Page 201
Proportional Integral Derivative Instruction
9-29
Output Limiting with Anti-Reset Windup You may set an output limit (percent of output) on the control output. When the instruction detects that the output (CO) has exceeded a limit, it sets an alarm bit (bit 10 for lower limit, bit 9 for upper limit) in word 0 of the PID control block, and prevents the output (CO) from exceeding either limit value. The instruction limits the output (CO) to 0 and 100% if you choose not to limit. Select upper and lower output limits by setting the limit enable bit (bit 3 of control word 0), and entering an upper limit (word 11) and lower limit (word 12). Limit values are a percentage (0 to 100%) of the control output (CO). The difference between selecting output alarms and output limits is that you must select output limiting to enable limiting. Limit and alarm values are stored in the same words. Entering these values enables the alarms, but not limiting. Entering these values and setting the limit enable bit enables limiting and alarms. Anti-reset windup is a feature that prevents the integral term from becoming excessive when the output (CO) reaches a limit. When the sum of the PID and bias terms in the output (CO) reaches the limit, the instruction stops calculating the integral sum until the output (CO) comes back in range. The integral sum is contained in words 17 and 18 of the control block.
The Manual Mode In the manual mode, the PID algorithm does not compute the value of the control variable. Rather, it uses the value as an input to adjust the integral sum (words 17 and 18) so that a bumpless transfer takes place upon re-entering the AUTO mode. To set the manual output level, design your ladder program to write to the CV address when in the manual mode. Note that this number is in the range of 0 to 16383, not 0 to 100. Writing to the CV percent (word 16) with your ladder program has no effect in the manual mode but adversely effects bumpless transfer. The example on the next page shows how you can manually control the control variable (CV) output with your ladder program.
Publication 1747-RM001G-EN-P - November 2008
Page 202
9-30
Proportional Integral Derivative Instruction
PID Rungstate If the PID rung is false, the integral sum (words 17 and 18) is cleared and CV remains in its last state.
I:2.0 ] [ 2
N7:10 (L) 1
I:2.0 ] [ 1
N7:10 (U) 1
N7:10 ] [ 1
I:2.0 ] [ 0
FRD
B3 [OSR] 0
FROM BCD Source
I1:1.0
Dest
N7:0
LIM
MUL
LIMIT TEST Low Lim
MULTIPLY Source A
N7:0
N7:0
Source
16384
100
Dest
Test High
Lim
0
B
N7:2
DDV DOUBLE Source
Notes on Operation
DIVIDE 100
Dest
A 3-digit BCD thumbwheel is wired to an input module at I1:1.0 (range 0-100). A pushbutton wired to I1:2.0/0 accepts the thumbwheel value. A selector switch for auto/manual mode is wired to I1:2.0/1 (auto) and I1:2.0/2 (manual). N7:0 stores the value entered on the thumbwheel switch. N7:2 stores an intermediate calculation. N7:8 is the PID control variable address. N7:10 is the control block address of the PID instruction. N7:26 Percent output is updated automatically by the PID instruction.
N7:8
S:5 (U) 0
LIM LIMIT TEST Low Lim
101
Test
N7:0
High
Lim
B3 ( ) 3
–1
Time Proportioning Outputs For heating or cooling applications, the Control Variable analog output is typically converted to a time-proportioning output. While this cannot be done directly with the processor, you can use the program on the following page to convert the Control Variable to a time proportioning output.
Publication 1747-RM001G-EN-P - November 2008
Page 203
Proportional Integral Derivative Instruction
9-31
In this program, cycle time is the preset of timer T4:0. Cycle time relates to % on-time as follows:
T4:0.PRE is the cycle time % on-time 100% output on-time
Example - Time proportioning outputs
PID PID Control Process Control Control
Block Variable Variable Block Length
N7:2 N7:0 N7:1 23
TON TIMER ON DELAY Timer Time Base Preset Accum
(EN)
T4:0 0.01 1000 0
(DN)
Cycle Time of Output GRT
O:1.0 (U) 0
GREATER THAN Source A T4:0.ACC 0 Source B N7:25 0
T4:0 ] [ DN
T4:0 (RES) NEQ NOT EQUAL Source A Source
N7:25 0 0
B
O:1.0 (L) 0
Control Variable
MUL
N7:2 ] [ 13
MULTIPLY Source A Source
PID Instruction Done Bit
Time Proportioning Output Contacts
B
Dest
N7:1 0 T4:0.PRE 1000 N7:25 0
DDV DOUBLE Source Dest
DIVIDE
Output as a Fraction of Cycle Time
16383 N7:25 0
CLR CLEAR Dest
Clears Minor Error Flag S:5 0
END
Publication 1747-RM001G-EN-P - November 2008
Page 204
9-32
Proportional Integral Derivative Instruction
Notes:
Publication 1747-RM001G-EN-P - November 2008
Page 205
Chapter
10
ASCII Instructions
This chapter contains general information about the ASCII instructions and explains how they function in your application program. Each of the instructions includes information on: • what the instruction symbol looks like. • how to use the instruction.
