Page 71
5-28
Wiring the SLC Servo Module because it directly affects how the 1398 is wired to the SLC Servo Module. If Homing to a Marker is:
Go to:
Necessary
Figure 5.24, Wiring Diagram for ULTRA 100 When Not Homing to a Marker and for ULTRA 200 (Manufactured After July 31, 1998) When Homing to a Marker Figure 5.25, Wiring Diagram for F, H, and S series ULTRA 100/200 (Manufactured Before July 31, 1998) When Homing to a Marker Figure 5.26, Wiring Diagram for Y series ULTRA 100/200 (Manufactured Before July 31, 1998) When Homing to a Marker
Not Necessary
Figure 5.24, Wiring Diagram for ULTRA 100 When Not Homing to a Marker and for ULTRA 200 (Manufactured After July 31, 1998) When Homing to a Marker
Wiring the SLC Servo Module when Homing to a Marker Both the ULTRA 100 drive (using any divisible resolution) and the ULTRA 200 drive (using any divisible resolution) require a breakout board (P/N 9101-1392) to interface between the integral encoder (inside the Y, F, or H-series motor) and the SLC Servo Module termination panel. The breakout board allows the SLC Servo Module to read the encoder signals directly from the encoder, instead of from the gate array circuit inside the ULTRA 100/200. If the encoder signals are read from the ULTRA 100/200 (using the gate arrays), the marker signal shifts with respect to the A and B channel on each successive power cycle to the ULTRA 100/200. IMPORTANT
Since the ULTRA 100/200 drive can be configured to use custom motors and custom encoders, the guidelines stated above may not be true for other manufacturers’ motor/encoder combinations. ULTRA 200 drives manufactured after July 31, 1998 do not need the J2 breakout. Look for a mm/yy date code stamped or printed on the Allen-Bradley label, located on the side of each drive unit. For example: Mfg. 1098 indicates the drive was manufactured in October 1998.
Publication 1746-6.1.2 - July 2000
Page 72
Wiring the SLC Servo Module
5-29
Figure 5.24 Wiring Diagram for ULTRA 100 When Not Homing to a Marker and for ULTRA 200 When Homing to a Marker 1746 HSRV/IMC 110 Termination Panel (1746-HT) Drive 2 5
DRIVE DR RET SHLD
7 8
Encoder
9
ENCODER COM ISO +24 VDC A+ ENC A- ENC B+ ENC
CH A.HI CH A.LO A,B SHLD CH B.HI CH B.LO Z SHLD CH Z.HI CH Z.LO Encoder Power +5V RET +15V SHLD Ext Power
J1 Connector
B- ENC 10 Z+, I+ ENC 11 Z-, I- ENC 12 24 VDC COM 13 DRIVE ENABLE 20 FAULT RESET 21 ANALOG CMD + 22 ANALOG CMD 23 DRIVE READY + 24 DIRVE READY 25 +24 VDC 26
24VDC FOR ULTRA 100 ONLY
(P/N 9101-1369)
+5V RET +15V +/- RET -15V +24V +24 RET EGND Drive Fault Reset Drive Enable
Estop Reset PB
Estop
(P/N 9101-1366) for F-, H-, or S- Motors (P/N 9101-1375) for Y Motors Encoder
+24V RES.PB RES.PB RESET STRING IN STRING OUT
Motor
Fast I/O FI.1 +24V FI.2 +24V FI.3 RET FO
Over Travel Limits
Estop PB
F, H, S, and Y Series Motors
1398 ULTRA 100
J2
Motor
J1
Publication 1746-6.1.2 - July 2000
Page 73
5-30
Wiring the SLC Servo Module
Figure 5.25 Wiring Diagram for F, H, and S series ULTRA 100/200 When Homing to a Marker
1746 HSRV/IMC 110 Termination Panel (1746-HT) 2 5 13 20
Encoder
21
CH A.HI CH A.LO A,B SHLD CH B.HI CH B.LO Z SHLD CH Z.HI CH Z.LO
22 23 24 25 26
ENCODER COM ISO +24V DC 24V DC COM DRIVE ENABLE
J1 Connector
Drive DRIVE DR RET SHLD
FAULT RESET ANALOG CMD + ANALOG CMD DRIVE READY + DIRVE READY +24V DC
24V DC for
Encoder Power
ULTRA 100
+5V RET +15V SHLD
J2 Connector
Only 1 2
ENC + (GRAY) ENC - (WHITE/GRAY)
3 4 Ext Power
5 +5V RET +15V +/- RET -15V +24V +24 RET EGND
6 7 8 9 10 11 12
A+ (BLACK) A- (WHITE/BLACK) B+ (RED) B- (WHITE/RED) I+ (GREEN) I- (WHITE/GREEN)
HALL A (WHITE/BROWN) HALL B (BROWN) 14 1 HALL C (WHITE/ORANGE) 15 1 ABS (ORANGE) 16 TS+ (VIOLET) 19 TS- (WHITE/VIOLET) 20
Drive Fault Reset
13
Drive Enable
Estop Reset PB
Estop
ENC + (BLUE) ENC - (BLUE/YELLOW)
FI.1 +24V FI.2 +24V FI.3 RET FO
1398 ULTRA 100 F, H, S Series Motor
Motor
J1
1
Publication 1746-6.1.2 - July 2000
J2
Estop PB
Over Travel Limits
(P/N 9101-1369)
Fast I/O
Motor
(P/N 9101-1371)
(P/N 9101-1365) Encoder
+24V RES.PB RES.PB RESET STRING IN STRING OUT
The encoder feedback cable (P/N 9101-1365 Rev. D) has the orange (ABS B #16) wire and the white/orange (HALL C #15) wire swapped.
