec 6 = 9.6 msec

Major Fault Messages Major Fault Potential Cause Message No.

Possible Resolution

2048

Quadrature fault: simultaneous transitions on the A and B channels of the encoder detected. This error causes an Estop state.

Because this fault is typically due to electrical noise coupling onto the feedback lines: 1. Check to make sure the feedback cable is isolated from electrical fields; and all relays, contactors, and solenoids are adequately suppressed. 2. Rehome the system.

2049

The SLC Servo Module detected a feedback fault that causes an Estop state. This occurs if the SLC Servo Module detects one of the following in the same electrical state: • channel A and A • channel B and B • channel Z and Z

Because this fault is typically due to electrical noise coupling onto the feedback lines: 1. Check to make sure the feedback cable is isolated from electrical fields; and all relays, contactors, and solenoids are adequately suppressed. 2. Rehome the system.

2050

The value of the axis following error exceeded the limit established in the configuration file. This can be caused by an obstruction to axis motion, servo wiring error, or loss of feedback channel. This error causes Estop. Reversal error is greater than maximum position following error.

1. Reset from Estop. 2. If the problem persists, check axis mechanics, wiring, and feedback devices. 3. Make reversal error smaller than maximum position following error.

Publication 1746-6.1.2 - July 2000

Page 172

Troubleshooting

Major Fault Potential Cause Message No. 2051

No communication with the SLC Servo Module has occurred within the last 5 seconds. This error causes Estop.

10-13

Possible Resolution 1. Reset from Estop. 2. If the problem occurs again check the SLC processor. Note: Switching from run mode to program mode on the SLC Servo Module also causes this error to appear.

2052

Set on power-up.

Issue a Clear Fault (O:s.1/8) or a Clear all faults (O:s.1/9)

2053

SLC Servo Module requesting Estop.

Turn discrete Estop request off.

2054

The user power supply is shorted or not connected. This error causes Estop.

1. Check the user power and its connections to the SLC Servo Module. 2. After it is fixed, reset from Estop.

2055

The user Estop string has opened.

1. Check that the device that opened the string is functioning properly. 2. Reset from Estop.

2056

Watchdog disable jumper is installed.

2057

The backplane is disabled.

Remove it. • The SLC Servo Module lost backplane communications. • I/O reset was detected. • The backplane was disabled.

Publication 1746-6.1.2 - July 2000

Page 173

10-14

Troubleshooting

Publication 1746-6.1.2 - July 2000

Page 174

Appendix

A

Input/Output Quick Reference

Configuration Output Bit Parameters

Use the following tables to locate word 0, word 1, word 2 and multi-word configuration output bit parameters.

Word 0 Parameters Parameter Name (Parameter Group)

Destination M1 FileLocation

Range

Default

Additional Information

DAC Enable (Servo Loop)

M0:s.0/0

Yes (1) / No (0)

Yes

Move commands are executed but, all motion is inhibited. This parameter is useful for debuggging ladder programs when the servo motor is not hooked up and putting an axis in virtual mode. This lets you use interpolated, incremental, actual or commanded positions to generate the master position commands for the ratioed slave axes in other modules. Use the SLC Ladder to transfer the position information between SLC Servo Modules.

Invert DAC (Servo Loop

M0:s.0/1

Yes (1) / No (0)

No

If the DAC output was positive to make a positive move, after inversion, the DAC output is now negative to make a positive move. This parameter is set up at axis integration time. Refer to the Setting Up Your Servo Module chapter in this manual for more information.

Reverse Feedback (Servo Loop)

M0:s.0/2

Yes (1) / No (0)

No

If the negative incremental feedback position was interpreted as negative motion, after the reversal the negative incremental feedback position is now interpreted as positive motion. This parameter is set up at axis integration time. Refer to the Setting Up Your Servo Module chapter in this manual for more information.

Reserved

M0:s.0/3

1

0

Publication 1746-6.1.2 - July 2000

Page 175

A-2

Input/Output Quick Reference

Parameter Name (Parameter Group)

Destination M1 FileLocation

Range

Default

Additional Information

Loop Type (Servo Loop)

M0:s.0/5, M0:s.0/4

00 - Open Loop, (5=0, 4=0)

Standard

The feedback loop is not closed and incremental position commands are scaled to the DAC output. They are sent as the velocity command voltage to the servo drive that is used to calibrate the drive. The output voltage at + maximum speed and maximum speed are scaled to correspond to the maximum axis speed described later. As a result, you can use the SLC Servo Module to calibrate the drive by downloading a configuration with open loop and executing a speed move at 50% of the maximum axis speed. If the drive is not calibrated, the observed speed returned in the status words is different from the commanded speed. In this case, you can adjust the drive to change the observed speed or change the maximum axis speed to match the commanded speed and observed speed. The procedure above has the same result as running the drive with a known velocity input voltage using the battery box.