Table 10.1 ASCII Instruction
1
Instruction Mnemonic
Instruction Name
Purpose
Page
ABL
Test ASCII Buffer for Line
Determine the number of characters in the buffer, up to and including the user configured end of line character(s).
10-6
ACB
Number of ASCII Characters in Buffer
Determine the total number of characters in the buffer.
10-7
ACI
String to Integer
Convert a string to an integer value.
10-8
ACL
ASCII Clear Receive and/or Send Buffer
Clear the receive and/or transmit buffers.
10-9
ACN
String Concatenate
Link two strings into one.
10-11
AEX
String Extract
Extract a portion of a string to create a new string.
10-12
AHL
ASCII Handshake Lines
Set or reset modem handshake lines.
10-13
AIC
Integer to String
Convert an integer value to a string.
10-14
ARD
ASCII Read Characters
Read characters from the input buffer and place them into a string.
10-15
ARL
ASCII Read Line
Read one line of characters from 10-17 the input buffer and place them into a string.
ASC
String Search
Search a string.
10-18
ASR
ASCII String Compare
Compare two strings.
10-19
AWA
ASCII Write with Append
Write a string with user-configured character(s) appended.
10-20
AWT
ASCII Write
Write a string.
10-22
Publication 1747-RM001G-EN-P - November 2008
Page 206
10-2
ASCII Instructions
ASCII Instruction Overview
ASCII instructions are available in SLC 5/03 OS301 and above processors, and all SLC 5/04 and SLC 5/05 processors. There are two types of ASCII instructions. • ASCII port control - these include instructions that use or alter the communication channel for receiving or transmitting data. When using these instructions, the system configuration for channel 0 must be set to “User Mode.” (ABL, ACB, ACL*, AHL*, ARD, ARL, AWA*, AWT*) *may be executed in either user or system mode ASCII port control instructions are queued in the order that they are scanned and are dependent on one another to execute (except ACL which executes immediately). For example, if you have an ARD (ASCII Read instruction) and then an AWT (ASCII Write instruction), the Done bit or the Error bit of the ARD must be set before the AWT can begin executing (even if the AWT was enabled while the processor was executing the ARD). A second ASCII port control instruction cannot begin executing until the first has completed. However, the processor does not wait for an ASCII port control instruction to complete before continuing to execute your ladder program. • ASCII string control - these include instructions that manipulate string data. (ACI, ACN, AEX, AIC, ASC, ASR) ASCII string control instructions execute immediately. They are never sent to the queue to wait their turn for execution.
Protocol Parameter Overview
Listed below are the ASCII protocol parameters that you set via the Channel 0 configuration screens in your programming software. Table 10.2 ASCII Protocol Parameters
Publication 1747-RM001G-EN-P - November 2008
Description
Specification
Baud Rate
Toggles between 110, 300, 600, 1.2K, 2.4K, 4.8K, 9.6K, and 19.2K (additional rate of 38.4K for SLC 5/04 and SLC 5/05 only). The default is 19.2K.
Start Bits
The default is 1 and cannot be changed.
Stop Bits
Options include 1, 1.5, and 2 The default is 1.
Parity
Toggles between None, Odd, and Even. The default is None.
Page 207
ASCII Instructions
10-3
Table 10.2 ASCII Protocol Parameters Description
Specification
Data Bits
Toggles between 7 and 8. The default is 8.
Termination Characters
Allows you to configure up to 2 ASCII characters. The default is CR.
Append Characters
Allows you to configure up to 2 ASCII characters. The AWA instruction adds the characters to the end of every string to serve as termination characters for the receiving device. The default is CR LF.
Using the ASCII Data File Type These are 1-word elements. Assign ASCII addresses as follows. Table 10.3 Addressing Format Format
Explanation A
ASCII file f
File number. A file number between 9 to 255 can be used.
:
Element delimiter e
Element number
/
Bit delimiter b
Bit number
Bit location within the element. Ranges from 0 to 15.
A9:2
Element 2, ASCII file 9
A10:0/7
Bit 7, Element 0, ASCII file 10
Af:e/b
Examples
Ranges from 0 to 255. This is a 1-word element.
Using the String (ST) Data File Type This file type is valid for SLC 5/03 OS301 and higher, SLC 5/04, and SLC 5/05 processors. These are 42-word elements. You can address string lengths by adding a .LEN to any string address (for example, ST17:1.LEN). Valid string data file numbers are 9 to 255. String lengths must be between 0 and 82 bytes. In general, lengths that are outside of this range cause the processor to set the ASCII Error bit (S:5/15) and the instruction is not executed. TIP
You can enter ASCII strings characters either directly into the ST file or as \ followed by the Hex value of the ASCII character. Refer to See Table 10.9 for more information.