Page 74
5-31
Wiring the SLC Servo Module
Figure 5.26 Wiring Diagram for Y series ULTRA 100/200 When Homing to a Marker
1746 HSRV/IMC 110 Termination Panel (1746-HT) 2 5 13 20
Encoder
21
CH A.HI CH A.LO A,B SHLD CH B.HI CH B.LO Z SHLD CH Z.HI CH Z.LO
22 23 24 25 26
ENCODER COM ISO +24 VDC 24 VDC COM
J1 Connector
Drive DRIVE DR RET SHLD
DRIVE ENABLE FAULT RESET ANALOG CMD + ANALOG CMD DRIVE READY + DIRVE READY +24 VDC
24V DC for Encoder Power
ULTRA 100
+5V RET +15V SHLD
J2 Connector
Only 1 2 3 4
Ext Power
5 +5V RET +15V +/- RET -15V +24V +24 RET EGND
6 7 8 9 10 11 12 Drive Fault Reset
13 14
Drive Enable
15
ENC + (GRAY) ENC - (WHITE/GRAY) ENC + (BROWN) ENC - (WHITE/BROWN) ENC + (YELLOW) ENC - (WHITE/YELLOW) A+ (BLACK) A- (WHITE/BLACK) B+ (RED) B- (WHITE/RED) I+ (GREEN) I- (WHITE/GREEN) HALL A (ORANGE) HALL B (WHITE/ORANGE) HALL C (BLUE)
Estop Reset PB
Estop
Motor
Fast I/O FI.1 +24V FI.2 +24V FI.3 RET FO
Over Travel Limits
1398 ULTRA 100
Estop PB
J2
(P/N 9101-1369)
Y Series Motor
(P/N 9101-1371)
(P/N 9101-1373) Encoder
+24V RES.PB RES.PB RESET STRING IN STRING OUT
Motor
J1
Publication 1746-6.1.2 - July 2000
Page 75
5-32
Wiring the SLC Servo Module
Connecting the Velocity Command
Use 18 through 22 gauge shielded/twisted pair wire to connect the analog velocity command output signal (consisting of Drive and DR Ret connections) from the termination panel Drive connector to the corresponding terminals of the various servo drives as shown in Figure 5.15 through Figure 5.23. Connect this signal so that the resulting direction of motion matches the correct direction of motion as you defined it. If you reverse these connections, you reverse the direction the axis moves in response to a given polarity of the velocity command.
ATTENTION
!
Publication 1746-6.1.2 - July 2000
To avoid shorts in the Velocity command circuitry, do not reverse the Drive Out connections of the SLC Servo Module. The drive amplifiers of some vendors only provide a single-ended input for the Velocity command.
Page 76
Chapter
6
Testing Your SLC Servo Module Hardware
Overview
This chapter includes the following topics: • Powering up your SLC Servo Module • Testing Estop wiring • Integrating the axis • Testing home using the home position switch • Testing home using encoder marker
Powering Up Your SLC Servo Module
Before you apply power to the SLC Servo Module: • Wire the AC line on the power supply. • Set the voltage (120V or 240V). • Connect the user-power cables. • Rout the user-power cables. • Connect the wiring from the termination panel to drives, encoders, fast input and output devices, Estop string and Estop reset button. • Connect the cable to the termination panel and the SLC Servo Module with the connectors firmly attached. To power-up your SLC Servo Module: 1. Create a ladder program to avoid memory loss in your SLC 500 Processor when you power up. Only include the rung shown below. Figure 6.1 Ladder Program to Avoid Memory Loss
S:1 8
2. Verify that your power supply connections for +5V DC, ±15V DC, and +24V DC are connected correctly to the termination panel.