01 - Standard Closed Loop, (5=0, 4=1)

The feedback loop is closed with only the proportional action; no velocity feedforward action is added. The servo loop runs with a following error and, if the servo is calibrated, the speed and following error ratio are maintained at the specified gain.

10 - Velocity Feedforward Loop, (5=1, 4=0)

The feedback loop is closed with the velocity feedforward action added to the proportional action. The servo loop runs with zero following error if the velocity feedforward is set to 1.0 and the system is calibrated. Use a velocity and acceleration Feedforward Constant to adjust the amount of following error when using the feedforward loop.

Velocity Time Base (Motion)

M0:s.0/6

Minutes (1) / Seconds (0)

Minutes

If the time base specified is seconds, the speed specified for each move block and configuration parameter is interpreted as position units per second (e.g., 10.0 Inches/Second). If the time base specified is minutes, the speed specified for each move block and configuration parameter is interpreted as position units per minute (e.g., 1000.0 Inches/Minute).

Software Overtravels Used (Axis)

M0:s.0/7

Yes (1) / No (0)

No

If the axis uses the rollover, set this parameter to no. Otherwise, the module flags it as a configuration error.

Reserved

M0:s.0/8

Home Type (Homing)

M0:s.0/10, M0:s.0/9

Publication 1746-6.1.2 - July 2000

0 00 – Homing Without a Limit Switch or Marker, (10=0, 9=0)

Home to Marker (10=0, 9=1)

Specifies that the axis is only homed using the set home command. Refer to Understanding Discrete Block Commands from the SLC processor in this manual.

Page 176

Input/Output Quick Reference

Parameter Name (Parameter Group)

Destination M1 FileLocation

Range

Default

A-3

Additional Information

01 – Homing to a Marker, (10=0, 9=1),

Specifies that the axis is homed by moving to a marker. The two parameters, Final Move to Which Marker? and Final Move to Marker?, specify which marker to move to and whether the final move to the marker is required or not.

10 – Homing to a Limit Switch (10=1, 9=0),

Specifies that the axis is homed only using a limit switch and markers are not used for homing. This can result in a final home position that can be inaccurate as markers are not used for homing.

11 – Homing to a Limit Switch and Marker (10=1, 9=1)

Specifies that the axis is homed using both the limit switch and marker. When the limit switch is found and a move is made to go off the limit switch, the home sequence is identical to home to marker. As a result, the two parameters, Final Move to Which Marker? and Final Move to Marker?, specify which marker to move to and whether the final move to the marker is required or not.

Marker Nearest Start Position (0) / 1 Rev, then Nearest Marker (1)

Marker Nearest Start Position

Marker Nearest Start Position (0) configures the axis to move to the nearest marker from the start position of the final move to the marker of the homing sequence. Move to one (1) revolution of the feedback device in the direction and at the speed specified by the Home Axis command, then stop. The axis then moves to the nearest marker.

Final Move to Marker? M0:s.0/12 (Homing)

Yes (1) / No (0)

Yes

If set, the axis performs the final move to the marker specified by Final Move to Which Marker?. Otherwise, the axis does not perform the final move to the marker specified by Final Move to Which Marker?, but instead assigns the current position of the axis to the configured Home Position ± the distance to the nearest marker. Refer to Homing to a Limit Switch in this manual for alternate usage.

Enable Incremental Position Command (System)

M0:s.0/13

Yes (1) / No (0)

No

If the incremental position command is enabled, the SLC Servo Module does not execute blend profile moves and the appropriate error messages are generated when a profile move is commanded.

Blend Move Profile (System)

M0:s.0/14

Yes (1) / No (0)

No

Mode Flag (System)

M0:s.0/15

Configure (1) / Command (0)

Command

Final Move to Which Marker? (Homing)

M0:s.0/11

1 s = Slot number for the SLC Servo Module

Publication 1746-6.1.2 - July 2000

Page 177

A-4

Input/Output Quick Reference

Word 1 Parameters Parameter Name (Parameter Group) Limit Source (Homing) Synchronized Move Source (Motion) Reserved

Discrete Bit Status Word 0 Definition (System)

Destination M File Location1 M0:s.1/0 M0:s.1/1

M0:s.1/2 through M0:s.1/5 M0:s.1/7, M0:s.1/6

Range

Default

Additional Information

Term Panel (1) / Backplane (0) Term Panel (1) / Backplane (0)

Backplane

Assign the home limit from the termination panel. The limit assignment is: FIN[3] = Home Limit When the Synchronized Move Source is assigned from the termination panel, the synchronized moves are initiated when FIN[3] makes a low to high transition.