Publication 1747-RM001G-EN-P - November 2008
Page 208
10-4
ASCII Instructions
You configure append or end-of-line characters via the Channel Configuration screen. The default append characters are carriage return and line feed; the default end-of-line (termination) character is a carriage return.
TIP
All instructions except ACL and AHL will error if the port is disabled. Assign string addresses as follows.
Table 10.4 Addressing Formats Format STf:e.s/b
Examples
Publication 1747-RM001G-EN-P - November 2008
Explanation ST
String file f
File number. A file number between 9 to 255 can be used.
:
Element delimiter e
Element number
.
Subelement delimiter s
Subelement number Ranges from 0 to 41. Word 0 is the length,.LEN. Words 1 to 41 are entered in as .DATA[0] to .DATA[40]
/
Bit delimiter b
Bit number
Bit location within the element. Ranges from 0 to 15.
ST9:2
Element 2, string file 9
ST9:2.LEN
Length, in bytes of element 2, string file 9
ST9:2.DATA[0]
Word 1 of element 2, string file 9
ST9:2.DATA[0]/15
Bit 15 of word 1 of element 2, string file 9
Ranges from 0 to 255. These are 42-word elements.
Page 209
ASCII Instructions
10-5
Entering Parameters The control element for ASCII instructions includes eight status bits, an error code byte, and two character words. Table 10.5 ASCII Control Element 15
14
13
12
11
10
09
08
07
06
Word 0
EN
EU
DN
EM
ER
UL
IN
FD
Error Code
Word 1
Number of Characters For Sending or Receiving (LEN)
Word 2
Number of Characters Sent or Received (POS)
05
04
03
02
01
00
EN = Enable Bit EU = Queue Bit DN = Asynchronous Done Bit EM = Synchronous Done Bit ER = Error Bit UL = Unload Bit IN = Running Bit (This is the IN Bit in the control data file [R6:].) FD = Found Bit • Found Bit FD (bit 8) indicates that the instruction found the end of line or termination characters in the buffer (applies to ABL and ACB instructions). • Running Bit IN (bit 9) indicates that a queued instruction is executing. • Unload Bit UL (bit 10) ceases instruction operation before (may be queued) or during execution. If this bit is set while an instruction is executing, any data already processed is sent to the destination. Note that the instruction is not removed from the queue; any remaining data is just not processed. You set this bit. • Error Bit ER (bit 11) indicates that an error occurred while executing the instruction, such as a mode change via channel 1, or the instruction was cancelled using the UL bit or ACL instruction. • Synchronous Done Bit EM (bit 12) is set concurrently to a program scan to indicate the completion of an ASCII instruction. • Asynchronous Done Bit DN (bit 13) is set opposite to a program scan when an instruction successfully completes its operation. Note that an instruction can take longer than one program scan to finish executing. • Queue Bit EU (bit 14) indicates that an ASCII instruction was placed in the ASCII queue. This action is delayed if the queue is already filled. The queue may contain up to 16 instructions. • Enable Bit EN (bit 15) indicates that an instruction is enabled due to a false-to-true transition. This bit remains set until the instruction has completed executing or errors.
Publication 1747-RM001G-EN-P - November 2008
Page 210
10-6
ASCII Instructions
Test ASCII Buffer for Line (ABL)
Use the ABL instruction to determine the total number of characters in the input buffer, up to and including the end-of-line characters (termination). This instruction looks for two termination characters that you configure via the ASCII port configuration screen. On a false-to-true transition, the processor reports the number of characters in the POS field of the ASCII control block. The serial port must be configured for User mode.
Entering Parameters ABL Ascii Test For Line Channel 0 Control R16:0 Characters 0 Error 0
EN
Enter the following parameters when programming this instruction.
DN ER
Fixed SLC SLC SLC SLC SLC 5/01 5/02 5/03 5/04 5/05 •
•
•
Output Instruction
• Channel is the number of the RS-232 port (Channel 0). • Control is the area that stores the control register required to operate the instruction. • Characters are the number of characters in the buffer that the processor finds (0-1024). This parameter is display only and resides in word 2 of the control block. • Error displays the hexadecimal error code that indicates why the ER bit was set in the control data file (R6). See page 10-24 error code descriptions.
Example
When the rung goes from false-to-true, the Enable bit (EN) is set. The instruction is put in the ASCII instruction queue, the Queue bit (EU) is set, and program scan continues. The instruction is then executed outside of the program scan. However, if the queue is empty the instruction executes immediately. Upon execution, the Running bit (IN) is set. The processor determines the number of characters (up to and including the end-of-line/termination characters) and puts this value in the position field. The Done bit (DN) is then set. If a zero appears in the POS field, no end-of-line/termination characters were found. The Found bit (FD) is set if the position field was set to a non-zero value. When the program scans the instruction and finds the Done bit (DN) set, the processor then sets the Synchronous Done bit (EM). The EM bit acts as a secondary done bit corresponding to the program scan.
Publication 1747-RM001G-EN-P - November 2008