1
Publication 1746-6.1.2 - July 2000
Page 77
6-2
Testing Your SLC Servo Module Hardware
3. Apply power to the SLC Rack with the SLC Servo Module installed in the rack. After the control module initializes and performs its quick hardware diagnostics, the green RUN LED should light. IMPORTANT
The green RUN LED must be on before continuing. If the RUN LED does not light, consult the table in the Troubleshooting chapter of this manual.
4. Verify that the SLC Servo Module has power from the SLC Rack backplane and the termination panel. 5. Using your programming device for the SLC processor (RSLogix 500, AI500, or APS software), enter the following program example with the appropriate changes. Figure 6.2 Typical Ladder Program
6. Using the data monitor, change the values in the configuration files to match the default specifications for the SLC Servo Module except for the Encoder Lines and Counts Per Position Unit parameters. For this program example: • Discrete configurations are in the file N7. • Multiword, floating-point parameters are in file F8.
Publication 1746-6.1.2 - July 2000
Page 78
Testing Your SLC Servo Module Hardware
Testing Estop Wiring
6-3
Before you test your Estop wiring:
ATTENTION
To avoid personal injury or hardware damage, uncouple the motor from its load.
! 1. Test your fast I/O. 2. Perform open and closed loop integration of drives and feedback devices. A wiring diagram for the Estop circuit is shown in the following Estop Circuitry figure. Use these connections to check the Estop Reset push-button and each contact on the Estop string. Figure 6.3 Estop Circuitry Axis
Estop Status to Porcessor
Termination Panel +24V
Estop Reset Request to Processor
P2 - 9
CR1
P2 - 8 Software Control
Estop Relay
ER
P2 - 7
Estop Reset P.B.
CR1
Motor Thermal SW
+24V P2 - 6
Axis O vertravel
Drive F ault
R emote Estop
CR1 CR1 Drive Enable Contacts
CR1 Control Module
To check the Estop reset push-button: 1. Uncouple the load from the motor. 2. Disconnect the drive enable contacts. 3. Disconnect the Estop string at the termination panel.
Publication 1746-6.1.2 - July 2000
Page 79
6-4
Testing Your SLC Servo Module Hardware
4. Short the (machine tool) hardware Estop string. 5. Press and hold down the Estop Reset push-button. The following events occur: • SLC Servo Module detects an Estop reset request. • SLC Servo Module closes the software-controlled Estop relay in the SLC Servo Module. • Because the Estop string is shorted, Relay CR1 seals the Estop Reset push-button. 6. Release the Estop reset push-button. The contacts in the Relay CR1 remain closed (in the power-on condition). 7. Verify that the Relay CR1 contacts are closed by doing the following: • Perform a continuity check on one of the drive enable contacts that are normally open. • Check the Relay CR1 contacts visually to see if they are closed. 8. Remove the string-out/string-in jumper. Relay CR1 drops out indicating an Estop condition. 9. Reconnect the Estop string and drive enable to the termination panel to get the system up and running.
IMPORTANT
Publication 1746-6.1.2 - July 2000
Open each contact on the string so that the system goes into Estop.
Page 80
Chapter
7
Setting Up Your SLC Servo Module
Overview
Before performing the procedures given in this chapter, follow the installation procedure supplied with the drive that will be interfaced to the SLC Servo Module. This chapter provides information to help you setup and configure the SLC processor and the SLC Servo Module and includes the following topics: • Understanding the theory of motion control • Powering up the SLC Servo Module • Communicating between the SLC processor and the SLC Servo Module • Entering encoder lines and computing counts • Initializing DAC output voltage for drive symmetry • Setting initial loop type • Defining positive axis movement for the SLC Servo Module • Coarse calibrating drive input scaling to SLC Servo Module DAC output voltage • Fine calibrating of the DAC output voltage scaling • Computing excess following error limit • Selecting loop type • Selecting axis acceleration rate • Determining velocity and acceleration feedforward (for zero following error loop type only) • Setting axis and home specific parameters • Understanding programming conventions • Configuring your SLC processor • Understanding your SLC Servo Module interface • Configuring your SLC Servo Module • Before programming your SLC Servo Module • Downloading your configuration • Understanding configuration errors • Configuring the M0 file data tables • Configuring the M0 file floating-point data tables • Understanding configuration parameters • Homing options
1
Publication 1746-6.1.2 - July 2000