Backplane

0

Series, Major Rev, Minor Rev (00)/Blend Move ProfileSegment(01)/ Reserved(10)/ Reserved(11)

Series, Major Rev, Minor Rev

Inhibit Informational Codes (System)

M0:s.1/8

Yes (1) / No (0)

No

Inhibit Minor Fault Codes (System) Inhibit Major Fault Codes (System) Reserved Inhibit Actual Position (System)

M0:s.1/9

Yes (1) / No (0)

No

M0:s.1/10

Yes (1) / No (0)

No

M0:s.1/11 M0:s.1/12

Yes (1) / No (0)

0 No

Inhibit Following Error (System)

M0:s.1/13

Yes (1) / No (0)

No

Inhibit Current Speed (System)

M0:s.1/14

Yes (1) / No (0)

No

Reserved

M0:s.1/15

0 1

Publication 1746-6.1.2 - July 2000 s = Slot number for the SLC Servo Module.

When both bits are zero, the SLC Servo Module provides its Series, Major Revision, and Minor Revision. When Bit 7 is 0 and Bit 6 is 1 the SLC Servo Module provides the blend move profile segment number being executed in the currently running blend move profile. If there is no currently running blend move profile, the SLC Servo Module clears Discrete Bit Status Word 0. Informational codes include axis homed successfully, Retract Position successful, etc. When clear, all informational transactions detected by the SLC Servo Module are reported to the SLC processor. You must clear them using either the Clear Fault or Clear All Faults bit. Inhibiting informational codes provide more time to the SLC Servo Module to execute the motion blocks. However, all errors detected are not reported. Inhibiting minor faults provide more time to the SLC Servo Module to execute the motion blocks. However, all errors detected are not reported. Inhibiting major faults provide more time to the SLC Servo Module to execute the motion blocks. However, all errors detected are not reported. Inhibiting actual position provides more time to the SLC Servo Module to execute the motion blocks. However, the actual position is not reported. Inhibiting following error provides more time to the SLC Servo Module to execute the motion blocks. However, the following error is not reported. Inhibiting current speed provides more time to the SLC Servo Module to execute the motion blocks. However, the current speed is not reported.

Page 178

Input/Output Quick Reference

A-5

Word 2 Parameters Parameter Name (Parameter Group) Fits per CIT (System)

Reserved Reserved

Destination M Range FileLocation1 M0:s.2/0 through 3 to 6 M0:s.2/3

Default

Additional Information

3

One coarse iteration represents the servo loop closure time. The fine iteration time on the SLC Servo Module is 1.6 msec. The default Fits per CIT provides a 4.8 msec servo loop closure time.2

M0:s.2/4 through M0:s.2/15 M0:s.3

0 0 1 s = Slot number for the SLC Servo Module.

2

A small number of Fits per CIT cause a fast servo loop closure time that yields better motion performance on the transitions, but slower communication with the SLC processor. As the number of Fits per CIT increases, motion performance on the transitions degrades, but communication with the SLC processor is slightly enhanced. For blended moves, Fits per CIT must be greater than 4.

Multi-Word Parameters Parameter Name (Parameter Group)

Destination M File Location1

Range

Reserved

Default

Additional Information

0

Encoder Lines (Lines/ Rev) (Feedback)

M0:s.4,s.5

1.0 to 8000

1000.0

Counts per Position Unit (Feedback)

M0:s.6,s.7

1.0 to 16909320.0

4000.0

This parameter specifies a conversion constant that allows the module to convert position units into internal resolution units and vice versa. The module uses 4X encoder decoding (both edges of channel A and B are counted). The count direction is determined from both the direction of the edge and the state of the opposite channel. Channel A leads channel B for increasing count. This is the most commonly used decode mode with incremental encoders, since it provides the highest resolution. Determine the parameters by using known specifications of axis hardware components. For example, if an axis has a 1000-line encoder directly coupled to a 5 pitch lead screw (5 turns per inch) and a position (unit of inches) for programming, the value for the parameter is: Counts per Position Unit = 1000 Lines/Rev x 4 Counts/Line x 5 Revs/Inch = 20000 Counts/Inch. For the position (unit of millimeters) for programming, the value for the parameter is: Counts per Position Unit = 20000/25.4 Counts/Millimeter

Publication 1746-6.1.2 - July 2000

Page 179

A-6

Input/Output Quick Reference

Parameter Name (Parameter Group)

Destination M File Location1

Range

Default

Additional Information

Positive Overtravel Limit (Axis)

M0:s.8,s.9

Negative Overtravel Limit to +axis travel limit

100.0

Value can be positive or negative, but must be more positive than the Negative Overtravel Limit. Control checks this parameter only if the Software Overtravels Used parameter is set to yes. Overtravels are active only after the axis is homed.

Negative Overtravel Limit (Axis)

M0:s.10,s.11

–axis travel limit to Positive Overtravel Limit

–100.0

Value can be positive or negative, but must be more negative than the Positive Overtravel Limit. Control checks this parameter only if the Software Overtravels Used parameter is set to yes. Overtravels are active only after the axis is homed.

Rollover Position (Axis)

M0:s.12,s.13

0.0 to axis travel limit

0.0

If the axis uses the software overtravels, set this parameter to zero. Otherwise, the module flags it as a configuration error.

Home Position – Position Units (Homing)

M0:s.14,s.15

Negative Overtravel Limit to Positive Overtravel Limit

0.0

This parameter allows the Home Position to be defined as a position other than zero.

Home Calibration (Homing)

M0:s.16,s.17

–axis travel limit to +axis travel limit

0.0

This parameter is used to fine tune your Home Calibration. During a homing operation, the axis moves off the home limit switch in the specified direction until the limit switch deactivates. The axis then moves to the home position by moving a distance equal to the sum of: Distance to Nearest Encoder Marker + Home Calibration Value The distance to the nearest encoder marker is in Direction to Move Off Limit Switch.

Speed/Direction of Move Off the Limit Switch – Position Units/Time (Homing)

M0:s.18,s.19

–physical limit to +physical limit

20.0

The Speed/Direction of Move Off the Limit Switch value is signed. The sign specifies the direction the axis moves. As a starting point for module configuration, set the magnitude of the value to 1% of the Maximum Axis Speed.

Speed/Direction of Move to the Marker – Position Units/Time (Homing)

M0:s.20,s.21

–physical limit to +physical limit

20.0

The Speed/Direction of Move to the Marker value is signed. Typically, the sign is ignored. However, there is a special case. The sign specifies the direction the axis moves due to a unique situation during Homing to a Limit Switch and Marker. If a marker is not seen after moving off the limit switch, this parameter specifies both direction and speed to search for the marker. As a starting point for module configuration, set the magnitude of the value to 1% of the Maximum Axis Speed.

0.0 to axis travel limit

0.0

This parameter compensates for positioning inaccuracy caused by mechanical play in the system when the axis changes direction. Home the axis to enable the Reversal Error value.

Reversal Error Value – M0:s.22,s.23 Position Units (Axis)

Publication 1746-6.1.2 - July 2000

Page 180

Input/Output Quick Reference

A-7

Parameter Name (Parameter Group)

Destination M File Location1

Range

Default

Additional Information

Output Voltage at + Max Speed – Volts (Servo Loop)

M0:s.24,s.25

0.0 to 10.0

10.0

This parameter has a default value of (+10.0V). This default uses the full range of the control’s DAC (2048 counts). If you specify a value that is less than the default value, the control scales the number of DAC counts in use accordingly. For example, if you enter +2.5V as the value for this parameter, only 512 counts of the DAC are in use for commanding speed. As a result, the speed resolution for the SLC Servo Module is reduced by a factor of 4. You set up this parameter at axis integration time. Refer to the Setting Up Your SLC Servo Module chapter for more information.

Output Voltage at Max Speed – Volts (Servo Loop)

M0:s.26,s.27

–10.0 to 0.0

–10.0

This parameter has a default value of (–10.0V). This default uses the full range of the control’s DAC (2048 counts). If you specify a value that is less than the default value, the control scales the number of DAC counts in use accordingly. For example, if you enter –2.5V as the value for this parameter, only 512 counts of the DAC are in use for commanding speed. As a result, the speed resolution for the SLC Servo Module is reduced by a factor of 4. You set up this parameter at axis integration time. Refer to the Setting Up Your SLC Servo Module chapter for more information.

Maximum Axis Speed – Position Units/Time (Motion)

M0:s.28,s.29

0.0 to +physical limit

3000.0

This parameter requires the use of Encoder Lines and Counts per Position Unit parameters described in the Feedback Parameters section of thismanual and the rated motor speed. Use this formula to calculate the value for the Maximum Axis Speed Parameter: Maximum Axis Speed in Position Units/Minute = (Motor Rated Speed rpm x 4 x Encoder Lines) / (Counts/Position Unit) The value computed is the absolute maximum speed. Maximum Axis Speed in Position Units/Second = (Maximum Axis Speed in Position Units/Minute / 60.0)

Time to Maximum Axis Speed – seconds (Motion)

M0:s.30,s.31

0.0 to +physical limit

1.0

This parameter specifies how fast an axis accelerates/decelerates to the maximum/minimum axis speed. Select this parameter carefully as axes with large load inertia do not accelerate at the same rate as a motor/drive system at no load. High acceleration/deceleration can cause the axis to vibrate and damage to the axis can occur.

Publication 1746-6.1.2 - July 2000